{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY6202-6CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY6202-6CC","canonicalUrl":"https://aoctrl.com/siemens/5SY6202-6CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY6202-6CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY6 series, miniature circuit breaker, 2-pole, B characteristic, 6 kA (EN 60898), 400 V AC, 72 V DC, 36 mm width (2 MW), IP20, sealable.","salesMarkdown":"The Siemens 5SY6202-6CC is a 2-pole miniature circuit breaker from the SENTRON 5SY6 series, designed for 400 V AC (single- or multi-phase) with a B tripping characteristic and a 6 kA breaking capacity per EN 60898. It also carries a 5 kA rating per UL 1077 and CSA C22.2 No.235, so it's accepted in North American panels alongside the European spec. The 6 kA breaking capacity at 400 V AC (EN 60898) tells you it can safely interrupt a fault up to that level without upstream damage; the 5 kA rating under UL 1077 covers North American installations. Rated for 72 V DC maximum, so it handles DC control circuits within that limit. Rated for ambient temperatures from -40 °C to 75 °C, with humidity influence specified up to 95% at 55 °C, tapering to 35% at 75 °C — important for outdoor or unconditioned enclosures. Vibration resistance per IEC 60068-2-6 covers ±1 mm at 5 to 25 Hz and 50 m/s² at 25 to 150 Hz, so it holds up on machinery with moderate vibration. The IP20 protection (with connected conductors) is typical for panel-mount breakers; the sealable feature and halogen-free / silicon-free construction suit environments where outgassing or contamination is a concern.","metaTitle":"Siemens 5SY6202-6CC SENTRON MCB, 2-pole, B-curve, 6 kA","metaDescription":"Siemens 5SY6202-6CC SENTRON miniature circuit breaker, 2-pole, B tripping characteristic, 6 kA per EN 60898, 400 V AC, 72 V DC max. Active production. Sourced to order. Request quo","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","title":"5SY6202-6CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 400 V 6kA, 2-pole, B, 2A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","at AC rated value":"400 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Energy Limitation Class":"3","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"No","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"B","according to EN 60898 rated value":"6 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage Of The Operating Voltage":"AC","Value Range Of The Supply Voltage Frequency":"50/60 Hz","operating voltage at DC rated value maximum":"72 V","with multi-phase operation at AC rated value":"440 V","with single-phase operation at AC rated value":"440 V","at AC according to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.5 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/325fe357c07982df9e22d0888c799867.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=464005&mlfb=5SY6202-6CC"},"ai":{"faq":[{"question":"Where can I buy 5SY6202-6CC and get a price?","answer":"The 5SY6202-6CC is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time."},{"question":"What is the breaking capacity of 5SY6202-6CC?","answer":"It is rated 6 kA per EN 60898 at 400 V AC, and 5 kA per UL 1077 and CSA C22.2 No.235. This covers most residential, commercial, and light industrial branch-circuit fault levels."},{"question":"What compliance documentation does Siemens provide for 5SY6202-6CC?","answer":"The part carries approvals per EN 60898, UL 1077, and CSA C22.2 No.235. It is halogen-free and silicon-free. Standard Siemens documentation includes RoHS and REACH declarations; request these with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY6202-6CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY6202-6CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}