{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SY8506-7","brand":"Siemens","brandSlug":"siemens","productSlug":"5SY8506-7","canonicalUrl":"https://aoctrl.com/siemens/5SY8506-7","factsUrl":"https://aoctrl.com/api/mcp/products/5SY8506-7","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SY8506-7 miniature circuit breaker, C characteristic, 2-pole (1P+N), 50 kA at 230 V AC per IEC 60947-2, 15 kA at 60 V DC, width 36 mm, depth 76 mm.","salesMarkdown":"It carries a 50 kA rated short-circuit capacity at 230 V AC per IEC 60947-2, and 15 kA at 60 V DC per the same standard — figures that tell you it can interrupt high-fault currents without upstream coordination in most panel designs. Under UL 1077 the interrupting rating is 5 kA, so if the installation falls under a UL 508A listed assembly, verify the available fault current against that lower threshold. The IP20 rating applies with connected conductors, meaning the busbar and wiring must be in place before the ingress protection is valid; the terminals themselves are not sealed. ## Environmental and service life Rated for ambient temperatures from -40 °C to 75 °C, with humidity limits that taper: max 95% RH at 55 °C, down to 35% at 75 °C. Vibration resistance per IEC 60068-2-6 is ±1 mm at 5 to 25 Hz and 50 m/s² at 25 to 150 Hz, which covers most industrial panel vibration profiles. Pollution degree 3 means it's suitable for environments with conductive or dry non-conductive pollution — typical for factory floors not in clean-room conditions.","metaTitle":"Siemens 5SY8506-7 SENTRON MCB, C-Curve 2-Pole 50kA, 76mm Dep","metaDescription":"Siemens 5SY8506-7 SENTRON miniature circuit breaker, C characteristic, 2-pole (1P+N), 50 kA at 230 V AC per IEC 60947-2, 15 kA at 60 V DC. Active production, sourced to order. Requ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"76 mm","Width":"36 mm","title":"5SY8506-7","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Sealable":"Yes","Standard":"IEC / EN 60947-2 / UL1077","description":"Miniature circuit breaker 230 V D=70 mm 25 kA according to EN 60947-2, 1P+N, C6","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"Quick assembly system","Mounting Position":"any","at AC rated value":"230 V","at DC rated value":"60 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Product Designation":"Miniature circuit breaker","protection class IP":"IP20, with connected conductors","Overvoltage Category":"III","Combined Terminal Top":"Yes","Combined Terminal Bottom":"Yes","Suitability For Operation":"Mechanical engineering / industry","Neutral Conductor Switching":"Yes","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"Any","Tripping Characteristic Class":"C","according to IEC 60947-2 rated value":"50 kA","Influence Of The Surrounding Temperature":"max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C","Type Of Voltage Of The Operating Voltage":"AC","at DC according to IEC 60947-2 rated value":"15 kA","Value Range Of The Supply Voltage Frequency":"50/60 Hz","operating voltage at DC rated value maximum":"72 V","with single-phase operation at AC rated value":"250 V","at AC according to UL 1077 and CSA C22.2 No.235":"5 kA","vibration resistance according to IEC 60068-2-6":"±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","supply voltage with single-phase operation at AC rated value":"230 V","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.6 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/466c7a0aab7e274881bb41e4f8d5e513.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=367767&mlfb=5SY8506-7"},"ai":{"faq":[{"question":"Where can I buy 5SY8506-7 and how do I get a price?","answer":"The 5SY8506-7 is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time."},{"question":"What is 5SY8506-7's listed depth (76 mm) on this component line?","answer":"The overall depth is 76 mm; the installation depth (the portion behind the DIN rail) is 70 mm."},{"question":"What compliance documentation does this brand provide for 5SY8506-7 (RoHS, REACH, UL, IEC)?","answer":"The 5SY8506-7 is certified to IEC/EN 60947-2 and UL 1077. It is halogen-free and silicon-free. RoHS and REACH declarations are standard with the SENTRON series; the manufacturer provides them on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SY8506-7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SY8506-7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}