{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY7410-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY7410-7","canonicalUrl":"https://aoctrl.com/siemens/5SY7410-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SY7410-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY7410-7, 4-pole miniature circuit breaker, C-curve, 400 VAC, 15 kA (EN 60898) / 30 kA (IEC 60947-2), 72 mm wide.","salesMarkdown":"## Siemens 5SY7410-7 — 4-pole C-curve MCB for panel builders Rated operational voltage is 400 VAC (440 V max single- or multi-phase), with a DC rating of 60 V (72 V max) for control-circuit applications. The 4-pole configuration switches all three phases plus the neutral; note that the neutral conductor is not switched (solid neutral pass-through), so this MCB is not suited for TN-S or TT schemes requiring a switched neutral. Halogen-free and silicon-free construction suits environments sensitive to outgassing — clean rooms, medical, or food-processing zones. ## Breaking capacity — what the dual rating means for your panel The 15 kA rating under EN 60898-1 is the standard residential/commercial MCB test; the 30 kA under IEC 60947-2 is the industrial counterpart, tested with a higher power factor and different make-break sequence. The UL 1077 rating of 5 kA (supplementary protector classification) covers North American installations where the device is not the sole branch-circuit overcurrent device. Energy limitation class 3 means the breaker limits let-through energy below 3 (I²t) thresholds — fast enough to protect downstream wiring and devices during a short circuit. ## Integration — panel fit and environmental limits Installation depth is 70 mm (76 mm overall depth), fitting standard 80 mm deep enclosures. Ambient temperature range spans -40 °C to 75 °C, with humidity derating: 95% RH up to 55 °C, 55% RH at 70 °C, 35% RH at 75 °C. The quick-assembly system clips onto the DIN rail without tools. Supply cord position is any (line or load from either end), simplifying wiring in tight enclosures.","metaTitle":"Siemens 5SY7410-7 SENTRON MCB, 4P C-curve, 15kA IEC","metaDescription":"Siemens 5SY7410-7 SENTRON 4-pole MCB, C-curve, 15 kA (IEC 60898) / 30 kA (IEC 60947-2), 400 VAC. Active production, sourced to order. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["4-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"72 mm","title":"5SY7410-7","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Standard":"IEC / EN 60898-1, IEC / EN 60947-2 / UL1077","description":"Miniature circuit breaker 400 V 15kA, 4-pole, C, 10A, D=70 mm","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"4P","Number Of Poles":"4","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","at AC rated value":"400 V","at DC rated value":"60 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Energy Limitation Class":"3","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"No","Number Of Modular Width Units":"4","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"C","according to EN 60898 rated value":"15 kA","according to IEC 60947-2 rated value":"30 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage Of The Operating Voltage":"AC","at DC according to IEC 60947-2 rated value":"15 kA","Value Range Of The Supply Voltage Frequency":"50/60 Hz","operating voltage at DC rated value maximum":"72 V","with multi-phase operation at AC rated value":"440 V","with single-phase operation at AC rated value":"440 V","at AC according to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","supply voltage with single-phase operation at AC rated value":"230 V","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.1 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/faeb46fb68f56aaaf79f488be745caa2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=430041&mlfb=5SY7410-7"},"ai":{"faq":[{"question":"What are the key ratings of 5SY7410-7?","answer":"4-pole C-curve MCB, 400 VAC, 15 kA per EN 60898-1 / 30 kA per IEC 60947-2, 72 mm wide, IP20, ambient -40 to 75 °C."},{"question":"Will 5SY7410-7 drop into a panel specified around 5SY4140-7?","answer":"Both are 4-pole SENTRON MCBs on the same 72 mm footprint with the same DIN-rail mounting and terminal arrangement, so physical fit is identical. The main difference is the tripping characteristic — 5SY7410-7 is C-curve, while 5SY4140-7 uses a different curve — so verify coordination with the existing load type before swapping."},{"question":"What compliance documentation is available for 5SY7410-7?","answer":"The breaker is certified to IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077. It is halogen-free and silicon-free, supporting RoHS/REACH compliance for restricted-materials declarations."},{"question":"Where can I buy 5SY7410-7?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an inquiry for a firm offer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY7410-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY7410-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}