{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY7110-6KK13","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY7110-6KK13","canonicalUrl":"https://aoctrl.com/siemens/5SY7110-6KK13","factsUrl":"https://aoctrl.com/api/mcp/products/5SY7110-6KK13","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY7110-6KK13, miniature circuit breaker, 1-pole, 10 A, B characteristic, breaking capacity 25 kA acc. to EN 60898, 30 kA acc. to IEC 60947-2, 1 MW width, IP20.","salesMarkdown":"At 400 V line-to-line that covers most industrial panel secondary faults. ## Thermal derating matters in a warm panel The 10 A rating is at 35 °C ambient. Inside a crowded enclosure at 50 °C the breaker is good for 8.74 A; at 60 °C it drops to 8.04 A. If you're loading a branch near the nominal rating, check the actual panel ambient — the 5SY7 series derates linearly above 35 °C. That's not a datasheet footnote; it's the difference between a circuit that holds and one that nuisance-trips on a hot afternoon. Sealable and touch-protected, so it's suitable for meter cabinets or utility compartments where sealing is required.","metaTitle":"Siemens 5SY7110-6KK13 SENTRON MCB, 1P, 10A, B-Curve, 25kA EN","metaDescription":"Siemens 5SY7110-6KK13 SENTRON miniature circuit breaker, 1-pole, 10 A, B characteristic, 25 kA per EN 60898. Current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SY7110-6KK13","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 230/400 V 25kA, 1-pole, B, 10 A for precounter area","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"1","Type Of Voltage":"AC","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"10 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Design Of The Product":"As automatic meter","Number Of Poles / Note":"1P","acc. to DIN EN 61346-2":"F","at 35 °C / rated value":"10 A","at 40 °C / rated value":"9.39 A","at 45 °C / rated value":"9.07 A","at 50 °C / rated value":"8.74 A","at 55 °C / rated value":"8.4 A","at 60 °C / rated value":"8.04 A","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Number Of Modular Width Units":"1","Tripping Characteristic Class":"B","acc. to EN 60898 / rated value":"25 kA","Position / Of Power Supply Cord":"Any","acc. to IEC 60947-2 / rated value":"30 kA","Product Feature / Touch Protection":"Yes","Supply Voltage Frequency / Rated Value":"50/60 Hz","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","at DC / acc. to IEC 60947-2 / rated value":"25 kA","at AC / acc. to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance / acc. to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Product Function / Neutral Conductor Switching":"No","with multi-phase operation / at AC / rated value":"440 V","operating voltage / at DC / rated value / maximum":"72 V","with single-phase operation / at AC / rated value":"440 V","Mechanical Service Life (Operating Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f10d581ba4f072da445e7aa06f0f4ed6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=283251&mlfb=5SY7110-6KK13"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 5SY7110-6KK13?","answer":"Submit an RFQ through the site. We source this part to order; pricing and stock levels are confirmed at quote time."},{"question":"What is the breaking capacity of 5SY7110-6KK13?","answer":"25 kA per EN 60898 and 30 kA per IEC 60947-2. That covers most industrial panel secondary fault levels."},{"question":"What is the width of 5SY7110-6KK13?","answer":"18 mm — one modular unit. Snaps onto DIN rail."},{"question":"What compliance documentation does Siemens provide for 5SY7110-6KK13?","answer":"The part carries IEC 60947-2 and EN 60898 ratings. It is halogen-free and silicon-free. RoHS and REACH compliance documentation is available from Siemens upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY7110-6KK13","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY7110-6KK13 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}