{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY7516-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY7516-7","canonicalUrl":"https://aoctrl.com/siemens/5SY7516-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SY7516-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY7516-7 miniature circuit breaker, 2-pole 1P+N, C-curve, 15 kA per EN 60898 / 25 kA per IEC 60947-2, 230 V AC, 60 V DC, 2 MW units, IP20.","salesMarkdown":"Rated for 230 V AC single-phase (250 V max) and 60 V DC (72 V max), so it covers standard single-phase lighting and receptacle circuits as well as DC control loops up to 60 V — but not three-phase line-to-line applications above 250 V. Sealable cover allows the installer to lock settings after commissioning. Compliant with IEC/EN 60898-1 for residential MCB duty and IEC/EN 60947-2 / UL 1077 for industrial supplementary protection — the dual certification means it can be specified for either a domestic consumer unit or an industrial panel, but the applicable breaking capacity and standard must match the installation's requirements. Halogen-free and silicon-free construction, suitable for clean-room or sensitive electronic environments where outgassing must be minimized. Vibration resistance per IEC 60068-2-6 covers ±1 mm at 5–25 Hz and 50 m/s² at 25–150 Hz — adequate for machine-mounted enclosures.","metaTitle":"Siemens 5SY7516-7 SENTRON MCB, C-curve 2-pole 1P+N, 15/25 kA","metaDescription":"Siemens 5SY7516-7 SENTRON miniature circuit breaker, 2-pole 1P+N, C-curve, 15 kA (EN 60898) / 25 kA (IEC 60947-2). Active production, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","title":"5SY7516-7","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Standard":"IEC / EN 60898-1, IEC / EN 60947-2 / UL1077","description":"Miniature circuit breaker 230 V 15kA, 1+N-pole, C, 16A, D=70 mm","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","at AC rated value":"230 V","at DC rated value":"60 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Energy Limitation Class":"3","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"Yes","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"C","according to EN 60898 rated value":"15 kA","according to IEC 60947-2 rated value":"25 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage Of The Operating Voltage":"AC","at DC according to IEC 60947-2 rated value":"15 kA","Value Range Of The Supply Voltage Frequency":"50/60 Hz","operating voltage at DC rated value maximum":"72 V","with single-phase operation at AC rated value":"250 V","at AC according to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","supply voltage with single-phase operation at AC rated value":"230 V","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.6 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/78672ded2e2d00e2482b5efaf2d639f2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=453703&mlfb=5SY7516-7"},"ai":{"faq":[{"question":"Where can I buy 5SY7516-7 and how do I get a price?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time; the part is sourced to order through independent distribution channels."},{"question":"What compliance documentation does Siemens provide for 5SY7516-7?","answer":"The part carries dual certification to IEC/EN 60898-1 and IEC/EN 60947-2 / UL 1077. It is halogen-free and silicon-free. RoHS/REACH declarations are standard for the SENTRON series."},{"question":"Will 5SY7516-7 drop into a panel specified around 5SY4116-7CV without rewiring?","answer":"Both are 2-pole 1P+N C-curve MCBs with the same 2 MW width (36 mm) and DIN-rail mount. The 5SY7516-7 carries higher breaking capacity (25 kA vs the 5SY4116-7CV's lower rating) and is the physically compatible upgrade — no rewiring needed, but verify the downstream SCCR coordination."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY7516-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY7516-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}