{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"61F-G4N AC110/220","brand":"Omron","brandSlug":"omron","productSlug":"61F-G4N-AC110-220","canonicalUrl":"https://aoctrl.com/omron/61F-G4N-AC110-220","factsUrl":"https://aoctrl.com/api/mcp/products/61F-G4N%20AC110%2F220","rawCanonicalId":null},"summary":{"shortDescription":"Omron 61F series, Type High/Low Level, 61F-G4N AC110/220, 110/220VAC supply, 0~4kOhm sensitivity, SPDT relay outputs, DIN rail mount.","salesMarkdown":"Outputs are five SPDT relays — two Form C and three Form C — each rated 3A at 200VAC. That gives you independent control for pump start/stop, high-level alarm, low-level alarm, and a spare for a remote indicator or valve. The control-to-sensor distance is rated up to 1 km, which covers remote tank farms or elevated reservoirs where the controller sits in the main panel and the electrodes are field-wired out to the tank. The package is bulk, so it ships individually for one-off replacements or in quantity for panel builds.","metaTitle":"Omron 61F-G4N AC110/220 Level Controller, High/Low, 110/220V","metaDescription":"Omron 61F-G4N AC110/220 level controller, High/Low type, 110/220VAC supply, 0~4kOhm sensitivity, 5 relay outputs, 1km sensor distance. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["General Purpose Relays"],"specifications":{"Type":"High/Low Level","Series":"61F","Weight":"1.9 lbs (861.8 g)","Package":"Bulk","Features":"Idling Prevention, Level Indication","Output Type":"Relay (6)","Sensitivity":"0 ~ 4kOhm","Contact Form":"SPDT (2 Form C), SPDT (3 Form C)","Mounting Type":"DIN Rail","lifecycle_stage":"mature","Voltage - Supply":"110/220VAC","Termination Style":"Screw Terminal","Operating Temperature":"-10°C~55°C","Contact Rating @ Voltage":"3A @ 200VAC","Distance - Control To Sensor (Max)":"1km"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e5b5dc1f0cd8beb6749356b26b621be0.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/61F-G4N%20AC110%2F220/alternatives.json"},"ai":{"faq":[{"question":"What is the 61F-G4N AC110/220 used for?","answer":"It is a High/Low level controller that detects liquid level via electrode conductivity. Typical applications include pump control for water tanks, sump basins, and process vessels where two-level (high and low) control is needed."},{"question":"Where can I buy the 61F-G4N AC110/220 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What does the 0~4kOhm sensitivity range mean?","answer":"It sets the conductivity threshold at which the controller detects liquid. A lower setting (e.g., 0.5 kOhm) works for high-conductivity liquids like salt water; a higher setting (e.g., 3.5 kOhm) is needed for low-conductivity liquids like deionized water or light process fluids."},{"question":"What compliance documentation is available for this part?","answer":"The evidence does not list specific compliance certifications (RoHS, REACH, UL, IEC) for this model. Standard Omron 61F series documentation typically includes a datasheet and instruction manual; request these with your RFQ if needed for your compliance review."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/omron/61F-G4N-AC110-220","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/omron/61F-G4N-AC110-220 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}