{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY6213-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY6213-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SY6213-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY6213-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY6213-7CC miniature circuit breaker, 2-pole, C-curve, 13 A rated, 6 kA breaking capacity per EN 60898, 5 kA per UL 1077.","salesMarkdown":"## Panel fit and protection profile The Siemens 5SY6213-7CC is a 2-pole SENTRON miniature circuit breaker with C-curve tripping characteristic, rated 13 A at 50/60 Hz. Breaking capacity is 6 kA per EN 60898 and 5 kA per UL 1077 / CSA C22.2 No.235, so it handles typical branch-circuit fault levels in commercial and light industrial panels. Rated current holds at 13 A up to 35 °C ambient. Above that, derate linearly: 11.95 A at 40 °C, 11.38 A at 45 °C, 10.78 A at 50 °C, 10.15 A at 55 °C. Maximum operating temperature is 75 °C; minimum is -40 °C. ## Approvals and documentation Rated and marked per EN 60898 (6 kA) and UL 1077 / CSA C22.2 No.235 (5 kA). IP20 protection with connected conductors. The breaker is sealable, which allows panel builders to lock settings after commissioning. Compliance documentation (CE, RoHS, REACH) is standard for the SENTRON series.","metaTitle":"Siemens 5SY6213-7CC SENTRON MCB, 2P C-curve 13 A, 6 kA","metaDescription":"Siemens 5SY6213-7CC SENTRON miniature circuit breaker, 2-pole, C-curve, 13 A rated, 6 kA breaking capacity per EN 60898. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","title":"5SY6213-7CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 400 V 6kA, 2-pole, C, 13A","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","Type Of Voltage":"AC","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"13 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Number Of Poles / Note":"2P","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","at 35 °C / rated value":"13 A","at 40 °C / rated value":"11.95 A","at 45 °C / rated value":"11.38 A","at 50 °C / rated value":"10.78 A","at 55 °C / rated value":"10.15 A","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Number Of Modular Width Units":"2","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"6 kA","Position / Of Power Supply Cord":"Any","Product Feature / Touch Protection":"Yes","Supply Voltage Frequency / Rated Value":"50/60 Hz","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","at AC / acc. to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance / acc. to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Product Function / Neutral Conductor Switching":"No","with multi-phase operation / at AC / rated value":"440 V","operating voltage / at DC / rated value / maximum":"72 V","with single-phase operation / at AC / rated value":"440 V","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fac3e6b5376e8ae212e6fe7b2bd0b2d6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=485339&mlfb=5SY6213-7CC"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 5SY6213-7CC?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time — no automated figures are published here."},{"question":"What is the closest functional second-source to 5SY6213-7CC?","answer":"The 5SY7210-7CC is a functional peer within the same SENTRON family, but verify your specific rating and curve requirements before substituting. The 5SY6213-7CC is a 2-pole C-curve 13 A; the 5SY7210-7CC may differ in poles or current rating."},{"question":"Will 5SY6213-7CC drop into a panel specified around 5SY7210-7CC?","answer":"Both are SENTRON MCBs on the same DIN-rail footprint, so mechanical fit is identical. However, verify the electrical ratings — poles, current, and curve — match your branch-circuit protection requirements before swapping."},{"question":"What compliance documentation does Siemens provide for 5SY6213-7CC?","answer":"Standard SENTRON documentation includes CE declaration, RoHS and REACH compliance, and the datasheet with EN 60898 and UL 1077 ratings. No custom certificates are provided with this catalog line."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY6213-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY6213-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}