{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1134-6GF00-7AA1","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1134-6GF00-7AA1","canonicalUrl":"https://aoctrl.com/siemens/6AG1134-6GF00-7AA1","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1134-6GF00-7AA1","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIPLUS S7-1500 analog input module, 6AG1134-6GF00-7AA1, 8 single-ended inputs, 24 V DC, 15 mm width.","salesMarkdown":"## What this module is, and what it needs The 6AG1134-6GF00-7AA1: SIPLUS variant of the standard S7-1500 AI module — 8 single-ended analog inputs, 24 V DC supply, 15 mm wide. It sits on a BU type A0 or A1 BaseUnit. Covers 4-20 mA and 0-20 mA ranges, with wire-break detection enabled on the 4-20 mA setting. No oversampling or isochronous mode — this is a standard-resolution scan module. Diagnostics include group error, diagnostic alarm, and overflow/underflow indication. Channel status shown per-channel green LED; module diagnostics via a DIAG LED. Power draw is 0.7 W typical without encoder supply, and the max total output current for all channels is 0.7 A. The module can supply sensors up to that limit. ## Field integration notes Fits alongside other S7-1500 slices on a DIN rail. The 15 mm width saves panel space — a full 8-channel analog block in a slim package. Shielded cable length max 200 m per channel. Termination is through the BaseUnit (BU type A0 or A1); wiring is plug-in, no screw terminals on the module itself. I&M data (I&M0 to I&M3) is supported for asset tracking and maintenance documentation. Firmware update possible via the engineering station. No calibration in RUN — it's a fixed-range module with 4 levels of smoothing (none, 4, 8, 16 times).","metaTitle":"Siemens 6AG1134-6GF00-7AA1 SIPLUS AI 8xI, 15mm, 24V","metaDescription":"SIPLUS analog input module, 8 single-ended channels, 4-20 mA with wire-break diagnostics, 24 V DC supply, active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"MSI":"No","24 V":"Yes","Depth":"58 mm","Width":"15 mm","title":"6AG1134-6GF00-7AA1","Height":"73 mm","I&M data":"Yes; I&M0 to I&M3","0 to 20 mA":"Yes","Wire-break":"Yes; at 4 to 20 mA","Group error":"Yes","description":"SIPLUS ET 200SP AI 8xI 2-/4-wire BA based on 6ES7134-6GF00-0AA1 with conformal coating, -40…+70 °C, analog input module, suitable for BU type A0, A1, color code CC01, module diagnostics, 16 bit","Oversampling":"No","4 mA to 20 mA":"Yes","Short-circuit":"Yes; Sensor supply to M; module by module","Shielded, Max.":"200 m","Parameterizable":"Yes","Weight, approx.":"31 g","lifecycle_stage":"current","-20 mA to +20 mA":"Yes","Diagnostic alarm":"Yes","Isochronous mode":"No","Power loss, typ.":"0.7 W; Without encoder supply voltage","Rated value (DC)":"24 V","usable BaseUnits":"BU type A0, A1","Limit value alarm":"No","FW update possible":"Yes","Overflow/underflow":"Yes","Between The Channels":"No","Diagnostics function":"Yes","Output current, max.":"0.7 A; total current of all encoders/channels","Isolation tested with":"707 V DC (type test)","Channel status display":"Yes; green LED","For Module Diagnostics":"Yes; green/red DIAG LED","For Channel Diagnostics":"No","For Voltage Measurement":"No","For current measurement":"8","Number of analog inputs":"8; Single-ended","Measuring range scalable":"No","Short-circuit protection":"Yes","Current consumption, max.":"25 mA; without sensor supply","Number of smoothing levels":"4; None; 4/8/16 times","Calibration possible in RUN":"No","Reverse polarity protection":"Yes","Conversion time (per channel)":"180 / 60 / 50 / 0.625 (67.5 / 22.5 / 18.75) ms","Horizontal Installation, Max.":"70 °C; = Tmax","Horizontal Installation, Min.":"-40 °C; = Tmin (incl. condensation/frost)","Input resistance (0 to 20 mA)":"100 Ω; 15 bit","Monitoring the supply voltage":"Yes","Address space per module, max.":"16 byte","Cycle time (all channels), min.":"1 ms; per channel","Input resistance (4 mA to 20 mA)":"100 Ω; 15 bit","Integration time, parameterizable":"Yes","Burden of 2-wire transmitter, max.":"650 Ω","Crosstalk between the inputs, min.":"50 dB","Reparameterization possible in RUN":"Yes","Input resistance (-20 mA to +20 mA)":"100 Ω; 16 bit incl. sign","permissible range, lower limit (DC)":"19.2 V","permissible range, upper limit (DC)":"28.8 V","Between The Channels And Backplane Bus":"Yes","Current, relative to input range, (+/-)":"0.3 %","Monitoring of the supply voltage (PWR-LED)":"Yes; green LED","Installation altitude above sea level, max.":"5 000 m","For Current Measurement As 2-Wire Transducer":"Yes","For Current Measurement As 4-Wire Transducer":"Yes","Protection against fouling acc. to EN 60664-3":"Yes; Type 1 protection","Linearity error (relative to input range), (+/-)":"0.01 %","Temperature error (relative to input range), (+/-)":"0.005 %/K","Ambient air temperature-barometric pressure-altitude":"Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)","Resolution with overrange (bit including sign), max.":"16 bit","Color code for module-specific color identification plate":"CC01","Resistant to commercially available coolants and lubricants":"Yes; Incl. diesel and oil droplets in the air","Between The Channels And The Power Supply Of The Electronics":"No","Interference voltage suppression for interference frequency f1 in Hz":"16.67 / 50 / 60 / 4 800 (16.67 / 50 / 60)","Permissible Input Current For Current Input (Destruction Limit), Max.":"50 mA","Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)":"0.05 %","Series mode interference (peak value of interference < rated value of input range), min.":"70 dB; With conversion time 67.5 / 22.5 / 18.75 ms: 40 dB","Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04":"Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)","Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A":"Yes; Conformal coating, Class A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$307.34","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e51396e92b3a763c69906944371f4bb2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1342894&mlfb=6AG1134-6GF00-7AA1"},"ai":{"faq":[{"question":"What does MSI 'No' mean on this module?","answer":"MSI is not listed for this part; it is not a market-specific identifier variant."},{"question":"What supply voltage does the module need?","answer":"It requires a 24 V DC supply, rated value 24 V."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1134-6GF00-7AA1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1134-6GF00-7AA1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}