{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY6613-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY6613-7","canonicalUrl":"https://aoctrl.com/siemens/5SY6613-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SY6613-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY6613-7, 4-pole miniature circuit breaker, 13 A, tripping characteristic C, breaking capacity 6 kA per EN 60898 / 15 kA per IEC 60947-2, 4 modular width units, IP20.","salesMarkdown":"The Siemens SENTRON 5SY6613-7 is a 4-pole miniature circuit breaker (3P+N) rated 13 A at AC with a C tripping characteristic — meaning it trips at 5 to 10 times rated current, the standard choice for motor and transformer inrush in industrial control panels. The 6 kA breaking capacity per EN 60898-1 covers most sub-distribution boards; the 15 kA rating per IEC 60947-2 / UL1077 applies when the breaker is used as a supplementary protector in higher-fault-capacity industrial switchgear. At 40 °C ambient the continuous rating derates to 12.38 A, and at 50 °C to 11.73 A — so if the panel runs warm, size the load accordingly. The neutral pole is not internally protected — it tracks the phase poles mechanically — so it is not a 4-pole protected breaker. The breaker carries approvals to IEC / EN 60898-1 and IEC / EN 60947-2 / UL1077.","metaTitle":"Siemens 5SY6613-7 SENTRON MCB, 4P C-13A 6kA/15kA","metaDescription":"Siemens SENTRON 5SY6613-7 4-pole MCB, 13 A, C-curve, 6 kA (EN 60898) / 15 kA (IEC 60947-2). Active production, sourced to order. IP20, halogen-free, 4 MW.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["4-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"72 mm","title":"5SY6613-7","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Standard":"IEC / EN 60898-1, IEC / EN 60947-2 / UL1077","description":"Miniature circuit breaker 400 V 6kA, 3+N-pole C, 13 A, D=70 mm","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"3P+N","Number Of Poles":"4","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","at AC rated value":"13 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","at 35 °C rated value":"13 A","at 40 °C rated value":"12.38 A","at 45 °C rated value":"12.05 A","at 50 °C rated value":"11.73 A","at 55 °C rated value":"11.38 A","Energy Limitation Class":"3","according to EN 61346-2":"F","Combined Terminal Bottom":"Yes","according to IEC 81346-2":"F","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"Yes","Number Of Modular Width Units":"4","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"C","according to EN 60898 rated value":"6 kA","according to IEC 60947-2 rated value":"15 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage Of The Operating Voltage":"AC","at DC according to IEC 60947-2 rated value":"15 kA","Value Range Of The Supply Voltage Frequency":"50/60 Hz","operating voltage at DC rated value maximum":"72 V","with multi-phase operation at AC rated value":"440 V","with single-phase operation at AC rated value":"440 V","at AC according to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Mechanical Service Life (Switching Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.4 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$27.94","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d72d98e2b1b47edfd23ac8d02103e37a.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=172310&mlfb=5SY6613-7"},"ai":{"faq":[{"question":"Where can I buy 5SY6613-7?","answer":"It is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of 5SY6613-7?","answer":"6 kA per EN 60898-1 and 15 kA per IEC 60947-2 / UL1077. The higher figure applies when the breaker is used as a supplementary protector in industrial switchgear."},{"question":"What compliance documentation does Siemens provide for 5SY6613-7?","answer":"The breaker is certified to IEC / EN 60898-1 and IEC / EN 60947-2 / UL1077. It is halogen-free and silicon-free, which supports RoHS and REACH compliance."},{"question":"Will 5SY6613-7 drop into a panel specified around 5SY4140-7 without rewiring?","answer":"Both are 4-pole SENTRON MCBs with the same 4 MW footprint (72 mm width) and DIN-rail mounting. The 5SY6613-7 is a 13 A C-curve; the 5SY4140-7 is a 40 A C-curve. If the panel wiring and busbar are rated for the higher current, the 5SY6613-7 will physically fit, but the load must be within its 13 A rating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY6613-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY6613-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}