{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY7215-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY7215-7","canonicalUrl":"https://aoctrl.com/siemens/5SY7215-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SY7215-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY7215-7 miniature circuit breaker, C-curve, 1.6 A rated current, 2-pole, 15 kA (EN 60898-1) / 50 kA (IEC 60947-2) breaking capacity, 36 mm wide, IP20.","salesMarkdown":"It carries a 15 kA breaking capacity per EN 60898-1 and a 50 kA rating per IEC 60947-2 / UL1077, so it can interrupt fault currents up to those levels without welding or cascading to upstream gear. Rated current is temperature-sensitive: 1.6 A at 35 °C, derated to 1.52 A at 40 °C, 1.44 A at 50 °C, and 1.36 A at 60 °C. The 1.6 A C-curve is a niche rating, typically used for small control transformers, signal power supplies, or lighting circuits where the load is well under 2 A but the inrush is moderate. Snap-on DIN rail mount, any orientation. Depth is 76 mm (installation depth 70 mm), height 90 mm, width 36 mm — that's 2 modular units. IP20 with conductors connected. Sealable, halogen-free, silicon-free — useful for food, pharma, or clean-room panels where outgassing is a concern. Touch protection is built in (product feature). The quick assembly system means it clips onto the rail and stays without a screwdriver — handy for panel builders cranking through a BOM. Rated under dual standards: IEC / EN 60898-1 (the household-and-similar MCB standard) and IEC / EN 60947-2 / UL1077 (the industrial breaker standard). That dual rating is the key: the 15 kA figure applies under the domestic standard, while the 50 kA figure applies under the industrial standard — meaning this breaker is tested to a higher fault level in industrial panels. Suitable for mechanical engineering and industry per the manufacturer's designation.","metaTitle":"Siemens 5SY7215-7 SENTRON MCB, C-Curve, 1.6 A, 2-Pole, 15/50","metaDescription":"Siemens 5SY7215-7 SENTRON miniature circuit breaker, 1.6 A, C-curve, 2-pole. Rated 15 kA per EN 60898-1 and 50 kA per IEC 60947-2. Current production. Quoted to order against an RF","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","title":"5SY7215-7","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Standard":"IEC / EN 60898-1, IEC / EN 60947-2 / UL1077","description":"Miniature circuit breaker 400 V 15kA, 2-pole, C, 1.6 A, D=70 mm","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","at AC / rated value":"1.6 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Energy Limitation Class":"3","according to EN 61346-2":"F","at 35 °C / rated value":"1.6 A","at 40 °C / rated value":"1.52 A","at 45 °C / rated value":"1.48 A","at 50 °C / rated value":"1.44 A","at 55 °C / rated value":"1.4 A","at 60 °C / rated value":"1.36 A","Combined Terminal Bottom":"Yes","according to IEC 81346-2":"F","Suitability For Operation":"Mechanical engineering / industry","Number Of Modular Width Units":"2","Tripping Characteristic Class":"C","Position / Of Power Supply Cord":"Any","Product Feature / Touch Protection":"Yes","according to EN 60898 / rated value":"15 kA","according to IEC 60947-2 / rated value":"50 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage / Of The Operating Voltage":"AC","at DC / according to IEC 60947-2 / rated value":"15 kA","Product Component / Neutral Conductor Switching":"No","with multi-phase operation / at AC / rated value":"440 V","operating voltage / at DC / rated value / maximum":"72 V","vibration resistance / according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","with single-phase operation / at AC / rated value":"440 V","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$39.37","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0f49aad0c9d675edc86d2201bedbf15f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=269241&mlfb=5SY7215-7"},"ai":{"faq":[{"question":"Where can I buy the 5SY7215-7 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What are the key ratings of the 5SY7215-7?","answer":"Rated 1.6 A at AC, C-curve trip characteristic, 2-pole, 15 kA breaking capacity per EN 60898-1 and 50 kA per IEC 60947-2 / UL1077. Width 36 mm (2 MW), depth 76 mm, IP20."},{"question":"Will the 5SY7215-7 drop into a panel specified around the 5SY7210-7CC without rewiring?","answer":"Yes — both are 2-pole, 36 mm wide SENTRON MCBs with the same DIN-rail footprint and terminal layout. The 5SY7215-7 is a 1.6 A C-curve; the 5SY7210-7CC is a lower-current variant. No rewiring needed for the swap."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY7215-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY7215-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}