{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY6102-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY6102-6","canonicalUrl":"https://aoctrl.com/siemens/5SY6102-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SY6102-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY6102-6, 1-pole miniature circuit breaker, B tripping characteristic, 6 kA per EN 60898 / 30 kA per IEC 60947-2, 18 mm wide, IP20.","salesMarkdown":"Rated breaking capacity is 6 kA per IEC/EN 60898-1 and 30 kA per IEC 60947-2, so it handles fault currents up to 30 kA at 400 V AC in an industrial installation. The 18 mm width (1 modular unit) snaps onto DIN rail and fits standard enclosure cutouts. ## Breaking capacity — what the ratings mean This MCB is rated for three different fault-current standards. Under EN 60898-1 (household-type coordination) it interrupts 6 kA. Under IEC 60947-2 (industrial coordination) it handles 30 kA at 400 V AC, and 15 kA at 60 V DC. For UL 1077 recognition it carries 5 kA. ## Mounting and integration details Depth is 76 mm (70 mm installation depth behind the panel), width 18 mm (1 modular unit), height 90 mm. Sealable terminals allow lockout/tagout. Halogen-free and silicon-free construction, so it won't outgas corrosive compounds in sealed enclosures. Complies with IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077 / CSA C22.2 No. 235.","metaTitle":"Siemens 5SY6102-6 SENTRON MCB, 1P, B-Curve, 6kA IEC, 30kA IE","metaDescription":"Siemens 5SY6102-6 SENTRON miniature circuit breaker. 1-pole, B-curve, 6kA (EN 60898) / 30kA (IEC 60947-2) breaking capacity. Current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SY6102-6","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Standard":"IEC / EN 60898-1, IEC / EN 60947-2 / UL1077","description":"Miniature circuit breaker 230/400 V 6kA, 1-pole, B, 2A, D=70 mm","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P","Number Of Poles":"1","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","at AC rated value":"400 V","at DC rated value":"60 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Energy Limitation Class":"3","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"No","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"B","according to EN 60898 rated value":"6 kA","according to IEC 60947-2 rated value":"30 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage Of The Operating Voltage":"AC","at DC according to IEC 60947-2 rated value":"15 kA","Value Range Of The Supply Voltage Frequency":"50/60 Hz","operating voltage at DC rated value maximum":"72 V","with multi-phase operation at AC rated value":"440 V","with single-phase operation at AC rated value":"440 V","at AC according to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","supply voltage with single-phase operation at AC rated value":"230 V","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.5 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$8.38","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/efcefbdc94c19a3f5a420783c35e503d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=83332&mlfb=5SY6102-6"},"ai":{"faq":[{"question":"Where can I buy 5SY6102-6?","answer":"This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time."},{"question":"What is 5SY6102-6's breaking capacity?","answer":"6 kA per EN 60898-1, 30 kA per IEC 60947-2 at 400 V AC, 15 kA at 60 V DC, and 5 kA per UL 1077."},{"question":"What standards does 5SY6102-6 comply with?","answer":"It complies with IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077 / CSA C22.2 No. 235."},{"question":"What is the width of 5SY6102-6?","answer":"18 mm, which is 1 modular unit on DIN rail."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY6102-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY6102-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}