{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY6232-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY6232-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SY6232-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY6232-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY6232-7CC miniature circuit breaker, 2-pole, C-curve, 32 A rated, 6 kA breaking capacity per EN 60898, 440 V AC, IP20.","salesMarkdown":"## Siemens SENTRON 5SY6232-7CC — 2-pole C-curve MCB, 32 A, 6 kA It's a 2-pole unit with a C-curve tripping characteristic, rated 32 A at 40 °C and 6 kA breaking capacity per EN 60898. ## Sizing and thermal derating — what the 32 A rating really means The 32 A rating holds at 35 °C ambient. At 40 °C it derates to 30.08 A; at 45 °C to 29.09 A; at 50 °C to 28.03 A; at 55 °C to 26.94 A. Plan your load accordingly, especially if you're pushing continuous current near the mark. The operating temperature range is -40 to 75 °C, with humidity limits: max 95% up to 55 °C, then derating to 55% at 70 °C and 35% at 75 °C. That's typical for an indoor industrial MCB — no outdoor or condensation-heavy duty without a weatherproof enclosure. Mounting position any — no derating for sideways or upside-down install. Combined terminals top and bottom, sealable if the panel requires padlocking. Neutral conductor switching is not provided — this is a 2-pole breaker switching both phases, not a 1P+N configuration. The design of pole is 2P, so it's for two live conductors, not a switched neutral.","metaTitle":"Siemens 5SY6232-7CC SENTRON MCB, 2P C-Curve 32A 6kA","metaDescription":"Siemens 5SY6232-7CC SENTRON miniature circuit breaker, 2-pole, C-curve, 32 A rated, 6 kA breaking capacity per EN 60898, 440 V AC. Active production, available to order. Request qu","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","title":"5SY6232-7CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 400 V 6kA, 2-pole, C, 32A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","at AC / rated value":"32 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Energy Limitation Class":"3","according to EN 61346-2":"F","at 35 °C / rated value":"32 A","at 40 °C / rated value":"30.08 A","at 45 °C / rated value":"29.09 A","at 50 °C / rated value":"28.03 A","at 55 °C / rated value":"26.94 A","Combined Terminal Bottom":"Yes","according to IEC 81346-2":"F","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"No","Number Of Modular Width Units":"2","Tripping Characteristic Class":"C","Position / Of Power Supply Cord":"Any","according to EN 60898 / rated value":"6 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage / Of The Operating Voltage":"AC","Value Range / Of The Supply Voltage Frequency":"50/60 Hz","with multi-phase operation / at AC / rated value":"440 V","operating voltage / at DC / rated value / maximum":"72 V","vibration resistance / according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","with single-phase operation / at AC / rated value":"440 V","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2f0d948517950b5e54e95c3fabb4ec50.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=111898&mlfb=5SY6232-7CC"},"ai":{"faq":[{"question":"Where can I buy 5SY6232-7CC and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at that time."},{"question":"What is the depth and width of 5SY6232-7CC?","answer":"Depth is 76 mm, width is 36 mm (2 modular units), height is 90 mm. Installation depth is 70 mm."},{"question":"Will 5SY6232-7CC drop into a panel specified for 5SY7210-7CC?","answer":"Both are 2-pole SENTRON MCBs on the same DIN-rail footprint — same width (36 mm), same mounting method. The key difference is rating: 5SY6232-7CC is 32 A C-curve; 5SY7210-7CC is a 10 A C-curve. If the panel was wired for 10 A, dropping in a 32 A breaker without checking the downstream conductor sizing and load is not safe. Mechanically it fits; electrically verify the branch circuit."},{"question":"What compliance documentation does the 5SY6232-7CC carry?","answer":"The breaker is halogen-free and silicon-free. It meets EN 60898 for breaking capacity (6 kA) and is classified per EN 61346-2 and IEC 81346-2 as function F. Standard IEC/EN certifications apply for a SENTRON MCB; the manufacturer provides RoHS and REACH declarations on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY6232-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY6232-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}