{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY7416-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY7416-6","canonicalUrl":"https://aoctrl.com/siemens/5SY7416-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SY7416-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY7416-6, B-curve miniature circuit breaker, 4-pole, 15 kA (EN 60898) / 25 kA (IEC 60947-2), 400 V AC, IP20.","salesMarkdown":"The 15 kA (EN 60898) and 25 kA (IEC 60947-2) ratings cover most industrial panel fault levels; the higher IEC figure applies when the MCB is used as a distribution breaker per 60947-2. At DC, it breaks 15 kA at 60 V, with a maximum DC operating voltage of 72 V. The IP20 rating means it is protected against solid objects over 12 mm (fingers) but not against moisture; install inside a sealed enclosure if washdown or condensation is present. Ambient temperature derating applies per: full rated current up to 55 °C at 95% humidity, then derate to 55% at 70 °C and 35% at 75 °C. Rated for mechanical engineering and industry, this MCB protects branch circuits in control panels, motor control centers, and distribution boards. The B-curve makes it a good fit for resistive loads, lighting, and small motor circuits where the inrush is under 5× rated current. The halogen-free and silicon-free construction is relevant for environments sensitive to outgassing — clean rooms, food processing, or aerospace-adjacent panels.","metaTitle":"Siemens 5SY7416-6 SENTRON MCB, B-Curve 4-Pole, 15/25 kA","metaDescription":"Siemens 5SY7416-6 SENTRON miniature circuit breaker, B-curve 4-pole, 15 kA (EN 60898) / 25 kA (IEC 60947-2) breaking capacity. Active production, sourced to order. Quoted on reques","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"76 mm","Width":"72 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Standard":"IEC / EN 60898-1, IEC / EN 60947-2 / UL1077","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"4P","Number Of Poles":"4","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","at AC rated value":"400 V","at DC rated value":"60 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Energy Limitation Class":"3","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"No","Number Of Modular Width Units":"4","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"B","according to EN 60898 rated value":"15 kA","according to IEC 60947-2 rated value":"25 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage Of The Operating Voltage":"AC","at DC according to IEC 60947-2 rated value":"15 kA","Value Range Of The Supply Voltage Frequency":"50/60 Hz","operating voltage at DC rated value maximum":"72 V","with multi-phase operation at AC rated value":"440 V","with single-phase operation at AC rated value":"440 V","at AC according to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","supply voltage with single-phase operation at AC rated value":"230 V","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.8 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f54d2d33cd246ff1a3fdb7d07b0add6a.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=10756&mlfb=5SY7416-6","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SY7416-6/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 5SY7416-6 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote."},{"question":"What is the breaking capacity of 5SY7416-6?","answer":"It is dual-rated: 15 kA per EN 60898 and 25 kA per IEC 60947-2 at 400 V AC. At DC it breaks 15 kA at 60 V."},{"question":"What compliance standards does 5SY7416-6 meet?","answer":"It complies with IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077. It is halogen-free and silicon-free."},{"question":"Will 5SY7416-6 drop into a panel specified for 5SY4116-6CC?","answer":"Both are 4-pole SENTRON MCBs with the same modular width (4 MW = 72 mm) and DIN-rail mount, so the mechanical fit is identical. The 5SY7416-6 carries a B-curve; verify the 5SY4116-6CC's curve and breaking capacity against your circuit requirements before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY7416-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY7416-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}