{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1134-4GB01-2AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1134-4GB01-2AB0","canonicalUrl":"https://aoctrl.com/siemens/6AG1134-4GB01-2AB0","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1134-4GB01-2AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIPLUS S7-1200 analog input module, order code 6AG1134-4GB01-2AB0, 2 inputs 4–20 mA, temperature range -25…60 °C, 15 mm wide.","salesMarkdown":"The 6AG1134-4GB01-2AB0: Rated for -25 °C to 60 °C ambient, this module handles unheated cabinets or warm panels without derating. The 2-input count sets the BOM line for analog sensing; each input is individually parameterizable for wire-break detection (enabled by default). Selectable integration time of 16,7 ms or 20 ms provides line-cycle rejection. Digital filtering offers 1x, 4x, 32x, or 64x cycle times; basic conversion per channel is 65 ms. Group diagnostics and overflow/underflow alarms are enable/disable per channel group, and the module reports a group error (SF LED red) on any fault. Isochronous mode is not supported, so this is not the right part for time-synchronous applications. Reverse-polarity protection on each input limits destruction to 35 mA per channel. CE and UL approvals are present — sufficient for most industrial control panels but verify if your facility requires additional marks.","metaTitle":"Siemens 6AG1134-4GB01-2AB0 SIPLUS S7-1200 Analog Input, 2 In","metaDescription":"Siemens 6AG1134-4GB01-2AB0 SIPLUS S7-1200 analog input module, 2 channels, 4-20 mA, -25 to 60°C, CE & UL. Active production, source to an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"Max.":"60 °C; = Tmax","Min.":"-25 °C; = Tmin","Depth":"52 mm","Width":"15 mm","title":"6AG1134-4GB01-2AB0","Height":"81 mm","Remark":"4 byte","CE mark":"Yes","Step: low":"Yes; 4x cycle time","Step: High":"Yes; 64x cycle time","Step: None":"Yes; 1x cycle time","Wire-break":"Yes","Group error":"Yes","UL approval":"Yes","description":"SIPLUS ET 200S EM 2AI standard I based on 6ES7134-4GB01-0AB0 with conformal coating, -25…+60 °C,","Step: Medium":"Yes; 32x cycle time","4 mA to 20 mA":"Yes; on 50 ohms","Shielded, Max.":"200 m","Parameterizable":"Yes; In four stages by means of digital filtering","Weight, approx.":"40 g","lifecycle_stage":"current","Isochronous mode":"No","Power loss, typ.":"0.6 W","Rated value (DC)":"24 V; From power module","Group diagnostics":"Disable / enable","Overflow/underflow":"Disable / enable","Between The Channels":"No","Group error SF (red)":"Yes","Integration time (ms)":"16,7 / 20 ms","Isolation tested with":"500 V DC","Measurement principle":"integrating","Number of analog inputs":"2","Reverse polarity protection":"Yes; Destruction limit 35 mA per channel","Conversion time (per channel)":"65 ms; 55 / 65 ms","Address space per module, max.":"4 byte","Cycle time (all channels) max.":"Number of active channels per module x basic conversion time","from backplane bus 3.3 V DC, max.":"10 mA","Between The Channels And Backplane Bus":"Yes","Current, relative to input range, (+/-)":"0.4 %","Between the channels and load voltage L+":"No","from load voltage L+ (without load), max.":"80 mA","Installation altitude above sea level, max.":"5 000 m","Ambient air temperature-barometric pressure-altitude":"Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)","Resolution with overrange (bit including sign), max.":"13 bit; 4 to 20 mA: 13 bit","Interference voltage suppression for interference frequency f1 in Hz":"50 / 60 Hz","Permissible Input Current For Current Input (Destruction Limit), Max.":"40 mA","Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04":"Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$227.33","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e51396e92b3a763c69906944371f4bb2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=387240&mlfb=6AG1134-4GB01-2AB0"},"ai":{"faq":[{"question":"What is the operating temperature range?","answer":"Rated for -25°C to 60°C ambient, covering most industrial indoor and unheated cabinet environments."},{"question":"What compliance documentation is available?","answer":"CE and UL approvals are listed. Check with your compliance team for RoHS/REACH status; the evidence does not confirm those marks."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1134-4GB01-2AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1134-4GB01-2AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}