{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY6410-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY6410-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SY6410-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY6410-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON, miniature circuit breaker, 4-pole, C-curve, 10 A rated, 6 kA breaking capacity per EN 60898, 4 MW units, IP20, 50/60 Hz AC.","salesMarkdown":"The Siemens 5SY6410-7CC is a SENTRON 4-pole miniature circuit breaker with a C tripping characteristic, rated 10 A at 35 °C and 6 kA breaking capacity per EN 60898. If your service entrance has a higher prospective fault current, you'll need a current-limiting upstream breaker or a higher-rated device. Temperature derating is real: at 40 °C the continuous rating drops to 9.4 A, at 50 °C to 8.76 A, and at 55 °C to 8.42 A. IP20 with connected conductors — fine inside a closed cabinet, not for wet or outdoor locations without an enclosure. The breaker is sealable, halogen-free, and silicon-free — important for food-and-bev or clean-room panels where outgassing can contaminate product. Operating voltage is AC 50/60 Hz; DC operation is limited to 72 V maximum.","metaTitle":"Siemens 5SY6410-7CC SENTRON MCB, 4P C-curve 10 A 6 kA","metaDescription":"Siemens 5SY6410-7CC SENTRON 4-pole miniature circuit breaker, C-curve, 10 A, 6 kA breaking capacity per EN 60898. Active production, quoted to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["4-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"72 mm","title":"5SY6410-7CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 400 V 6kA, 4-pole, C, 10 A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"4P","Number Of Poles":"4","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","at AC rated value":"10 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","at 35 °C rated value":"10 A","at 40 °C rated value":"9.4 A","at 45 °C rated value":"9.09 A","at 50 °C rated value":"8.76 A","at 55 °C rated value":"8.42 A","Energy Limitation Class":"3","according to EN 61346-2":"F","Combined Terminal Bottom":"Yes","according to IEC 81346-2":"F","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"No","Number Of Modular Width Units":"4","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"C","according to EN 60898 rated value":"6 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage Of The Operating Voltage":"AC","Value Range Of The Supply Voltage Frequency":"50/60 Hz","operating voltage at DC rated value maximum":"72 V","with multi-phase operation at AC rated value":"440 V","with single-phase operation at AC rated value":"440 V","at AC according to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Mechanical Service Life (Switching Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.1 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/776d3297b34f0a5e003f6a0fc2fb6264.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=63281&mlfb=5SY6410-7CC"},"ai":{"faq":[{"question":"What is the breaking capacity of the 5SY6410-7CC?","answer":"It is rated 6 kA per EN 60898, which covers typical commercial and light industrial fault currents. For higher fault levels, upstream current-limiting coordination is required."},{"question":"Where can I buy the 5SY6410-7CC?","answer":"We supply it through our independent distribution channel. Submit an RFQ for current pricing and availability — orders are quoted to order, not stocked on the shelf."},{"question":"Will the 5SY6410-7CC replace a 5SY4140-7 in an existing panel?","answer":"Both are 4-pole C-curve SENTRON MCBs on the same DIN-rail footprint (4 MW units, 72 mm wide). The 5SY6410-7CC carries a 10 A rating and 6 kA breaking capacity; the 5SY4140-7 has different ratings. Check your existing coordination study — the physical fit is the same, but the electrical ratings must match the circuit design."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY6410-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY6410-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}