{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY6010-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY6010-6","canonicalUrl":"https://aoctrl.com/siemens/5SY6010-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SY6010-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY6010-6, miniature circuit breaker, B characteristic, 10 A, 1+N-pole, 6 kA per EN 60898, 250 V AC, 1 MW wide, halogen-free.","salesMarkdown":"The Siemens 5SY6010-6 is a SENTRON miniature circuit breaker with B-curve tripping, rated 10 A at 30 °C and 230/250 V AC single-phase. The 1+N-pole configuration switches both line and neutral, with the neutral pole opening simultaneously. That matters for any circuit where you want full isolation on a single-width module — saves a slot in a crowded consumer unit or sub-distribution board. B-curve means the magnetic trip fires at 3 to 5 times rated current (30–50 A for this 10 A unit). That is the right characteristic for resistive and general-purpose loads with modest inrush — lighting, heaters, control transformers. Do not use it on motor or drive feeds where the start-up surge would nuisance-trip; that is C or D curve territory. If your panel's prospective short-circuit current exceeds 6 kA, you need a higher-rated MCB or a current-limiting upstream fuse — this unit will not clear a 10 kA fault safely. Rated current derates with ambient temperature: 10 A at 30 °C, 9.5 A at 40 °C, 9.3 A at 45 °C. ## Mechanical fit and panel integration At 18 mm wide (1 modular width), it occupies a single slot. This is normal for indoor panel mounting; do not install in washdown or outdoor locations without an IP-rated enclosure. Touch protection is built in on the line-side terminals.","metaTitle":"Siemens 5SY6010-6 SENTRON MCB, B 10 A, 1+N, 6 kA","metaDescription":"Siemens 5SY6010-6 SENTRON miniature circuit breaker, B-curve, 10 A rated, 1+N pole, 6 kA breaking capacity per EN 60898, 250 V AC. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"76 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Halogen-Free":"Yes","Silicon-Free":"Yes","lifecycle_stage":"current","Fastening Method":"standard rail","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"10 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"No","Design Of The Product":"Miniature circuit breaker compact","Energy Limitation Class":"3","at 30 °C / rated value":"10 A","at 40 °C / rated value":"9.5 A","at 45 °C / rated value":"9.3 A","Combined Terminal Bottom":"No","Suitability For Operation":"Residential buildings/infrastructure","Number Of Modular Width Units":"1","Tripping Characteristic Class":"B","acc. to EN 60898 / rated value":"6 kA","Position / Of Power Supply Cord":"Any","Product Feature / Touch Protection":"Yes","Type Of Voltage / Of The Operating Voltage":"AC","vibration resistance / acc. to IEC 60068-2-6":"Yes","insulation voltage (Ui) / at AC / rated value":"250 V","with single-phase operation / at AC / maximum":"250 V","Product Component / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$122.05","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=277993&mlfb=5SY6010-6","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SY6010-6/alternatives.json"},"ai":{"faq":[{"question":"Will 5SY6010-6 drop into a panel specified around 5SY6013-7 without rewiring?","answer":"Yes, the mechanical footprint is identical — both are 18 mm wide, DIN-rail mounted, 1 MW. The swap is a straight pull-and-replace. Verify the load current and trip curve first; the 5SY6013-7 has different ratings."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY6010-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY6010-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}