{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY7513-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY7513-7","canonicalUrl":"https://aoctrl.com/siemens/5SY7513-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SY7513-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY7513-7 miniature circuit breaker, C-curve, 2-pole 1P+N, 15 kA per EN 60898 / 25 kA per IEC 60947-2, 230 VAC, 60 VDC, 2 MW units wide.","salesMarkdown":"The 2-pole 1P+N design switches the neutral conductor, which matters for single-phase subcircuits where isolating both line and neutral is required by local code or the equipment specification. Breaking capacity is dual-rated: 15 kA per EN 60898 and 25 kA per IEC 60947-2. For UL 1077-listed supplementary protection, the interrupting rating is 5 kA. Rated operational voltage is 230 VAC single-phase, with a DC rating of 60 V and a maximum DC voltage of 72 V. Frequency is 50/60 Hz. This breaker is rated for mechanical engineering and industry — think control cabinets for conveyors, pumps, packaging lines, or machine tools where the C-curve matches the load profile. The sealable design lets a panel builder lock the toggle position after commissioning, preventing unauthorized reset on a locked-out circuit.","metaTitle":"Siemens 5SY7513-7 SENTRON MCB, C-Curve 2-Pole 1P+N, 15/25 kA","metaDescription":"Siemens 5SY7513-7 SENTRON miniature circuit breaker, C-curve, 2-pole 1P+N, 15 kA (EN 60898) / 25 kA (IEC 60947-2). Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Standard":"IEC / EN 60898-1, IEC / EN 60947-2 / UL1077","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","at AC rated value":"230 V","at DC rated value":"60 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Energy Limitation Class":"3","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"Yes","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"C","according to EN 60898 rated value":"15 kA","according to IEC 60947-2 rated value":"25 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage Of The Operating Voltage":"AC","at DC according to IEC 60947-2 rated value":"15 kA","Value Range Of The Supply Voltage Frequency":"50/60 Hz","operating voltage at DC rated value maximum":"72 V","with single-phase operation at AC rated value":"250 V","at AC according to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","supply voltage with single-phase operation at AC rated value":"230 V","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.4 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=458991&mlfb=5SY7513-7","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SY7513-7/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SY7513-7?","answer":"Dual-rated: 15 kA per EN 60898 and 25 kA per IEC 60947-2 at 230 VAC. For UL 1077 supplementary protection, the interrupting rating is 5 kA. The 25 kA figure is the one to use for industrial panel SCCR."},{"question":"What compliance documentation does this brand provide for 5SY7513-7?","answer":"The breaker is certified to IEC/EN 60898-1 and IEC/EN 60947-2, with UL 1077 and CSA C22.2 No. 235 listing. Halogen-free and silicon-free. Standard manufacturer declarations for RoHS and REACH are available on request."},{"question":"Where can I buy 5SY7513-7?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm offer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY7513-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY7513-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}