{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY7613-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY7613-6","canonicalUrl":"https://aoctrl.com/siemens/5SY7613-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SY7613-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY7613-6 miniature circuit breaker, 4-pole (3P+N), 13 A, tripping characteristic B, breaking capacity 15 kA per EN 60898 / 25 kA per IEC 60947-2, IP20.","salesMarkdown":"It carries a 13 A rated current at 50/60 Hz AC with a B tripping curve — meaning it trips between 3 and 5 times rated current, which is the standard choice for resistive and general-purpose loads like lighting circuits, control transformers, and small motor starters in industrial panels. ## Sizing and derating for panel temperature At 35 °C ambient the breaker carries the full 13 A. Derate to 12.48 A at 40 °C, 12.22 A at 45 °C, 11.95 A at 50 °C, 11.67 A at 55 °C, and 11.39 A at 60 °C. For a panel that runs warm — say 50 °C inside the enclosure — you're effectively working with a 12 A device, so size upstream protection accordingly. Mounting position is any orientation.","metaTitle":"Siemens 5SY7613-6 SENTRON MCB, 4P, 13 A, B-Curve, 15 kA","metaDescription":"Siemens 5SY7613-6 SENTRON miniature circuit breaker, 4-pole 3P+N, 13 A rated, B tripping curve. Breaking capacity 15 kA per EN 60898, 25 kA per IEC 60947-2. IP20. Active production","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["4-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"72 mm","title":"5SY7613-6","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","description":"Miniature circuit breaker 400 V 15kA, 3+N-pole, B, 13 A, D=70 mm","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"4","Type Of Voltage":"AC","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"13 A","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Number Of Poles / Note":"3P+N","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","at 35 °C / rated value":"13 A","at 40 °C / rated value":"12.48 A","at 45 °C / rated value":"12.22 A","at 50 °C / rated value":"11.95 A","at 55 °C / rated value":"11.67 A","at 60 °C / rated value":"11.39 A","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Number Of Modular Width Units":"4","Tripping Characteristic Class":"B","acc. to EN 60898 / rated value":"15 kA","Position / Of Power Supply Cord":"Any","acc. to IEC 60947-2 / rated value":"25 kA","Product Feature / Touch Protection":"Yes","Supply Voltage Frequency / Rated Value":"50/60 Hz","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","at DC / acc. to IEC 60947-2 / rated value":"15 kA","at AC / acc. to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance / acc. to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Product Function / Neutral Conductor Switching":"Yes","with multi-phase operation / at AC / rated value":"440 V","operating voltage / at DC / rated value / maximum":"72 V","with single-phase operation / at AC / rated value":"440 V","Mechanical Service Life (Operating Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d61f35d1ff51f9c950f56e44fda99ccc.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=438251&mlfb=5SY7613-6"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SY7613-6?","answer":"Rated 15 kA per EN 60898 and 25 kA per IEC 60947-2. Use the 60947-2 figure for industrial control panel coordination."},{"question":"Where can I buy 5SY7613-6?","answer":"Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an inquiry for a firm quote."},{"question":"Does 5SY7613-6 replace 5SY4140-7?","answer":"No direct replacement — 5SY4140-7 is a different pole/current variant. The 5SY7613-6 is a 4-pole 13 A B-curve breaker; the 5SY4140-7 is a different configuration. Verify your BOM's pole count and rating before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY7613-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY7613-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}