{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY5132-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY5132-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SY5132-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY5132-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY5132-7CC, 1-pole miniature circuit breaker, C tripping characteristic, rated 32 A at 35 °C, 10 kA DC breaking capacity at 220 V, IP20.","salesMarkdown":"## Derating and ambient conditions The 32 A rating holds at 35 °C; above that, the continuous current must be derated: 29.82 A at 40 °C, 28.67 A at 45 °C, 27.46 A at 50 °C, and 26.21 A at 55 °C. If your panel ambient runs at 50 °C, the effective rating drops about 14% — plan your load margin accordingly. The operating temperature range spans -40 °C to 75 °C, with humidity limits of 95% up to 55 °C, tapering to 35% at 75 °C. Vibration resistance per IEC 60068-2-6: ±1 mm at 5 to 25 Hz and 50 m/s² at 25 to 150 Hz. This covers the typical vibration profile of industrial machinery — motor starters, conveyor panels, and machine-tool enclosures. ## Panel integration and compliance Polarity must be observed on DC circuits — the device is not polarity-agnostic. The 1-pole design does not switch the neutral conductor. Product designation per IEC 81346-2 and DIN EN 61346-2 is letter F (protective device).","metaTitle":"Siemens 5SY5132-7CC SENTRON MCB, 1P, C-32A, 10kA DC","metaDescription":"Siemens 5SY5132-7CC SENTRON miniature circuit breaker, 1-pole, C-curve, 32A at 35°C, 10kA DC breaking capacity, IP20. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SY5132-7CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit-breaker 220 V DC 10kA, 1-pole, C, 32A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P","Number Of Poles":"1","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at DC / rated value":"220 V","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Design Of The Product":"Machine manufacture / industry","acc. to DIN EN 61346-2":"F","at 35 °C / rated value":"32 A","at 40 °C / rated value":"29.82 A","at 45 °C / rated value":"28.67 A","at 50 °C / rated value":"27.46 A","at 55 °C / rated value":"26.21 A","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","Position / Of Power Supply Cord":"Consider polarity","Product Feature / Touch Protection":"Yes","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","at DC / acc. to IEC 60947-2 / rated value":"10 kA","Type Of Voltage / Of The Operating Voltage":"DC","vibration resistance / acc. to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Product Component / Neutral Conductor Switching":"No","operating voltage / at DC / rated value / maximum":"250 V"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/27be8a1ef07a2b9e3972d8be53cea6c9.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=345320&mlfb=5SY5132-7CC"},"ai":{"faq":[{"question":"What are the key ratings of 5SY5132-7CC?","answer":"It is a 1-pole C-curve MCB rated 32 A at 35 °C, with a DC breaking capacity of 10 kA at 220 V per IEC 60947-2. The C-curve trips at 5 to 10 times rated current."},{"question":"Will 5SY5132-7CC drop into a panel specified around 5SY4116-7CV without rewiring?","answer":"Both are 1-pole SENTRON MCBs in the same 18 mm width and similar depth, so the mechanical fit is identical. The key difference is the 5SY5132-7CC is a C-curve device rated 32 A, while the 5SY4116-7CV is a different rating and characteristic — verify your load current and tripping curve before substitution."},{"question":"Where can I buy 5SY5132-7CC?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Contact us with your volume and target price for a current quote."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY5132-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY5132-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}