{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY5150-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY5150-7","canonicalUrl":"https://aoctrl.com/siemens/5SY5150-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SY5150-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY5150-7, miniature circuit breaker, C-curve, 1-pole, 10 kA breaking capacity per IEC/EN 60898-2, 15 kA per IEC 60947-2, rated AC 400 V / DC 220 V, 1 MW width, IP20.","salesMarkdown":"## Siemens 5SY5150-7 — C-curve MCB for universal-current branch circuits It breaks 10 kA per IEC/EN 60898-2 at 400 V AC and 15 kA per IEC 60947-2 at 250 V DC — the higher DC rating matters when clearing faults on control-power or PV-string circuits where DC arc extinction is harder. Rated operating voltage is 400 V AC single-phase (440 V max) and 220 V DC (250 V max). Depth is 76 mm (70 mm installation depth). Mount in any position — no derating for orientation. The IP20 rating applies with connected conductors; the sealable option (padlockable toggle) allows lockout/tagout without an external lockout hasp. Combined top and bottom terminals simplify daisy-chaining busbars or looping feed-through. Halogen-free and silicon-free construction avoids outgassing concerns in sealed enclosures or clean-room panels. The 10 kA rating at 400 V AC (IEC/EN 60898-2) covers most commercial and light-industrial service-entrance fault levels. The 15 kA DC rating per IEC 60947-2 applies at 250 V DC — useful for DC distribution or battery-backed control circuits where the higher interrupting rating avoids cascading failure. Energy limitation class 3 means it lets through less let-through energy (I²t) than class 1 or 2 breakers, improving downstream device protection. Vibration resistance per IEC 60068-2-6 (±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz) covers most machine-mounted and conveyor-line applications. ## Ambient derating and operating limits Humidity derating applies above 55 °C: max 95% RH at 55 °C, dropping to 55% at 70 °C and 35% at 75 °C. In a hot panel near drives or transformers, expect the breaker to carry full rated current only up to 55 °C; above that, the thermal trip element shifts — account for derating in the branch-circuit ampacity calculation.","metaTitle":"Siemens 5SY5150-7 SENTRON MCB, C-Curve, 1P, 10 kA","metaDescription":"Siemens 5SY5150-7 SENTRON miniature circuit breaker, C-curve, 1-pole, 10 kA per IEC/EN 60898-2, 15 kA per IEC 60947-2. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"76 mm","Poles":"1","Width":"18 mm","Height":"90 mm","Mounting":"Quick assembly system","IP Rating":"IP20","Product Status":"Active","Temp Operating Max":"75 °C","Temp Operating Min":"55 °C","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0721aa4edfade3e6811956fb211993d4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=412684&mlfb=5SY5150-7","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SY5150-7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY5150-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY5150-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}