{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY6232-8CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY6232-8CC","canonicalUrl":"https://aoctrl.com/siemens/5SY6232-8CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY6232-8CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY6CC series, 5SY6232-8CC miniature circuit breaker, 2-pole, D tripping characteristic, 32 A rated current, 6 kA breaking capacity (IEC 60898), 400 V AC.","salesMarkdown":"The 5 kA interrupting rating per UL 1077 and CSA C22.2 No.235 extends its applicability to North American panels that reference those standards. ## D-curve and deployment context The D-curve (tripping between 10 and 20 times rated current) is the key selector here. For a 32 A breaker, that means magnetic trip between 320 A and 640 A — well above the starting surge of a 15 kW motor or a bank of power-supply capacitors. In a control panel feeding multiple inductive loads, this avoids nuisance trips that a C-curve (5-10x In) would see on every start. The 5SY6232-8CC occupies 2 modular width units (36 mm total) on a DIN rail, with a depth of 76 mm and an installation depth of 70 mm. It mounts in any position and uses a quick-assembly system for rail snap-on. Combined top and bottom terminals simplify busbar or daisy-chain wiring across multiple poles. Rated for ambient temperatures from -40 °C to 75 °C, with a derating curve above 55 °C (max 95% humidity at 55 °C, tapering to 35% at 75 °C). Halogen-free and silicon-free construction. Vibration resistance per IEC 60068-2-6: ±1 mm at 5-25 Hz, 50 m/s² at 25-150 Hz. The breaker is sealable, allowing panel builders to lock the toggle position after commissioning to prevent unauthorized switching.","metaTitle":"Siemens 5SY6232-8CC SENTRON MCB, 2P D-32A 6kA","metaDescription":"Siemens SENTRON 5SY6232-8CC miniature circuit breaker, 2-pole, D-curve, 32 A rated, 6 kA IEC breaking capacity. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","title":"5SY6232-8CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Rated Value":"50/60 Hz","description":"Miniature circuit breaker 400 V 6kA, 2-pole, D, 32A","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","Type Of Voltage":"AC","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Number Of Poles / Note":"2P","acc. to DIN EN 61346-2":"F","Combined Terminal Bottom":"Yes","circuit-breaker / Design":"5SY6CC","Suitability For Operation":"Mechanical engineering / industry","Number Of Modular Width Units":"2","Tripping Characteristic Class":"D","at DC / rated value / maximum":"72 V","acc. to EN 60898 / rated value":"6 kA","Position / Of Power Supply Cord":"Any","Product Feature / Touch Protection":"Yes","supply voltage / at AC / rated value":"400 V","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","operational current / at AC / rated value":"32 A","at AC / acc. to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance / acc. to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Product Function / Neutral Conductor Switching":"No","with multi-phase operation / at AC / rated value":"440 V","with single-phase operation / at AC / rated value":"440 V","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/100addd4c438b6177b5202898ae9d130.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=94845&mlfb=5SY6232-8CC"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SY6232-8CC?","answer":"6 kA per EN 60898 at 400 V AC, and 5 kA per UL 1077 and CSA C22.2 No.235."},{"question":"What is the difference between 5SY6232-8CC and 5SY7210-7CC?","answer":"The 5SY7210-7CC is a different pole count and rating within the same SENTRON 5SY family. The 5SY6232-8CC is a 2-pole, 32 A, D-curve breaker; the 5SY7210-7CC is a different variant. Both share the same DIN-rail footprint and SENTRON platform, but the ratings and tripping characteristics differ — verify your BOM's specific current and pole requirements before substituting."},{"question":"Where can I buy 5SY6232-8CC?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation does Siemens provide for 5SY6232-8CC?","answer":"The breaker carries IEC 60898 and UL 1077 / CSA C22.2 No.235 certifications. It is halogen-free and silicon-free, meeting typical RoHS and REACH requirements for industrial equipment. Specific declarations are available from the manufacturer upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY6232-8CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY6232-8CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}