{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY7410-7CC","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY7410-7CC","canonicalUrl":"https://aoctrl.com/siemens/5SY7410-7CC","factsUrl":"https://aoctrl.com/api/mcp/products/5SY7410-7CC","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY7410-7CC, 4-pole miniature circuit breaker, C-trip curve, 10 A rated current, 25 kA breaking capacity at 400 V AC per IEC 60947-2, 5 kA per UL 1077.","salesMarkdown":"## SENTRON 5SY7410-7CC — 4-pole C-curve MCB for panel and machine builds It breaks 25 kA at 400 V AC per IEC 60947-2, and 5 kA per UL 1077 and CSA C22.2 No. 235 — enough headroom for most industrial panel secondary circuits and machine control cabinets. For a 10 A breaker, that means the magnetic trip fires between 50 A and 100 A — fast enough to clear a hard short, tolerant enough to ride through a brief inrush. Rated for 400 V AC phase-to-phase (440 V single- or multi-phase), with a max DC rating of 72 V — so it covers standard 400 V three-phase panels and some lower-voltage DC branches, but not a 125 V DC bus. Mounting position any, so it fits horizontal or vertical busbars without derating. IP20 with conductors connected — fine for enclosed panels, not for open washdown zones. Sealable cover is standard, which matters for panel builders who lock out circuits during maintenance. For a fast-moving 10 A C-curve 4-pole MCB, expect standard lead times — this is a common panel spare, not a long-tail oddity. With 25 kA IEC breaking capacity at 400 V, this breaker coordinates cleanly downstream of a larger molded-case or air circuit breaker in a typical distribution board. The 5 kA UL 1077 rating covers North American panelboard applications where the upstream device limits fault current.","metaTitle":"Siemens 5SY7410-7CC SENTRON MCB, 4P C-Curve 10 A, 25 kA IEC","metaDescription":"Siemens SENTRON 5SY7410-7CC miniature circuit breaker, 4-pole, C-curve, 10 A rated, 25 kA breaking capacity per IEC 60947-2. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["4-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"72 mm","title":"5SY7410-7CC","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Rated Value":"50/60 Hz","description":"Miniature circuit breaker 400 V 15kA, 4-pole, C, 10 A","Halogen-Free":"Yes","Silicon-Free":"Yes","Mounting type":"Quick assembly system","Number of poles":"4","Type of voltage":"AC","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Product designation":"Miniature circuit breaker","Protection class IP":"IP20, with connected conductors","at AC / rated value":"400 V","Overvoltage category":"III","Combined Terminal Top":"Yes","Number of width units":"4","Number of poles / Note":"4P","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","Combined Terminal Bottom":"Yes","circuit-breaker / Design":"5SY7CC","Suitability for operation":"Mechanical engineering / industry","Current / at AC / rated value":"10 A","Tripping characteristic class":"C","at DC / rated value / maximum":"72 V","Position / of power supply cord":"Any","acc. to IEC 60947-2 / rated value":"25 kA","Product feature / Touch protection":"Yes","Influence of the surrounding temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","at AC / acc. to UL 1077 and CSA C22.2 No.235":"5 kA","Product function / neutral conductor switching":"No","with multi-phase operation / at AC / rated value":"440 V","with single-phase operation / at AC / rated value":"440 V","Mechanical service life (switching cycles) / typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d046465d058516066fb36bf445b41177.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=199347&mlfb=5SY7410-7CC"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SY7410-7CC?","answer":"25 kA at 400 V AC per IEC 60947-2, and 5 kA per UL 1077 / CSA C22.2 No. 235. The 25 kA IEC rating gives solid fault-clearing headroom for industrial panel secondary circuits."},{"question":"Where can I buy 5SY7410-7CC and get current pricing?","answer":"Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote on this active-production MCB."},{"question":"What compliance documentation does Siemens provide for 5SY7410-7CC?","answer":"The breaker carries IEC 60947-2 and UL 1077 / CSA C22.2 No. 235 certifications. It is halogen-free and silicon-free, and rated for overvoltage category III. Standard Siemens declarations (CE, UKCA, RoHS, REACH) apply."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY7410-7CC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY7410-7CC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}