{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY6613-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY6613-6","canonicalUrl":"https://aoctrl.com/siemens/5SY6613-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SY6613-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON miniature circuit breaker, 5SY6613-6, 4-pole (3P+N), B-curve, 13 A, 6 kA per EN 60898 / 15 kA per IEC 60947-2, IP20, current production.","salesMarkdown":"The Siemens SENTRON 5SY6613-6 is a 4-pole miniature circuit breaker (3P+N) with a B-curve trip characteristic, rated 13 A at 50/60 Hz AC. It is designed for branch-circuit overcurrent and short-circuit protection in industrial control panels, distribution boards, and mechanical-engineering installations. The 13 A rating holds at 35 °C; derate to 12.48 A at 40 °C, 12.22 A at 45 °C, 11.95 A at 50 °C, and 11.67 A at 55 °C — plan your continuous load against the ambient temperature of the enclosure. The higher IEC figure applies when the breaker is used in industrial distribution with a known upstream fault level; the EN figure governs in residential or light-commercial boards. Mounts in any position via the quick-assembly system — snaps onto standard DIN rail. Halogen-free and silicon-free construction reduces corrosive off-gassing in enclosed panels. Sealable for lockout/tagout. Ambient temperature range -40 to 75 °C with humidity limits per.","metaTitle":"Siemens SENTRON 5SY6613-6 MCB, 4-pole B-curve 13 A, 6/15 kA","metaDescription":"Siemens SENTRON 5SY6613-6 miniature circuit breaker, 4-pole (3P+N), B-curve, 13 A rated, 6 kA (EN 60898) / 15 kA (IEC 60947-2). Current production. IP20. Sourced to order against R","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["4-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"72 mm","title":"5SY6613-6","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 400 V 6kA, 3+N-pole B, 13 A, D=70 mm","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"4","Type Of Voltage":"AC","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"13 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Number Of Poles / Note":"3P+N","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","at 35 °C / rated value":"13 A","at 40 °C / rated value":"12.48 A","at 45 °C / rated value":"12.22 A","at 50 °C / rated value":"11.95 A","at 55 °C / rated value":"11.67 A","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Number Of Modular Width Units":"4","Tripping Characteristic Class":"B","acc. to EN 60898 / rated value":"6 kA","Position / Of Power Supply Cord":"Any","acc. to IEC 60947-2 / rated value":"15 kA","Product Feature / Touch Protection":"Yes","Supply Voltage Frequency / Rated Value":"50/60 Hz","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","at DC / acc. to IEC 60947-2 / rated value":"15 kA","at AC / acc. to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance / acc. to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Product Function / Neutral Conductor Switching":"Yes","with multi-phase operation / at AC / rated value":"440 V","operating voltage / at DC / rated value / maximum":"72 V","with single-phase operation / at AC / rated value":"440 V","Mechanical Service Life (Operating Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d962cdf8705c3918d0d9e12eb1d1b6e4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=166697&mlfb=5SY6613-6"},"ai":{"faq":[{"question":"Where can I buy 5SY6613-6 and how do I get a price?","answer":"The 5SY6613-6 is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time."},{"question":"Will 5SY6613-6 drop into a panel that was specified around 5SY6613-8 without rewiring?","answer":"Both are 4-pole (3P+N) SENTRON MCBs with the same DIN-rail footprint (72 mm width, 4 modular units) and identical depth (76 mm). The 5SY6613-6 is a 13 A B-curve; the 5SY6613-8 is a different rating. Physical swap is possible if the ampacity and trip curve match the circuit design — verify the load before substituting."},{"question":"What compliance documentation does this brand provide for 5SY6613-6 (RoHS, REACH, UL, IEC)?","answer":"The 5SY6613-6 is certified to EN 60898 (6 kA) and IEC 60947-2 (15 kA). It carries the Siemens SENTRON brand and is halogen-free and silicon-free. For RoHS/REACH declarations and UL listing status, request the manufacturer's compliance documentation at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY6613-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY6613-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}