{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"61F-GP-ND AC120","brand":"Omron","brandSlug":"omron","productSlug":"61F-GP-ND-AC120","canonicalUrl":"https://aoctrl.com/omron/61F-GP-ND-AC120","factsUrl":"https://aoctrl.com/api/mcp/products/61F-GP-ND%20AC120","rawCanonicalId":null},"summary":{"shortDescription":"Omron 61F Series, Type High/Low Level, Output Relay, SPDT (2 Form C), Voltage - Supply 120VAC, Sensitivity 0 ~ 1.3kOhm, Termination Style Plug In, 11 Pin (Octal), Socketable Mounting.","salesMarkdown":"The Omron 61F-GP-ND AC120 is a conductive-type level controller that detects liquid presence by sensing resistance between probes. It's set up as a High/Low level controller, meaning it can manage both fill-to-a-level and drain-to-a-level sequences in a tank. The sensitivity adjustment spans 0 to 1.3 kOhm, so you tune it to the conductivity of whatever liquid you're monitoring — clean water at one end, something with higher resistivity further up the scale. Power it with 120VAC, and the relay output gives you a SPDT (2 Form C) contact rated 3A at 250VAC. That's enough to kick a contactor or alarm directly without an interposer relay. The socketable 11-pin octal base means replacement is a pull-and-plug job — no rewiring when the controller itself needs swapping. The control-to-sensor distance is rated up to 1 km, so the probes can be a long way from the controller. For current pricing and availability, submit an RFQ.","metaTitle":"Omron 61F-GP-ND AC120 Level Controller, 120VAC, SPDT Relay","metaDescription":"Omron 61F-GP-ND AC120 conductive level controller, high/low type, 0-1.3kOhm sensitivity, SPDT relay output, 120VAC supply, socketable 11-pin octal. Active production, sourced to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["General Purpose Relays"],"specifications":{"Type":"High/Low Level","Series":"61F","Weight":"0.342 lb (155.13 g)","Package":"Bulk","Output Type":"Relay","Sensitivity":"0 ~ 1.3kOhm","Contact Form":"SPDT (2 Form C)","Mounting Type":"Socketable","lifecycle_stage":"mature","Voltage - Supply":"120VAC","Termination Style":"Plug In, 11 Pin (Octal)","Operating Temperature":"-10°C~55°C","Contact Rating @ Voltage":"3A @ 250VAC","Distance - Control To Sensor (Max)":"1km"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/522756c82eecdf8715481f0dac2b20b3.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/61F-GP-ND%20AC120/alternatives.json"},"ai":{"faq":[{"question":"What type of level controller is the 61F-GP-ND AC120?","answer":"It's a High/Low level type, meaning it can control both fill and drain operations based on probe resistance changes."},{"question":"What is the sensitivity range of the 61F-GP-ND AC120?","answer":"The sensitivity is adjustable from 0 to 1.3 kOhm, allowing you to match the probe circuit to the conductivity of the target liquid."},{"question":"What is the supply voltage for the 61F-GP-ND AC120?","answer":"It requires a 120VAC supply."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/omron/61F-GP-ND-AC120","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/omron/61F-GP-ND-AC120 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}