{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY6006-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY6006-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SY6006-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY6006-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY6006-7CC, miniature circuit breaker compact, 1P+N, 6 A, C-curve, 6 kA per IEC/EN60898-1, 230 V AC, 18 mm width, DIN rail.","salesMarkdown":"It breaks fault currents up to 6 kA per IEC/EN60898-1 at 230 V AC, 50/60 Hz — standard for protecting branch circuits in residential and light commercial panels. The 76 mm depth plus 70 mm installation depth means it clears most standard enclosures without a deep can. If your panel feeds from a transformer with higher available fault current, you'll need to coordinate upstream. Rated insulation voltage is 250 V AC, overvoltage category III, pollution degree 2 — standard for fixed-installation distribution boards. The neutral pole switches with the phase, so it disconnects both conductors on a fault. Power loss runs 1.4 W per pole in hot operation, which matters for thermal derating when you pack multiple units side by side in a small enclosure. ## Integration details Accepts supplementary devices like shunt trips or auxiliary contacts — check the SENTRON accessory catalog for compatibility. Sealable for tamper-proofing in metered or secured installations.","metaTitle":"Siemens 5SY6006-7CC SENTRON MCB, 1P+N, 6A, C-Curve, 6kA, 230","metaDescription":"Siemens SENTRON 5SY6006-7CC miniature circuit breaker, 1P+N, 6A, C-curve, 6kA breaking capacity per IEC/EN60898-1. 18mm wide, DIN rail mount. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SY6006-7CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Standard":"IEC/EN60898-1, GB/T10963.1","description":"CIRCUIT BREAKER, 1MW 230V, 6KA, 1+N-POLE, C, 6A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","lifecycle_stage":"current","Fastening Method":"DIN rail","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"No","Design Of The Product":"Miniature circuit breaker compact","Energy Limitation Class":"3","Combined Terminal Bottom":"No","Suitability For Operation":"Residential buildings/infrastructure","Neutral Conductor Switching":"Yes","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"C","according to EN 60898 rated value":"6 kA","Ambient Temperature During Operation":"-25...45°C: max. 85%rF, 45 60°C: max. 43%rF","Type Of Voltage Of The Operating Voltage":"AC","insulation voltage (Ui) at AC rated value":"250 V","with single-phase operation at AC maximum":"250 V","Value Range Of The Supply Voltage Frequency":"50/60 Hz","vibration resistance according to IEC 60068-2-6":"Yes","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.4 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/937bfe1170b67eb480106a3f12d6b9b9.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=752836&mlfb=5SY6006-7CC"},"ai":{"faq":[{"question":"What compliance standards does the 5SY6006-7CC meet?","answer":"It is designed to IEC/EN60898-1 and GB/T10963.1, which are the governing standards for miniature circuit breakers in residential and similar installations. It carries an overvoltage category III rating and pollution degree 2. The housing is halogen-free and silicon-free."},{"question":"Where can I buy the 5SY6006-7CC and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"Will the 5SY6006-7CC drop into a panel specified for the 5SL6006-7?","answer":"Both are 1-pole 6 A C-curve MCBs from the SENTRON family, sharing the same 18 mm width and DIN-rail mounting. The 5SY series is the higher-spec line with a 6 kA breaking capacity per IEC/EN60898-1, while the 5SL typically carries a lower interrupting rating. If your panel was designed around the 5SL, verify the available fault current — the 5SY6006-7CC will physically fit and electrically work, but it's over-specced for a 3 kA or 4.5 kA system, which is fine. No rewiring needed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY6006-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY6006-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}