{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY6506-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY6506-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SY6506-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY6506-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON, miniature circuit breaker, 5SY6506-7CC, C characteristic, 2-pole (1P+N), 6 kA at 230 V AC per EN 60898, 36 mm width, 76 mm depth.","salesMarkdown":"The 6 kA breaking capacity at 230 V AC (per EN 60898) covers most commercial and light industrial panel fault levels; for UL 1077 / CSA C22.2 No.235 installations the rating is 5 kA. The neutral conductor is switched, so this breaker fully isolates the downstream circuit on overcurrent or manual opening — important for maintenance isolation on single-phase sub-circuits. At 36 mm wide (2 modular width units) and 76 mm deep, this breaker occupies two standard DIN-rail slots. Mounting position is unrestricted, so it can be installed horizontally or inverted if panel layout demands it. The quick-assembly fastening system clips onto the DIN rail without tools and releases via a screwdriver slot. IP20 with connected conductors is the standard for enclosed distribution boards; no special sealing is needed inside a rated panel. ## Environmental and mechanical margins Rated for ambient temperatures from -40 °C to 75 °C, with derating above 55 °C: max 95% humidity up to 55 °C, dropping to 55% at 70 °C and 35% at 75 °C. The 10 000 mechanical operating cycles typical cover decades of occasional switching in a distribution board. Vibration resistance per IEC 60068-2-6 (±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz) confirms suitability for installation near rotating machinery or on factory walls subject to low-frequency vibration. ## Supplementary devices and power loss Power loss is 1.2 W per pole at rated current in hot operating state, so a 2-pole unit dissipates 2.4 W total. In a densely populated enclosure with many breakers, that heat adds up; plan ventilation or de-rate if ambient inside the panel exceeds 55 °C.","metaTitle":"Siemens 5SY6506-7CC SENTRON MCB, C-Curve, 2-Pole 1P+N, 6kA","metaDescription":"Siemens 5SY6506-7CC SENTRON miniature circuit breaker, C characteristic, 2-pole 1P+N, 6 kA per EN 60898. Active production, sourced to order. IP20, 36 mm wide, 76 mm deep.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","title":"5SY6506-7CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 230 V 6kA, 1+N-pole, C, 6A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Energy Limitation Class":"3","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"Yes","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"C","according to EN 60898 rated value":"6 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage Of The Operating Voltage":"AC","Value Range Of The Supply Voltage Frequency":"50/60 Hz","operating voltage at DC rated value maximum":"72 V","with single-phase operation at AC rated value":"250 V","at AC according to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","supply voltage with single-phase operation at AC rated value":"230 V","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.2 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1d93e78a158eb2f0abaf993805115358.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=486779&mlfb=5SY6506-7CC"},"ai":{"faq":[{"question":"Where can I buy 5SY6506-7CC and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead-time estimate."},{"question":"What is 5SY6506-7CC's listed depth (76 mm) on this component line?","answer":"The depth is 76 mm, with an installation depth of 70 mm — the extra 6 mm accounts for the terminal screws and busbar connection overhang."},{"question":"What is 5SY6506-7CC's listed width (36 mm) on this component line?","answer":"The width is 36 mm, which equals 2 modular width units on a standard DIN-rail panel."},{"question":"Will 5SY6506-7CC drop into a panel that was specified around 5SY4101-7CV without rewiring?","answer":"Both are 2-module-wide SENTRON MCBs on the same DIN-rail footprint, so the mechanical fit is identical. The 5SY6506-7CC is a C-curve 1P+N breaker with neutral switching; the 5SY4101-7CV is a different rating/curve variant. If the panel wiring was designed for a 1P+N configuration with switched neutral, the 5SY6506-7CC drops in without rewiring — but verify the rated current and breaking capacity match the circuit design."},{"question":"What compliance documentation does this brand provide for 5SY6506-7CC (RoHS, REACH, UL, IEC)?","answer":"The breaker is rated per EN 60898 at 6 kA and per UL 1077 / CSA C22.2 No.235 at 5 kA. Halogen-free and silicon-free construction supports RoHS/REACH compliance. Standard Siemens SENTRON documentation includes the EC Declaration of Conformity and the UL/CSA file; request specific certificates with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY6506-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY6506-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}