{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY5416-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY5416-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SY5416-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY5416-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY5416-7CC, miniature circuit breaker, 880 V DC, 10 kA, 4-pole, C-curve, 16 A.","salesMarkdown":"## DC-rated MCB for industrial panels It breaks DC faults up to 10 kA per IEC 60947-2. ## DC breaking capacity and voltage The 10 kA DC rating at 880 V suits DC bus or string protection in industrial PV, UPS, or drive-link applications. The maximum operating voltage extends to 1 000 V DC. Vibration resistance per IEC 60068-2-6 at ±1 mm / 5–25 Hz and 50 m/s² / 25–150 Hz confirms it holds up on machinery or near rotating equipment.","metaTitle":"Siemens 5SY5416-7CC SENTRON MCB, 880 V DC, 16 A, C-Curve, 4P","metaDescription":"Siemens SENTRON 5SY5416-7CC miniature circuit breaker, 880 V DC, 16 A, C-curve, 4-pole, 10 kA DC breaking capacity. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["4-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"72 mm","title":"5SY5416-7CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit-breaker 880 V DC 10kA, 4-pole, C, 16A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"4P","Number Of Poles":"4","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","at DC rated value":"880 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"II","Combined Terminal Top":"Yes","Design Of The Product":"Machine manufacture / industry","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"No","Number Of Modular Width Units":"4","Position Of Power Supply Cord":"Consider polarity","Tripping Characteristic Class":"C","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage Of The Operating Voltage":"DC","at DC according to IEC 60947-2 rated value":"10 kA","operating voltage at DC rated value maximum":"1 000 V","at AC according to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Product Extension Installable Supplementary Devices":"Yes"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7e378868f4d7e40b165917aef0a328e7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=425555&mlfb=5SY5416-7CC"},"ai":{"faq":[{"question":"Will 5SY5416-7CC drop into a panel specified around 5SY5416-7 without rewiring?","answer":"Yes — same 4-pole layout, same 4 MW (72 mm) width, same quick-assembly DIN-rail mount, same terminal positions. No rewiring needed; just verify your bus is pure DC (the -7CC is DC-only per)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY5416-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY5416-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}