{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1132-4BB31-7AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1132-4BB31-7AB0","canonicalUrl":"https://aoctrl.com/siemens/6AG1132-4BB31-7AB0","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1132-4BB31-7AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens S7-1200 digital output module 6AG1132-4BB31-7AB0, 2 transistor outputs, 24 V DC, 2 A rated per channel, diagnostics per channel, 15 mm wide.","salesMarkdown":"## Panel Integration Brief Wire-break and short-circuit detection are channel-granular and can be separately enabled or disabled via diagnostics functions. The group error SF LED gives a visual summary. Outputs respond to CPU/memory STOP by substituting a value or holding the last valid state. Shielded cable run up to 1 000 m, unshielded up to 600 m. Power loss typ. 1.4 W. ## Switching Performance Resistive load switching up to 100 Hz; inductive load limited to 2 Hz with 0.5 H; lamp load max 10 Hz. Transition times: 0 → 1 at 100 µs, 1 → 0 at 400 µs. Reverse polarity protection is present when sharing the load voltage with the power module.","metaTitle":"Siemens 6AG1132-4BB31-7AB0 S7-1200 DO 2A/ch","metaDescription":"Current production S7-1200 2-output module, 24 V DC, 2 A per channel, per-channel diagnostics, -25 to 70 °C. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"Max.":"70 °C; = Tmax","Min.":"-25 °C; = Tmin","Depth":"52 mm","Width":"15 mm","Height":"81 mm","Remark":"3 byte","Wire-break":"Yes; channel by channel","Lower Limit":"12 Ω","Upper Limit":"3 400 Ω","For Uprating":"No","With Packing":"2 bit","Short-circuit":"Yes; channel by channel","Shielded, Max.":"1 000 m","Weight, approx.":"40 g","lifecycle_stage":"current","\"0\" To \"1\", Max.":"100 µs","\"1\" To \"0\", Max.":"400 µs","Power loss, typ.":"1.4 W","Rated value (DC)":"24 V; From power module","Unshielded, Max.":"600 m","On Lamp Load, Max.":"10 Hz","Between The Channels":"No","Diagnostics function":"Yes; Can be read out","For Signal \"1\", Min.":"L+ (-1 V)","Group error SF (red)":"Yes","Isolation tested with":"500 V DC","Diagnostics wire break":"Disable / enable","Type of digital output":"Transistor","Current per module, max.":"4 A","Response threshold, typ.":"4 A","Short-circuit protection":"Yes","Diagnostics short-circuit":"Disable / enable","Number of digital outputs":"2","With Inductive Load, Max.":"2 Hz; 0,5 H","With Resistive Load, Max.":"100 Hz","For Signal \"1\" Rated Value":"2 A","Reverse voltage protection":"Yes; when using the same load voltage as on the power module","Controlling a digital input":"Yes","Response to CPU/master STOP":"Substitute a value/keep last value","Reverse polarity protection":"Yes; polarity reversal can lead to the digital outputs being connected through","Substitute values connectable":"Yes; 0/1","Address space per module, max.":"1 byte","For Redundant Control Of A Load":"Yes; per module","from backplane bus 3.3 V DC, max.":"10 mA","For Signal \"0\" Residual Current, Max.":"0.5 mA","Between The Channels And Backplane Bus":"Yes","For Signal \"1\" Permissible Range, Max.":"2.4 A","For Signal \"1\" Permissible Range, Min.":"7 mA","Status indicator digital output (green)":"Yes","from load voltage L+ (without load), max.":"5 mA; Per channel","Installation altitude above sea level, max.":"5 000 m","Limitation of inductive shutdown voltage to":"-55 to -60 V, typ. L+( )","Ambient air temperature-barometric pressure-altitude":"Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)","Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04":"Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e51396e92b3a763c69906944371f4bb2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=142432&mlfb=6AG1132-4BB31-7AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6AG1132-4BB31-7AB0/alternatives.json"},"ai":{"faq":[{"question":"What is the maximum operating temperature?","answer":"The module is rated for a maximum ambient temperature of 70 °C."},{"question":"What is the minimum operating temperature?","answer":"The module is rated down to -25 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1132-4BB31-7AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1132-4BB31-7AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}