{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY6213-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY6213-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SY6213-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY6213-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY6213-7CC miniature circuit breaker, 2-pole, C-curve, 13 A rated, 6 kA breaking capacity per EN 60898, 5 kA per UL 1077.","salesMarkdown":"## Panel fit and protection profile The Siemens 5SY6213-7CC is a 2-pole SENTRON miniature circuit breaker with C-curve tripping characteristic, rated 13 A at 50/60 Hz. Breaking capacity is 6 kA per EN 60898 and 5 kA per UL 1077 / CSA C22.2 No.235, so it handles typical branch-circuit fault levels in commercial and light industrial panels. Rated current holds at 13 A up to 35 °C ambient. Above that, derate linearly: 11.95 A at 40 °C, 11.38 A at 45 °C, 10.78 A at 50 °C, 10.15 A at 55 °C. Maximum operating temperature is 75 °C; minimum is -40 °C. ## Approvals and documentation Rated and marked per EN 60898 (6 kA) and UL 1077 / CSA C22.2 No.235 (5 kA). IP20 protection with connected conductors. The breaker is sealable, which allows panel builders to lock settings after commissioning. Compliance documentation (CE, RoHS, REACH) is standard for the SENTRON series.","metaTitle":"Siemens 5SY6213-7CC SENTRON MCB, 2P C-curve 13 A, 6 kA","metaDescription":"Siemens 5SY6213-7CC SENTRON miniature circuit breaker, 2-pole, C-curve, 13 A rated, 6 kA breaking capacity per EN 60898. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"76 mm","Poles":"2","Width":"36 mm","Height":"90 mm","Mounting":"Quick assembly system","IP Rating":"IP20","Product Status":"Active","Temp Operating Max":"75 °C","Temp Operating Min":"55 °C","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fac3e6b5376e8ae212e6fe7b2bd0b2d6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=485339&mlfb=5SY6213-7CC","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SY6213-7CC/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY6213-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY6213-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}