{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY6532-8CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY6532-8CC","canonicalUrl":"https://aoctrl.com/siemens/5SY6532-8CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY6532-8CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY6CC series miniature circuit breaker, 5SY6532-8CC, 2-pole 1P+N, 32 A, D tripping characteristic, 230 V AC, 6 kA IEC 60898.","salesMarkdown":"## Siemens 5SY6532-8CC — 32 A D-curve MCB in the SENTRON 5SY6CC family It's built for high-inrush loads — motors, transformers, welding equipment — where the D curve's 10–20× In magnetic trip delay keeps nuisance trips off the floor. The 1P+N configuration switches the neutral, so it covers both poles in a single-width 36 mm footprint. The D curve means this breaker holds through the startup surge of a 32 A motor drawing 6–8× its running current for a few hundred milliseconds — a C curve would nuisance trip on that same inrush. The 72 V DC maximum rating is useful for control-power protection in DC bus applications, though it's not the primary role. At 36 mm wide (2 width units), it takes up standard MCB real estate in a distribution board. Wire range covers 0.75 to 35 mm² solid or stranded, so it'll take a 10 mm² feed for a 32 A submain or a 4 mm² tail for a motor circuit. Sealable for lockout/tagout compliance. Overvoltage category III per IEC 60664, meaning it's rated for fixed-installation mains supply.","metaTitle":"Siemens 5SY6532-8CC SENTRON MCB, 32 A, D Curve, 2-pole","metaDescription":"Siemens 5SY6532-8CC SENTRON miniature circuit breaker, 32 A rated, D tripping characteristic, 6 kA IEC breaking capacity. 2-pole 1P+N design. Current lifecycle stage. Sourced to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Solid":"0.75 ... 35 mm²","Width":"36 mm","title":"5SY6532-8CC","Height":"90 mm","Sealable":"Yes","Stranded":"0.75 ... 35 mm²","Rated Value":"50/60 Hz","description":"Miniature circuit breaker 230 V 6kA, 1+N-pole, D, 32A","Halogen-Free":"Yes","Silicon-Free":"Yes","Wertebereich":"-25 ... +55 °C","Mounting type":"Quick assembly system","Number of poles":"2","Type of voltage":"AC","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Ambient temperature":"-40 ... +75 °C","Product designation":"Miniature circuit breaker","Protection class IP":"IP20, with connected conductors","at AC / rated value":"230 V","Overvoltage category":"III","Combined Terminal Top":"Yes","Number of width units":"2","Number of poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","Combined Terminal Bottom":"Yes","circuit-breaker / Design":"5SY6CC","Suitability for operation":"Mechanical engineering / industry","Current / at AC / rated value":"32 A","Tripping characteristic class":"D","at DC / rated value / maximum":"72 V","acc. to EN 60898 / rated value":"6 kA","Position / of power supply cord":"Any","Product feature / Touch protection":"Yes","Influence of the surrounding temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","at AC / acc. to UL 1077 and CSA C22.2 No.235":"5 kA","Tightening torque / with screw-type terminals":"2.5 ... 3.5 N·m","Product function / neutral conductor switching":"Yes","with single-phase operation / at AC / rated value":"250 V","Mechanical service life (switching cycles) / typical":"10 000","Tightening torque [lbf·in] / with screw-type terminals":"22 ... 31 lbf·in"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/583e5a276630764455224b3f622df591.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=180885&mlfb=5SY6532-8CC"},"ai":{"faq":[{"question":"Where can I buy 5SY6532-8CC and get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"Will 5SY6532-8CC drop into a panel specified for 5SY6140-6CC?","answer":"Both are 2-pole 1P+N SENTRON 5SY6CC breakers with the same 36 mm width, DIN-rail mounting, and wire range. The 5SY6532-8CC is a 32 A D curve; the 5SY6140-6CC is a 40 A D curve. Same footprint, same terminals — no rewiring needed if the circuit rating allows the swap. Check that the downstream load and cable are rated for 32 A (the lower value) before substituting."},{"question":"What compliance documentation does Siemens provide for 5SY6532-8CC?","answer":"The breaker carries IEC 60898 (6 kA) and UL 1077 / CSA C22.2 No.235 (5 kA) ratings. It's halogen-free and silicon-free. Overvoltage category III. Standard Siemens declarations of conformity and the datasheet are available through the manufacturer's documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY6532-8CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY6532-8CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}