{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY7116-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY7116-7","canonicalUrl":"https://aoctrl.com/siemens/5SY7116-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SY7116-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY7116-7, 1-pole miniature circuit breaker, C tripping characteristic, 15 kA per EN 60898 / 25 kA per IEC 60947-2, 400 V AC.","salesMarkdown":"It is rated for 400 V AC and carries dual breaking capacities: 15 kA per IEC/EN 60898-1 and 25 kA per IEC 60947-2, with a DC rating of 15 kA at 60 V per IEC 60947-2. For UL 1077 applications, it is rated at 5 kA. This dual-standard rating means the same unit can be specified for IEC-based distribution panels and UL-recognized industrial control panels, simplifying BOM consolidation across regional projects. The 25 kA breaking capacity under IEC 60947-2 gives this MCB headroom for high-fault installations, such as main distribution boards or industrial sub-distribution where the prospective short-circuit current exceeds 15 kA. The 15 kA rating under EN 60898-1 covers the more common residential and light commercial duty. For DC circuits, the 15 kA rating at 60 V (max 72 V operating) covers battery banks and DC bus applications up to that voltage. ## Panel integration Mounting position is any orientation. Halogen-free and silicon-free construction is specified.","metaTitle":"Siemens 5SY7116-7 SENTRON MCB, 1P C-Curve, 15/25 kA","metaDescription":"Siemens 5SY7116-7 SENTRON miniature circuit breaker, 1-pole, C characteristic, 15 kA (EN 60898) / 25 kA (IEC 60947-2). Current lifecycle stage. Sourced to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SY7116-7","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Standard":"IEC / EN 60898-1, IEC / EN 60947-2 / UL1077","description":"Miniature circuit breaker 230/400 V 15kA, 1-pole, C, 16A, D=70 mm","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P","Number Of Poles":"1","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","at AC rated value":"400 V","at DC rated value":"60 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Energy Limitation Class":"3","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"No","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"C","according to EN 60898 rated value":"15 kA","according to IEC 60947-2 rated value":"25 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage Of The Operating Voltage":"AC","at DC according to IEC 60947-2 rated value":"15 kA","Value Range Of The Supply Voltage Frequency":"50/60 Hz","operating voltage at DC rated value maximum":"72 V","with multi-phase operation at AC rated value":"440 V","with single-phase operation at AC rated value":"440 V","at AC according to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","supply voltage with single-phase operation at AC rated value":"230 V","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.6 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$12.19","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9cc2f0e3ff750c7e83c142e37bbe37ea.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=85846&mlfb=5SY7116-7"},"ai":{"faq":[{"question":"Where can I buy 5SY7116-7 and get a price?","answer":"The 5SY7116-7 is sourced through independent distribution channels. Submit an RFQ for current availability and pricing; stock levels and lead times are confirmed at quote time."},{"question":"What are the key breaking capacity ratings for 5SY7116-7?","answer":"15 kA per IEC/EN 60898-1, 25 kA per IEC 60947-2 at 400 V AC, and 15 kA at 60 V DC per IEC 60947-2. For UL 1077 applications, the rating is 5 kA."},{"question":"What compliance documentation is available for 5SY7116-7?","answer":"The MCB carries approvals to IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077. RoHS and REACH compliance documentation is available from Siemens."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY7116-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY7116-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}