{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY6201-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY6201-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SY6201-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY6201-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON miniature circuit breaker, 5SY6201-7CC, 2-pole, 1 A rated, C characteristic, 6 kA per EN 60898, 440 V AC, 50/60 Hz.","salesMarkdown":"It breaks fault currents up to 6 kA per EN 60898 at 440 V AC, 50/60 Hz. The 5SY6201-7CC occupies 2 modular width units (36 mm) on a DIN rail, with a depth of 76 mm and height of 90 mm. Installation depth is 70 mm. ## Thermal and environmental limits The breaker derates above 35 °C: at 40 °C the rated current drops to 0.92 A, at 45 °C to 0.88 A, at 50 °C to 0.83 A, and at 55 °C to 0.78 A. Relative humidity limits are 95% up to 55 °C, 55% up to 70 °C, and 35% at 75 °C. Protection class is IP20 with connected conductors — not for wet washdown areas.","metaTitle":"Siemens SENTRON 5SY6201-7CC MCB, 1A, C-Curve, 2-Pole, 6kA","metaDescription":"Siemens SENTRON 5SY6201-7CC miniature circuit breaker, 1A rated, C tripping characteristic, 2-pole, 6kA breaking capacity per EN 60898. 440V AC, 50/60 Hz. Active production. Availa","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","title":"5SY6201-7CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 400 V 6kA, 2-pole, C, 1A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","at AC / rated value":"1 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Energy Limitation Class":"3","according to EN 61346-2":"F","at 35 °C / rated value":"1 A","at 40 °C / rated value":"0.92 A","at 45 °C / rated value":"0.88 A","at 50 °C / rated value":"0.83 A","at 55 °C / rated value":"0.78 A","Combined Terminal Bottom":"Yes","according to IEC 81346-2":"F","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"No","Number Of Modular Width Units":"2","Tripping Characteristic Class":"C","Position / Of Power Supply Cord":"Any","according to EN 60898 / rated value":"6 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage / Of The Operating Voltage":"AC","Value Range / Of The Supply Voltage Frequency":"50/60 Hz","with multi-phase operation / at AC / rated value":"440 V","operating voltage / at DC / rated value / maximum":"72 V","vibration resistance / according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","with single-phase operation / at AC / rated value":"440 V","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/82f36b361177f5a39d6983b2609a2245.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=370886&mlfb=5SY6201-7CC"},"ai":{"faq":[{"question":"Where can I buy 5SY6201-7CC and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time."},{"question":"What is the depth of 5SY6201-7CC?","answer":"The depth is 76 mm, with an installation depth of 70 mm."},{"question":"What is the width of 5SY6201-7CC?","answer":"The width is 36 mm, which corresponds to 2 modular width units on a DIN rail."},{"question":"Will 5SY6201-7CC drop into a panel specified around 5SY4301-7CV without rewiring?","answer":"Both are 2-pole SENTRON MCBs with the same 36 mm width and DIN-rail mounting, so the footprint matches. However, the 5SY4301-7CV is a 1 A B-curve breaker, while this is a C-curve — the tripping characteristic differs. If the panel's branch requires a C-curve for moderate inrush, the 5SY6201-7CC is a direct dimensional swap; no rewiring needed for the busbar or terminal connections."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY6201-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY6201-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}