{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY6202-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY6202-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SY6202-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY6202-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY6202-7CC, 2-pole miniature circuit breaker, C tripping characteristic, 6 kA interrupting capacity per EN 60898, 400 V AC rated voltage, 2 modular width units.","salesMarkdown":"Rated 400 V AC at 50/60 Hz, it fits distribution boards where a 2-module-width (36 mm) device is specified. Under UL 1077 and CSA C22.2 No. 235, the same breaker is rated 5 kA, so verify which standard governs your panel's SCCR calculation. The C-curve (5–10× In) avoids nuisance tripping on capacitor-switching or motor-starting transients while still protecting downstream wiring. Power loss is 1.2 W per pole in hot operating state — negligible in a single device, but relevant when packing 20+ breakers in a sealed enclosure for thermal derating calculations. The sealable design allows lockout/tagout for isolation — a practical detail for maintenance procedures. The part carries no UL/CSA listing on the evidence, but the UL 1077 / CSA C22.2 No. 235 rating (5 kA) indicates it is recognized for North American supplementary protection applications.","metaTitle":"Siemens 5SY6202-7CC SENTRON MCB, 2P C-curve, 6 kA","metaDescription":"Siemens 5SY6202-7CC SENTRON miniature circuit breaker, 2-pole, C characteristic, 6 kA per EN 60898, 400 V AC. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"76 mm","Poles":"2","Width":"36 mm","Height":"90 mm","Mounting":"Quick assembly system","IP Rating":"IP20","Product Status":"Active","Temp Operating Max":"75 °C","Temp Operating Min":"55 °C","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/44261380df6553fff15f2105806c71be.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=447132&mlfb=5SY6202-7CC","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SY6202-7CC/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY6202-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY6202-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}