{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY6513-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY6513-6","canonicalUrl":"https://aoctrl.com/siemens/5SY6513-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SY6513-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY6513-6, 13 A miniature circuit breaker, 1P+N, B tripping characteristic, 6 kA per EN 60898 / 15 kA per IEC 60947-2, 2 MW, IP20.","salesMarkdown":"It carries dual breaking capacities: 6 kA per IEC/EN 60898-1 for residential and commercial branch circuits, and 15 kA per IEC 60947-2 / UL1077 for industrial panel applications — the higher figure is the one that matters when you are coordinating with upstream protective devices in a plant distribution board. The 13 A rating holds at 35 °C ambient; it derates to 12.38 A at 40 °C, 12.05 A at 45 °C, 11.73 A at 50 °C, and 11.38 A at 55 °C. If your enclosure runs hot, size the load accordingly — the 13 A nameplate is only good in a cool cabinet. Not the right curve for motor starting; that is a C or D job. The 2-module width (36 mm) and 76 mm depth fit standard DIN-rail enclosures. Mounting position is any orientation.","metaTitle":"Siemens 5SY6513-6 SENTRON MCB, 13A, 1P+N, B-Curve, 6/15kA","metaDescription":"Siemens 5SY6513-6 SENTRON miniature circuit breaker, 13 A, 1P+N, B characteristic, 6 kA (EN 60898) / 15 kA (IEC 60947-2). Active production, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","title":"5SY6513-6","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Standard":"IEC / EN 60898-1, IEC / EN 60947-2 / UL1077","description":"Miniature circuit breaker 230 V 6kA, 1+N-pole B, 13 A, D=70 mm","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","at AC / rated value":"13 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Energy Limitation Class":"3","according to EN 61346-2":"F","at 35 °C / rated value":"13 A","at 40 °C / rated value":"12.38 A","at 45 °C / rated value":"12.05 A","at 50 °C / rated value":"11.73 A","at 55 °C / rated value":"11.38 A","Combined Terminal Bottom":"Yes","according to IEC 81346-2":"F","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"Yes","Number Of Modular Width Units":"2","Tripping Characteristic Class":"B","Position / Of Power Supply Cord":"Any","according to EN 60898 / rated value":"6 kA","according to IEC 60947-2 / rated value":"15 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage / Of The Operating Voltage":"AC","Value Range / Of The Supply Voltage Frequency":"50/60 Hz","at DC / according to IEC 60947-2 / rated value":"15 kA","operating voltage / at DC / rated value / maximum":"72 V","vibration resistance / according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","with single-phase operation / at AC / rated value":"250 V","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0f9a5a85eea147aba04893896f0c4917.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=419749&mlfb=5SY6513-6"},"ai":{"faq":[{"question":"What is the breaking capacity of the 5SY6513-6?","answer":"The 5SY6513-6 carries a 6 kA breaking capacity per IEC/EN 60898-1 and a 15 kA breaking capacity per IEC 60947-2 / UL1077. Use the 15 kA figure for industrial panel coordination."},{"question":"Does the 5SY6513-6 switch the neutral?","answer":"Yes, the 1P+N design switches both the phase and neutral conductors, providing full isolation on the outgoing circuit."},{"question":"Where can I buy the 5SY6513-6 and get current pricing?","answer":"The 5SY6513-6 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit a request for a firm commercial offer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY6513-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY6513-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}