{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"61F-G2-AC100/200","brand":"Omron","brandSlug":"omron","productSlug":"61F-G2-AC100-200","canonicalUrl":"https://aoctrl.com/omron/61F-G2-AC100-200","factsUrl":"https://aoctrl.com/api/mcp/products/61F-G2-AC100%2F200","rawCanonicalId":null},"summary":{"shortDescription":"Omron 61F series, Type High/Low Level level controller, 100/200VAC supply, relay output, 0-4kOhm sensitivity, chassis mount.","salesMarkdown":"The Omron 61F-G2-AC100/200 is a conductive-type level controller from the 61F series, configured for high/low level detection — meaning it monitors two probe points to maintain a fill/drain cycle or trigger a high-level alarm. The 100/200VAC supply input lets it run off common line voltages without a separate control transformer. Sensitivity is adjustable from 0 to 4kOhm, which covers most water-based liquids (tap water, wastewater, dilute chemicals) but not deionized or distilled water where conductivity is too low. The two SPDT relays (one Form C per channel) each switch 5A at 220VAC, enough to drive a small pump contactor or alarm indicator directly. Chassis-mount form factor — screws onto a backplate or inside a panel enclosure. Screw terminals for all connections: supply, probe electrodes, and relay outputs. The control-to-sensor distance rating of 1km means the sensing electrodes can be located at the tank while the controller sits in the electrical room, as long as the probe wiring stays within that loop resistance. Wiring practice: keep probe wires separate from power cables to avoid false triggering from coupled noise.","metaTitle":"Omron 61F-G2-AC100/200 Level Controller, High/Low Type, 100/","metaDescription":"Omron 61F-G2-AC100/200 high/low level controller. 100/200VAC supply, 5A relay output, 0-4kOhm sensitivity, 1km sensor distance. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["General Purpose Relays"],"specifications":{"Type":"High/Low Level","Series":"61F","Weight":"1.7 lbs (771.1 g)","Package":"Bulk","Features":"Alarm High - Contact","Output Type":"Relay (2)","Sensitivity":"0 ~ 4kOhm","Contact Form":"SPDT (1 Form C), SPDT (2 Form C)","Mounting Type":"Chassis Mount","lifecycle_stage":"mature","Voltage - Supply":"100/200VAC","Termination Style":"Screw Terminal","Operating Temperature":"-10°C ~ 55°C","Contact Rating @ Voltage":"5A @ 220VAC","Distance - Control To Sensor (Max)":"1km"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$386.55 – $849.01","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5bab43a36b8b8bb4f739afcf82140702.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/61F-G2-AC100%2F200/alternatives.json"},"ai":{"faq":[{"question":"What is the 61F-G2-AC100/200 used for?","answer":"It is a conductive level controller for high/low level detection in water and conductive liquid tanks — controls fill/drain cycles or triggers alarms based on two probe electrodes."},{"question":"What is the maximum distance between the controller and the tank sensors?","answer":"Up to 1km, as long as the loop resistance stays within the 0-4kOhm sensitivity range."},{"question":"Where can I buy the 61F-G2-AC100/200?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/omron/61F-G2-AC100-200","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/omron/61F-G2-AC100-200 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}