{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1134-6HB00-2CA1","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1134-6HB00-2CA1","canonicalUrl":"https://aoctrl.com/siemens/6AG1134-6HB00-2CA1","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1134-6HB00-2CA1","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIMATIC ET200SP, 6AG1134-6HB00-2CA1, analog input module, 4 AI, 15/16 bit, diagnostics, 24 V DC.","salesMarkdown":"## Analog input module for ET 200SP – 4 channels, multi-range, diagnostics The 6AG1134-6HB00-2CA1: This 4-channel analog input module fits SIMATIC ET 200SP base units type A0 or A1. Each channel can be parameterized for voltage (0 to 10 V, 1 to 5 V, ±10 V, ±5 V) or current (0 to 20 mA, 4 to 20 mA, ±20 mA) measurement. Unipolar ranges resolve to 15 bit; bipolar ranges use 16 bit including sign. Diagnostics include wire-break detection on the 4 to 20 mA range, short-circuit detection for 1 to 5 V or current ranges, two upper and two lower limit value alarms per channel, and overflow/underflow flags. A group error LED plus per-channel red LED speed fault isolation. The resolution difference between unipolar (15 bit) and bipolar (16 bit including sign) is the same effective steps – the extra bit is the sign. Both deliver fine granularity for process signals, but the bipolar ranges give ±10 V or ±5 V with zero-center. Dimensions 15 x 73 x 58 mm; requires base unit type A0 or A1; supply 24 V DC, power loss 0.95 W; shielded cable max 1 000 m (current) or 200 m (voltage); output current 100 mA continuous, 150 mA for < 10 s.","metaTitle":"Siemens 6AG1134-6HB00-2CA1 Analog Input, 15/16 bit, 24V","metaDescription":"Siemens 6AG1134-6HB00-2CA1 current-production analog input module for ET 200SP. 4 channels, 0-10V/0-20mA, 15/16-bit resolution, diagnostics, wire-break detection. I&M data, firmwar","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"MSI":"No","24 V":"Yes","Depth":"58 mm","Width":"15 mm","title":"6AG1134-6HB00-2CA1","Height":"73 mm","I&M data":"Yes; I&M0 to I&M3","0 to +10 V":"Yes; 15 bit","0 to 20 mA":"Yes; 15 bit","1 V to 5 V":"Yes; 15 bit","Wire-break":"Yes; Measuring range 4 to 20 mA only","Group error":"Yes","description":"SIPLUS ET 200SP AI 2xU/I 2/4-W HF based on 6ES7134-6HB00-0CA1 with conformal coating, -40…+60 °C, analog input module, suitable for BU type A0, A1, color code CC05, channel diagnostics, 16-bit, +/-0.1%","-5 V to +5 V":"Yes; 16 bit incl. sign","Jitter, max.":"5 µs","Oversampling":"No","4 mA to 20 mA":"Yes; 15 bit","Short-circuit":"Yes; For 1 to 5 V or for current measuring ranges short-circuit in encoder supply","-10 V to +10 V":"Yes; 16 bit incl. sign","Shielded, Max.":"1 000 m; 200 m for voltage measurement","Parameterizable":"Yes","Weight, approx.":"32 g","lifecycle_stage":"current","-20 mA to +20 mA":"Yes; 16 bit incl. sign","Diagnostic alarm":"Yes","Firmware version":"V1.0","Isochronous mode":"Yes","Power loss, typ.":"0.95 W; without sensor supply","Rated value (DC)":"24 V","usable BaseUnits":"BU type A0, A1","Limit value alarm":"Yes; two upper and two lower limit values in each case","FW update possible":"Yes","Overflow/underflow":"Yes","Between The Channels":"Yes","Diagnostics function":"Yes","Output current, max.":"100 mA; max. 150 mA for a duration of < 10 s (four-wire)","Isolation tested with":"707 V DC (type test)","Measurement principle":"Sigma Delta","Channel status display":"Yes; green LED","For Module Diagnostics":"Yes; green/red DIAG LED","For Channel Diagnostics":"Yes; red LED","For Voltage Measurement":"Yes","Number of analog inputs":"2; Differential inputs","Measuring range scalable":"No","Short-circuit protection":"Yes","between the inputs (UCM)":"75 V DC/60 V AC","Common mode voltage, max.":"35 V","Between Different Circuits":"75 V DC/60 V AC (base isolation)","Bus cycle time (TDP), min.":"1 ms","Number of smoothing levels":"6; none; 2-/4-/8-/16-/32-fold","Calibration possible in RUN":"Yes","Reverse polarity protection":"Yes","Input resistance (0 to 10 V)":"75 kΩ","Horizontal Installation, Max.":"60 °C; = Tmax","Horizontal Installation, Min.":"-40 °C; = Tmin (incl. condensation/frost)","Input resistance (0 to 20 mA)":"130 Ω","Input resistance (1 V to 5 V)":"75 kΩ","Monitoring the supply voltage":"Yes","Address space per module, max.":"4 byte; + 1 byte for QI information","Common mode interference, min.":"90 dB","Input resistance (-5 V to +5 V)":"75 kΩ","Input resistance (4 mA to 20 mA)":"130 Ω","Current consumption (rated value)":"39 mA; without sensor supply","Input resistance (-10 V to +10 V)":"75 kΩ","Integration time, parameterizable":"Yes","Burden of 2-wire transmitter, max.":"650 Ω","Crosstalk between the inputs, min.":"-50 dB","Reparameterization possible in RUN":"Yes","Input resistance (-20 mA to +20 mA)":"130 Ω","permissible range, lower limit (DC)":"19.2 V","permissible range, upper limit (DC)":"28.8 V","Between The Channels And Backplane Bus":"Yes","Current, relative to input range, (+/-)":"0.05 %; 0.1 % at SFU 4.8 kHz","Voltage, relative to input range, (+/-)":"0.05 %; 0.1 % at SFU 4.8 kHz","Filtering and processing time (TCI), min.":"800 µs","Monitoring of the supply voltage (PWR-LED)":"Yes; green PWR LED","Installation altitude above sea level, max.":"5 000 m","For Current Measurement As 2-Wire Transducer":"Yes","For Current Measurement As 4-Wire Transducer":"Yes","Protection against fouling acc. to EN 60664-3":"Yes; Type 1 protection","Linearity error (relative to input range), (+/-)":"0.02 %","Temperature error (relative to input range), (+/-)":"0.005 %/K","Ambient air temperature-barometric pressure-altitude":"Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)","Resolution with overrange (bit including sign), max.":"16 bit","Color code for module-specific color identification plate":"CC03","Basic execution time of the module (all channels released)":"1 ms","Resistant to commercially available coolants and lubricants":"Yes; Incl. diesel and oil droplets in the air","Between The Channels And The Power Supply Of The Electronics":"Yes","Interference voltage suppression for interference frequency f1 in Hz":"16.6 / 50 / 60 / 300 / 600 / 1 200 / 2 400 / 4 800","Permissible Input Current For Current Input (Destruction Limit), Max.":"50 mA","Permissible Input Voltage For Voltage Input (Destruction Limit), Max.":"30 V","Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)":"0.01 %","Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04":"Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)","Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A":"Yes; Conformal coating, Class A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e51396e92b3a763c69906944371f4bb2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=689857&mlfb=6AG1134-6HB00-2CA1"},"ai":{"faq":[{"question":"What is the MSI setting for this module?","answer":"The MSI (multilingual support identifier) is set to No."},{"question":"Does this module support 24 V DC supply?","answer":"Yes, the rated supply voltage is 24 V DC."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1134-6HB00-2CA1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1134-6HB00-2CA1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}