{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY5413-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY5413-6","canonicalUrl":"https://aoctrl.com/siemens/5SY5413-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SY5413-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY5413-6, 4-pole miniature circuit breaker, B-curve, 13 A rated at 35 °C, 10 kA breaking capacity per EN 60898, 4 MW width.","salesMarkdown":"The 5SY5413-6: The 13 A rating at 35 °C is the baseline; the datasheet provides a full derating curve — 12.38 A at 40 °C, 12.05 A at 45 °C, 11.73 A at 50 °C, 11.38 A at 55 °C, and 11.02 A at 60 °C. If the breaker lives in a warm enclosure, size up one step or verify the actual ambient against these numbers. For motor or high-inrush loads, a C or D curve would be a better fit. For DC circuits, the same 10 kA applies per EN 60898-2. The 4-pole design (4P) switches all four conductors — three phases plus neutral. This is typical for three-phase loads where the neutral must be switched for isolation, or for TT/TN-S systems where neutral protection is required. The sealable feature (padlockable toggle) allows lockout/tagout per safety procedures. ## Deployment context The breaker carries a degree of pollution 2 rating and overvoltage category II. The product designation per IEC 81346-2 is function code F (protection device).","metaTitle":"Siemens 5SY5413-6 SENTRON MCB, 4P B-Curve 13A 10kA","metaDescription":"Siemens 5SY5413-6 SENTRON miniature circuit breaker, 4-pole, B-curve, 13A rated at 35°C, 10kA breaking capacity per EN 60898. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["4-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"72 mm","title":"5SY5413-6","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Circuit breaker Universal current 880 V DC 400 V AC 10kA, 4-pole, B, 13A max. 1000 V DC","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"4P","Number Of Poles":"4","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"13 A","at DC / rated value":"880 V","protection class IP":"IP20, with connected conductors","Overvoltage Category":"II","Combined Terminal Top":"Yes","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","at 35 °C / rated value":"13 A","at 40 °C / rated value":"12.38 A","at 45 °C / rated value":"12.05 A","at 50 °C / rated value":"11.73 A","at 55 °C / rated value":"11.38 A","at 60 °C / rated value":"11.02 A","Combined Terminal Bottom":"Yes","Suitability For Operation":"universal current","at DC / acc. to EN 60898-2":"10 kA","Number Of Modular Width Units":"4","Tripping Characteristic Class":"B","acc. to EN 60898 / rated value":"10 kA","Position / Of Power Supply Cord":"AC as required, observe DC polarity","Product Feature / Touch Protection":"Yes","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","at DC / acc. to IEC 60947-2 / rated value":"15 kA","Type Of Voltage / Of The Operating Voltage":"AC/DC","vibration resistance / acc. to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Product Component / Neutral Conductor Switching":"No","with multi-phase operation / at AC / rated value":"440 V","operating voltage / at DC / rated value / maximum":"1 000 V","with single-phase operation / at AC / rated value":"440 V","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/555211a68d9336a65bbe8078f4be7136.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=318464&mlfb=5SY5413-6"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SY5413-6?","answer":"10 kA per EN 60898 for AC circuits, and 10 kA per EN 60898-2 for DC circuits."},{"question":"Where can I buy 5SY5413-6?","answer":"Sourced and quoted to order against an RFQ through independent distribution channels. Price and availability are confirmed at quote time."},{"question":"Will 5SY5413-6 drop into a panel specified around 5SY5416-7 without rewiring?","answer":"Both are 4-pole SENTRON MCBs in the same 4 MW footprint (72 mm wide), so the mechanical fit is identical. The difference is the trip curve and rating: 5SY5413-6 is a 13 A B-curve; 5SY5416-7 is a different rating/curve. If the circuit design requires a B-curve at 13 A, the swap is direct. If the original spec called for a different curve or ampacity, verify before substitution."},{"question":"What compliance documentation does Siemens provide for 5SY5413-6?","answer":"The part is designed to EN 60898 and EN 60898-2, carries a pollution degree 2 and overvoltage category II rating, and is halogen-free and silicon-free. Full RoHS/REACH/UL/IEC declarations are available from the manufacturer upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY5413-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY5413-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}