{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY6102-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY6102-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SY6102-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY6102-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY6102-7CC, 1-pole miniature circuit breaker, C-curve, 2 A rated, 6 kA breaking capacity per EN 60898, 440 V AC max, 18 mm wide.","salesMarkdown":"The Siemens 5SY6102-7CC is a SENTRON miniature circuit breaker (MCB) — a 1-pole unit with a C-curve tripping characteristic, rated 2 A at 440 V AC single-phase or multi-phase, and a 6 kA breaking capacity per EN 60898. That C-curve means it's designed for moderate inrush loads like motor starters or small transformers: the magnetic trip activates between 5 and 10 times rated current, so it holds through a brief start-up surge but clears a hard fault fast. The 6 kA rating is the maximum prospective fault current it can safely interrupt at 440 V AC — enough for most sub-distribution boards in commercial or light industrial panels. ## Panel fit and environmental range Width is 18 mm (one modular unit), depth 76 mm, height 90 mm. Snaps onto DIN rail via the quick-assembly system; mounting position is any orientation. The IP20 rating (with connected conductors) is standard for enclosed distribution boards — not for wet or outdoor locations. Ambient temperature range is -40 °C to 75 °C, with derated current values above 35 °C: 1.88 A at 40 °C, 1.82 A at 45 °C, 1.75 A at 50 °C, 1.68 A at 55 °C. Pollution degree 3 and overvoltage category III suit it for fixed installations where transient overvoltages are expected.","metaTitle":"Siemens 5SY6102-7CC SENTRON MCB, 1P C-curve 2 A, 6 kA","metaDescription":"Siemens 5SY6102-7CC SENTRON miniature circuit breaker, 1-pole, C-curve, 2 A rated, 6 kA breaking capacity per EN 60898. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SY6102-7CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 230/400 V 6kA, 1-pole, C, 2A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P","Number Of Poles":"1","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","at AC rated value":"2 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","at 35 °C rated value":"2 A","at 40 °C rated value":"1.88 A","at 45 °C rated value":"1.82 A","at 50 °C rated value":"1.75 A","at 55 °C rated value":"1.68 A","Energy Limitation Class":"3","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"No","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"C","according to EN 60898 rated value":"6 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage Of The Operating Voltage":"AC","Value Range Of The Supply Voltage Frequency":"50/60 Hz","operating voltage at DC rated value maximum":"72 V","with multi-phase operation at AC rated value":"440 V","with single-phase operation at AC rated value":"440 V","at AC according to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","supply voltage with single-phase operation at AC rated value":"230 V","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.2 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c9d6265fd9c6fada2e0e5e71f81fc03e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=401575&mlfb=5SY6102-7CC"},"ai":{"faq":[{"question":"Where can I buy 5SY6102-7CC and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."},{"question":"What is 5SY6102-7CC's listed depth (76 mm) on this component line?","answer":"The depth is 76 mm, with an installation depth of 70 mm. Width is 18 mm (1 modular unit), height 90 mm."},{"question":"Will 5SY6102-7CC drop into a panel that was specified around 5SY4101-7CV without rewiring?","answer":"Both are 1-pole, 18 mm wide MCBs on DIN rail, so the physical footprint is identical. The 5SY6102-7CC is a C-curve 2 A unit; the 5SY4101-7CV is a different rating and curve — check the specific load and trip coordination before swapping. No rewiring needed for the same busbar position if ratings match."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY6102-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY6102-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}