{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY5208-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY5208-6","canonicalUrl":"https://aoctrl.com/siemens/5SY5208-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SY5208-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY5208-6, 2-pole miniature circuit breaker, B-curve, 10 kA (EN 60898) / 15 kA (IEC 60947-2), 400 V AC / 440 V DC, 2 MW.","salesMarkdown":"It is not the right curve for motor circuits or high-inrush capacitive loads; those call for C or D curves. The higher figure under 60947-2 matters when the part is specified for industrial panel duty where fault current at the bus can exceed 10 kA — the 15 kA rating gives headroom without needing an upstream current-limiting device. Rated for both AC and DC operation: 400 V AC (multi-phase or single-phase) and 440 V DC, with a maximum DC operating voltage of 500 V. The DC rating follows EN 60898-2, so it is verified for DC fault interruption — not all MCBs carry a certified DC rating. Sealable terminals are provided, allowing the installer to lock the cover after commissioning. Halogen-free and silicon-free construction, which matters for clean-room or semiconductor-adjacent installations where outgassing must be minimized. The part carries dual certification: IEC/EN 60898-2 for residential and commercial use, and UL 1077 for North American supplementary protection applications.","metaTitle":"Siemens 5SY5208-6 SENTRON MCB, 2P B-Curve, 10kA, 400V AC","metaDescription":"Siemens 5SY5208-6 SENTRON miniature circuit breaker, 2-pole, B-curve, 10 kA per EN 60898, 15 kA per IEC 60947-2. 400 V AC / 440 V DC. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"76 mm","Poles":"2","Width":"36 mm","Height":"90 mm","Mounting":"Quick assembly system","IP Rating":"IP20","Product Status":"Active","Temp Operating Max":"75 °C","Temp Operating Min":"55 °C","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b301c74b08585fa68044a46c1e886b2e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1385699&mlfb=5SY5208-6","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SY5208-6/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY5208-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY5208-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}