{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY7116-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY7116-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SY7116-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY7116-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY7116-7CC, 1-pole miniature circuit breaker, C characteristic, 25 kA interrupting capacity per IEC 60947-2, 400 V AC, 18 mm width.","salesMarkdown":"Rated for 400 V AC single-phase or multi-phase operation, and 230 V AC single-phase supply, it handles the common panel voltages across European and Asian industrial sites. The 50/60 Hz rating covers both mains frequencies. For DC circuits, the maximum operating voltage is 72 V — useful for control-voltage spurs but not for 110 V DC battery banks. Under UL 1077 and CSA C22.2 No. 235, the interrupting capacity is 5 kA — enough for North American supplementary protection applications where the upstream breaker already provides the main fault clearance. Mounting position is unrestricted — horizontal, vertical, or upside-down works. Sealable design allows locking in the OFF position for lockout/tagout compliance. Halogen-free and silicon-free construction reduces toxic gas and contamination risk in sensitive environments like clean rooms or food processing. Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz, adequate for machine-mounted panels near conveyors or compressors.","metaTitle":"Siemens 5SY7116-7CC SENTRON MCB, 1P, C-Curve, 25 kA IEC","metaDescription":"Siemens 5SY7116-7CC SENTRON miniature circuit breaker, 1-pole, C characteristic, 25 kA per IEC 60947-2, 400 V AC, 18 mm wide. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"18 mm","title":"5SY7116-7CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 230/400 V 15kA, 1-pole, C, 16A","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P","Number Of Poles":"1","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","at AC rated value":"400 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"No","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"C","according to IEC 60947-2 rated value":"25 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage Of The Operating Voltage":"AC","Value Range Of The Supply Voltage Frequency":"50/60 Hz","operating voltage at DC rated value maximum":"72 V","with multi-phase operation at AC rated value":"440 V","with single-phase operation at AC rated value":"440 V","at AC according to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","supply voltage with single-phase operation at AC rated value":"230 V","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.8 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/594df8e900f58037b85e85ccaa3941df.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=154505&mlfb=5SY7116-7CC"},"ai":{"faq":[{"question":"What is 5SY7116-7CC's interrupting capacity under IEC and UL?","answer":"Per IEC 60947-2 it is rated 25 kA at 400 V AC; per UL 1077 and CSA C22.2 No. 235 it is 5 kA. The UL figure is for supplementary protection — verify the upstream device's SCCR for full fault clearance."},{"question":"Will 5SY7116-7CC drop into a panel specified around 5SY4116-7CV without rewiring?","answer":"Both are 1-pole, 18 mm wide MCBs with C characteristic, so the footprint and busbar connection are identical. The 5SY7116-7CC carries a higher IEC interrupting rating (25 kA vs the 5SY4116-7CV's rating — check that peer's spec for exact value), but terminal layout and DIN-rail clip are the same. No rewiring needed for a drop-in swap."},{"question":"What compliance documentation does this brand provide for 5SY7116-7CC?","answer":"The SENTRON series typically carries CE marking for the European market, and the UL/CSA listing is confirmed by the 5 kA rating per UL 1077 and CSA C22.2 No. 235. RoHS and REACH compliance are standard for current Siemens industrial products; specific declarations are available on request."},{"question":"Where can I buy 5SY7116-7CC and how is it quoted?","answer":"This part is sourced and quoted to order through independent industrial-automation distribution. Submit an RFQ for current pricing, stock availability, and lead time — volume and blanket-order terms are negotiable at quote."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY7116-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY7116-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}