{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY6013-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY6013-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SY6013-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY6013-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY6013-7CC, miniature circuit breaker compact, 1 MW 230V, 6kA, 1+N-pole, C-curve, 13A.","salesMarkdown":"The 5SY6013-7CC: The 13 A rating at 30 °C is the headline figure for branch-circuit protection. But note the derating: at 40 °C it drops to 12.35 A, and at 45 °C to 12.09 A. If your panel ambient runs warm — say, above 40 °C — the effective continuous current is lower than the nominal 13 A. The C-curve means the magnetic trip is set to 5–10× In, so it handles motor inrush or transformer energization without nuisance tripping, but still clears a hard short fast. The 6 kA breaking capacity is per EN 60898, which is the residential and commercial standard; for industrial installations requiring IEC 60947-2 ratings, check the SCCR coordination with the upstream device. ## DIN-rail fit and panel integration At 18 mm width it occupies one modular unit, so it fits a standard 18 mm-per-pole distribution board slot. Touch protection is built in. Rated insulation voltage is 250 V AC, with a maximum operating voltage of 250 V AC in single-phase operation.","metaTitle":"Siemens 5SY6013-7CC SENTRON MCB, 1+N-Pole, C-Curve, 13A, 6kA","metaDescription":"Siemens SENTRON 5SY6013-7CC miniature circuit breaker, 1 MW 230V, 6kA breaking capacity, C characteristic, 13A. Current production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SY6013-7CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"CIRCUIT BREAKER, 1MW 230V, 6KA, 1+N-POLE, C, 13A","Halogen-Free":"Yes","Silicon-Free":"Yes","lifecycle_stage":"current","Fastening Method":"standard rail","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"13 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"No","Design Of The Product":"Miniature circuit breaker compact","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","at 30 °C / rated value":"13 A","at 40 °C / rated value":"12.35 A","at 45 °C / rated value":"12.09 A","Combined Terminal Bottom":"No","Suitability For Operation":"Residential buildings/infrastructure","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"6 kA","Position / Of Power Supply Cord":"Any","Product Feature / Touch Protection":"Yes","Type Of Voltage / Of The Operating Voltage":"AC","vibration resistance / acc. to IEC 60068-2-6":"Yes","insulation voltage (Ui) / at AC / rated value":"250 V","with single-phase operation / at AC / maximum":"250 V","Product Component / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c4b202c7e4ce67b74a4baa9ba0b0cb67.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=752839&mlfb=5SY6013-7CC"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SY6013-7CC?","answer":"6 kA per EN 60898. That is the standard breaking capacity for residential and light commercial distribution boards at 230/400 V. For industrial applications requiring higher SCCR, verify coordination with the upstream protective device."},{"question":"Will 5SY6013-7CC drop into a panel specified around 5SY6013-7?","answer":"Yes — the 5SY6013-7CC shares the same 18 mm width, 76 mm depth, DIN-rail mounting, and 1 MW footprint as the broader 5SY6 family. No rewiring or busbar modification is needed for the mechanical fit. The difference is the integrated neutral pole on the -7CC variant versus a standard single-pole unit."},{"question":"What compliance documentation does Siemens provide for 5SY6013-7CC?","answer":"The part carries a CE marking per the Low Voltage Directive and is designed to EN 60898. It is halogen-free and silicon-free. For specific RoHS/REACH declarations or UL recognition, request the manufacturer's declaration of conformity with your RFQ — compliance documentation is provided at order time."},{"question":"Where can I buy 5SY6013-7CC?","answer":"Sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time. Submit an RFQ for a firm price and delivery commitment."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY6013-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY6013-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}