{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1134-6HD01-2BA1","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1134-6HD01-2BA1","canonicalUrl":"https://aoctrl.com/siemens/6AG1134-6HD01-2BA1","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1134-6HD01-2BA1","rawCanonicalId":null},"summary":{"shortDescription":"Siemens S7-1200 SIPLUS analog input module, 6AG1134-6HD01-2BA1, 4 differential inputs, 15/16 bit, voltage and current ranges, I&M0-3, diagnostic functions.","salesMarkdown":"## Four differential channels, clean signal path The 6AG1134-6HD01-2BA1 is a 4-channel differential analog input module for the S7-1200 system, designed for industrial signal acquisition where noise rejection is a priority. Each channel can be configured for voltage ranges (0 to +10 V, 1 V to 5 V, -5 V to +5 V, -10 V to +10 V) or current ranges (0 to 20 mA, 4 to 20 mA), with 15-bit resolution for unipolar and 16-bit including sign for bipolar ranges. Differential inputs inherently reject common-mode noise from long cable runs, and the integrating Sigma-Delta measurement principle naturally filters line-frequency interference. Diagnostic alarms for wire-break (active on 4–20 mA) and short-circuit protection (for 1–5 V or 2-wire mode) are built in, and a group error LED provides quick visual status. I&M data (I&M0 through I&M3) is supported for device identification in the engineering tool. ## Signal integrity and cabling Isolation between channels and ground is type-tested at 707 V DC, which helps prevent ground loops in mixed-power panels. Maximum shielded cable length is 1 000 m for current signals and 200 m for voltage signals. The module mounts on BU type A0 or A1 base units, occupying a 15 mm slot in the rack. ## Sourcing reality Expect a commissioning note: power draw is 0.85 W typical without encoder supply, and the rated supply is 24 V DC.","metaTitle":"Siemens 6AG1134-6HD01-2BA1 Analog Input Module, 4 AI, 16-bit","metaDescription":"Active production. 4 differential analog inputs, 15/16 bit, diagnostic alarms, short-circuit protection, isolation 707 V DC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"MSI":"No","24 V":"Yes","Depth":"58 mm","Width":"15 mm","title":"6AG1134-6HD01-2BA1","Height":"73 mm","I&M data":"Yes; I&M0 to I&M3","0 to +10 V":"Yes; 15 bit","0 to 20 mA":"Yes; 15 bit","1 V to 5 V":"Yes; 15 bit","Wire-break":"Yes; at 4 to 20 mA","Group error":"Yes","description":"***spare part*** SIPLUS ET 200SP AI 4xU/I 2-w ST based on 6ES7134-6HD01-0BA1 with conformal coating, -40…+60 °C, start up -25 °C, analog input module, suitable for BU type A0, A1, color code CC03, module diagnostics, 16 bit, +/-0.3%","-5 V to +5 V":"Yes; 16 bit incl. sign","Oversampling":"No","4 mA to 20 mA":"Yes; 15 bit","Short-circuit":"Yes; with 1 to 5 V or 2-wire mode: Short-circuit of the encoder supply to ground or of an input to the encoder supply","-10 V to +10 V":"Yes; 16 bit incl. sign","Shielded, Max.":"1 000 m; 200 m for voltage measurement","Parameterizable":"Yes","Weight, approx.":"31 g","lifecycle_stage":"current","Diagnostic alarm":"Yes","Isochronous mode":"No","Power loss, typ.":"0.85 W; Without encoder supply voltage","Rated value (DC)":"24 V","usable BaseUnits":"BU type A0, A1","2-Wire Connection":"BU type A0, A1","Limit value alarm":"No","Overflow/underflow":"Yes","Between The Channels":"Yes; channel group-specific between 2-wire current input group and voltage input group","Diagnostics function":"Yes","Output current, max.":"20 mA; max. 50 mA per channel for a duration < 10 s","Isolation tested with":"707 V DC (type test)","Measurement principle":"integrating (Sigma-Delta)","Channel status display":"Yes; green LED","For Module Diagnostics":"Yes; green/red LED","For Channel Diagnostics":"No","For Voltage Measurement":"Yes","Number of analog inputs":"4; Differential inputs","Measuring range scalable":"No","Short-circuit protection":"Yes","between the inputs (UCM)":"10 V DC","Common mode voltage, max.":"10 V","Current consumption, max.":"37 mA; without sensor supply","Mechanical coding element":"Yes","Number of smoothing levels":"4; None; 4/8/16 times","Calibration possible in RUN":"No","Reverse polarity protection":"Yes","Vertical Installation, Max.":"50 °C; = Tmax","Vertical Installation, Min.":"-40 °C; = Tmin; Startup @ -25 °C","Input resistance (0 to 10 V)":"120 kΩ","Conversion time (per channel)":"180 / 60 / 50 ms","Horizontal Installation, Max.":"60 °C; = Tmax","Horizontal Installation, Min.":"-40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C","Input resistance (0 to 20 mA)":"100 Ω; + approx. 0.7 V diode forward voltage","Input resistance (1 V to 5 V)":"120 kΩ","Monitoring the supply voltage":"Yes","Address space per module, max.":"8 byte; + 1 byte for QI information","Common mode interference, min.":"90 dB","Cycle time (all channels), min.":"Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels)","Input resistance (-5 V to +5 V)":"120 kΩ","Input resistance (4 mA to 20 mA)":"100 Ω; + approx. 0.7 V diode forward voltage","Input resistance (-10 V to +10 V)":"120 kΩ","Integration time, parameterizable":"Yes","Burden of 2-wire transmitter, max.":"650 Ω","Crosstalk between the inputs, min.":"50 dB","Reparameterization possible in RUN":"Yes","permissible range, lower limit (DC)":"19.2 V","permissible range, upper limit (DC)":"28.8 V","Between The Channels And Backplane Bus":"Yes","Current, relative to input range, (+/-)":"0.3 %","Voltage, relative to input range, (+/-)":"0.3 %","Monitoring of the supply voltage (PWR-LED)":"Yes; green LED","Installation altitude above sea level, max.":"5 000 m","For Current Measurement As 2-Wire Transducer":"Yes","For Current Measurement As 4-Wire Transducer":"No","Suitable for applications according to CQI-9":"Yes","Protection against fouling acc. to EN 60664-3":"Yes; Type 1 protection","Suitable for applications according to AMS 2750":"Yes; Declaration of Conformity, see online support entry 109757262","Linearity error (relative to input range), (+/-)":"0.01 %","Temperature error (relative to input range), (+/-)":"0.005 %/K","Ambient air temperature-barometric pressure-altitude":"Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)","Resolution with overrange (bit including sign), max.":"16 bit","Color code for module-specific color identification plate":"CC03","Resistant to commercially available coolants and lubricants":"Yes; Incl. diesel and oil droplets in the air","Between The Channels And The Power Supply Of The Electronics":"Yes; only for voltage inputs","Interference voltage suppression for interference frequency f1 in Hz":"16.6 / 50 / 60 Hz","Permissible Input Current For Current Input (Destruction Limit), Max.":"50 mA","Permissible Input Voltage For Voltage Input (Destruction Limit), Max.":"30 V","Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)":"0.05 %","Series mode interference (peak value of interference < rated value of input range), min.":"70 dB","Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A":"Yes; Conformal coating, Class A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e51396e92b3a763c69906944371f4bb2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1133463&mlfb=6AG1134-6HD01-2BA1"},"ai":{"faq":[{"question":"Does the module have wire-break detection?","answer":"Yes, wire-break detection is active when the input is configured for the 4 to 20 mA range."},{"question":"What is the isolation rating between channels and ground?","answer":"Isolation is tested at 707 V DC (type test), providing common-mode rejection in noisy installations."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1134-6HD01-2BA1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1134-6HD01-2BA1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}