{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1134-3AB00-7AY0","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1134-3AB00-7AY0","canonicalUrl":"https://aoctrl.com/siemens/6AG1134-3AB00-7AY0","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1134-3AB00-7AY0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SITOP DC UPS module 6AG1134-3AB00-7AY0, 24 V DC, 10 A rated, 30 A peak, screw terminals, DIN rail mount.","salesMarkdown":"The Siemens 6AG1134-3AB00-7AY0 is a SITOP DC UPS module sized for a 24 V DC control bus. Rated for 10 A continuous with a 30 A peak capacity, it handles the inrush of a contactor bank or a solenoid manifold without dropping the bus. Input and output are both 24 V DC screw terminals accepting 0.2…6 mm² wire. The module snaps onto a standard DIN rail (EN 60715 35x7.5/15) and measures 50 mm wide by 125 mm deep by 139 mm tall – fits a narrow backplane slot. IP20 protection class keeps it inside a clean panel only. ## Ratings that matter for sizing The 10 A rated current sets the continuous load you can buffer; the 30 A peak figure covers transient loads for up to 30 ms at 3× rated, or 1.5× rated for 5 seconds per minute – enough for a motor starter inrush or a capacitor bank during a bus transfer. Output voltage follows input minus about 0.2 V, so you don't lose a diode drop; the module stays transparent in normal operation. Typical active power is 240 W at nominal input. Charging current for the connected battery module is specified at 0.1 A (trickle) and 3 A (fast charge), though the exact split depends on the battery module model. Startup delay is typical 60 ms – the module waits for the bus to stabilize before switching to buffered mode. ## Signaling and diagnostics for the controls integrator Three floating contact outputs and LED indicators report system status: green LED and closed NO contact when energy storage is above 85%; yellow LED when actively buffering via battery; red LED (steady or flashing) for low battery pre-warning (<20.4 V DC) or when battery replacement is needed. The changeover contacts are rated for DC 60 V / 1 A or AC 30 V / 1 A – suitable for direct connection to a PLC input. ## EMC and compliance – panel builder note CE marked. Conducted and radiated emissions meet EN 55022 Class B (residential/commercial), so this module won't force a higher EMC shield than the rest of the panel. Immunity complies with EN 61000-6-2 industrial environment standard. Operating resource protection class III means it relies on the SELV supply upstream. This order code is current production. Sourced to order through Siemens channels; lead time depends on quantity and factory backlog. Drop a quote request on this page for a delivery estimate.","metaTitle":"Siemens 6AG1134-3AB00-7AY0 SITOP DC UPS, 24V 10A","metaDescription":"Siemens SITOP DC UPS module, 24 V DC, 10 A rated, 30 A peak. CE marked, EN 55022 Class B, current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"Top":"50 mm","Left":"0 mm","Right":"0 mm","title":"6AG1134-3AB00-7AY0","Bottom":"50 mm","At Input":"24 V DC: 2 screw terminals for 0.2 ... 6 mm²/24 ... 13 AWG","At Output":"24 V DC: 2 screw terminals for 0.2 ... 6 mm²/24 ... 13 AWG","CE marking":"Yes","Rated Value":"10 A","description":"SIPLUS PS UPS1600 10A based on 6EP4134-3AB00-0AY0 with conformal coating, -25…+70 °C, uninterruptible power supply input: 24 V DC output: 24 V DC/ 10 A","Peak Current":"30 A","MTBF at 40 °C":"415 574 h","lifecycle_stage":"current","Charging Current":"0.1 A, 3 A","Fastening Method":"Snaps onto DIN rail EN 60715 35x7.5/15","In Buffering Mode":"Buffered mode: LED yellow (Bat), floating changeover contact \"OK/Bat\" to setting \"Bat\"; Prewarning battery voltage < 20.4 VDC: LED red (alarm), floating changeover contact \"Alarm/Bat\" to setting \"Alarm\"; Energy storage > 85%: LED green (Bat > 85%), floating NO contact \"Bat > 85\" closed","Other Information":"Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)","In Normal Operation":"0 ... 30 A","Input Voltage Range":"21 ... 29 V DC","protection class IP":"IP20","For Normal Operation":"Normal operation: LED green (OK), floating changeover contact \"Bat/OK\" to setting \"OK\" (\"OK\" means: Voltage of the supplying power supply unit is greater than cut-in threshold set at the DC UPS module); Lack of buffer standby: LED red (alarm), floating changeover contact \"Alarm/Bat\" to setting \"Alarm\"; Battery replacement required: LED red (alarm) flashing with approx. 0.25 Hz, floating changeover contact \"Alarm/Bat\" switching with approx. 0.25 Hz; Energy storage > 85%: LED green (Bat > 85%), floating NO contact \"Bat > 85\" closed; Permissible contact current capacity: DC 60 V/1 A or AC 30 V /1 A","Depth Of The Enclosure":"125 mm","Electrical Accessories":"Battery module","Type Of Energy Storage":"with batteries","Voltage Curve At Input":"DC","Width Of The Enclosure":"50 mm","Design Of The Interface":"without","Height Of The Enclosure":"139 mm","For Emitted Interference":"EN 55022 Class B","For Interference Immunity":"EN 61000-6-2","Formula For Output Voltage":"Vin - approx. 0.2 V","Startup Delay Time Typical":"60 ms","Supplied Active Power Typical":"240 W","Type Of Electrical Connection":"screw-type terminals","product component PC interface":"No","For Rechargeable Battery Module":"24 V DC: 2 screw terminals for 0.2 ... 6 mm²/24 ... 13 AWG","supply voltage at DC rated value":"24 V","Design Of Short-Circuit Protection":"Limitation to 3 x I rated for 30 ms/min; through-conductivity for 1.5 x I rated for 5 sec/min","Operating Resource Protection Class":"Class III","in buffering mode at DC rated value":"24 V","in normal operation at DC rated value":"24 V","For Control Circuit And Status Message":"14 screw terminals for 0.2 ... 1.5 mm²/24 ... 16 AWG","output voltage in buffering mode at DC":"18.5 ... 27 V","reference code according to IEC 81346-2":"TA","Adjustable Charging Current Maximum Note":"Automatically depending on battery module","Property Of The Output Short-Circuit Proof":"Yes","Galvanic Isolation Between Input And Output":"No","Ambient Temperature During Storage And Transport":"-40 ... +85","Design Of The Mains Power Cut Bridging-Connection":"Adjustable range using rotary coding switch: 0.5 min, 1 min, 2 min, 5 min, 10 min, 20 min, max. buffering time","Voltage Increase Time Of The Output Voltage Typical":"60 ms","In Case Of Operation On Rechargeable Battery Typical":"6 W","input current at rated input voltage 24 V rated value":"14 A; for max. charging current (3 A)","Adjustable Response Value Voltage For Buffer Connection":"21 ... 25 V; Adjustable: 21 V, 21.5 V, 22 V, 22.5 V, 23 V, 24 V, 25 V DC","Installation Altitude At Height Above Sea Level Maximum":"6 000 m","Product Feature Of The Enclosure Housing Can Be Lined Up":"Yes","Adjustable Response Value Voltage For Buffer Connection Preset":"21.5 V","Chemical Resistance To Commercially Available Cooling Lubricants":"Yes; incl. diesel and oil droplets in the air","Reverse Polarity Protection Against Input Voltage Polarity Reversal":"Yes","Ambient Temperature In Horizontal Mounting Position During Operation":"-25 ... +70; with natural convection","At Rated Output Voltage For Rated Value Of The Output Current Typical":"6 W","Reverse Polarity Protection Against Energy Storage Unit Polarity Reversal":"Yes","Ambient Condition Relating To Ambient Temperature - Air Pressure - Installation Altitude":"In case of operation at altitudes of 2000 - 6000 m above sea level: Output power derating of -7.5 %/1000 m or reduction of the ambient temperature by 5 K/1000 m","product conformity of the coating Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A":"Yes; Conformal Coating, Class A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e51396e92b3a763c69906944371f4bb2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=907785&mlfb=6AG1134-3AB00-7AY0"},"ai":{"faq":[{"question":"What compliance markings does this module carry?","answer":"CE marking is confirmed. Emissions meet EN 55022 Class B; immunity per EN 61000-6-2. Operating class III (SELV). RoHS/UL/REACH are not listed in this specification."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1134-3AB00-7AY0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1134-3AB00-7AY0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}