{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1134-6JD00-2CA1","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1134-6JD00-2CA1","canonicalUrl":"https://aoctrl.com/siemens/6AG1134-6JD00-2CA1","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1134-6JD00-2CA1","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIPLUS ET 200SP, analog input module, 2 AI RTD/TC, 6AG1134-6JD00-2CA1, 15 mm width, 30 g.","salesMarkdown":"## Integration notes A SIPLUS variant of the ET 200SP analog input module, the 6AG1134-6JD00-2CA1 holds two RTD or thermocouple channels on the grid for harsh environments, provided that the cable run stays within the shielded maximum—200 m for resistance sensors, 50 m for thermocouples—and that the resolution is fixed at 15 or 16 bit depending on the sensor type. The body occupies 15 mm of DIN rail width (73 mm high, 58 mm deep), so it fits a high-density I/O rack without crowding the next slice. No oversampling on this slice—so if the application demands sub-cycle capture for start-up transients, another module in the cabinet handles that. Channel-wise wire-break detection and a group-error signal are provided, easing fault isolation during panel walkdowns. ## Sourcing posture Our desk stocks traceable batches for line-down BOM fills and scheduled panel builds; lead time and compliance declarations (RoHS, REACH) are supplied with each shipment.","metaTitle":"Siemens 6AG1134-6JD00-2CA1 SIPLUS AI 2xRTD/TC","metaDescription":"SIPLUS ET 200SP analog input module, 2 channels for RTD or thermocouple sensors. Supports Pt100, Pt1000, Ni100, types K, J, T, etc, 15/16 bit. Width 15 mm. Sourced to RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"MSI":"No","PTC":"Yes; 15 bit","Cu 10":"Yes; 16 bit incl. sign","Depth":"58 mm","Width":"15 mm","title":"6AG1134-6JD00-2CA1","Height":"73 mm","Ni 100":"Yes; 16 bit incl. sign","Ni 120":"Yes; 16 bit incl. sign","Ni 200":"Yes; 16 bit incl. sign","Ni 500":"Yes; 16 bit incl. sign","Pt 100":"Yes; 16 bit incl. sign","Pt 200":"Yes; 16 bit incl. sign","Pt 500":"Yes; 16 bit incl. sign","Type B":"Yes; 16 bit incl. sign","Type C":"Yes; 16 bit incl. sign","Type E":"Yes; 16 bit incl. sign","Type J":"Yes; 16 bit incl. sign","Type K":"Yes; 16 bit incl. sign","Type L":"Yes; 16 bit incl. sign","Type N":"Yes; 16 bit incl. sign","Type R":"Yes; 16 bit incl. sign","Type S":"Yes; 16 bit incl. sign","Type T":"Yes; 16 bit incl. sign","Type U":"Yes; 16 bit incl. sign","Ni 1000":"Yes; 16 bit incl. sign","Pt 1000":"Yes; 16 bit incl. sign","I&M data":"Yes; I&M0 to I&M3","LG-Ni 1000":"Yes; 16 bit incl. sign","Wire-break":"Yes; channel by channel","Group error":"Yes","description":"SIPLUS ET 200SP AI 4xRTD/TC high feature based on 6ES7134-6JD00-0CA1 with conformal coating, -40…+60 °C, analog input module, suitable for BU type A0, A1, color code CC00, channel diagnostics, 16-bit, +/-0.1%, 2/3/4-wire","-1 V to +1 V":"Yes; 16 bit incl. sign","Oversampling":"No","0 To 150 Ohms":"Yes; 15 bit","0 To 300 Ohms":"Yes; 15 bit","0 To 600 Ohms":"Yes; 15 bit","0 To 3000 Ohms":"Yes; 15 bit","0 To 6000 Ohms":"Yes; 15 bit","Shielded, Max.":"200 m; 50 m with thermocouples","Parameterizable":"Yes","Weight, approx.":"30 g","lifecycle_stage":"current","-50 mV to +50 mV":"Yes; 16 bit incl. sign","-80 mV to +80 mV":"Yes; 16 bit incl. sign","Diagnostic alarm":"Yes","Isochronous mode":"No","Power loss, typ.":"0.75 W","Rated value (DC)":"24 V","usable BaseUnits":"BU type A0, A1","Limit value alarm":"Yes; two upper and two lower limit values in each case","-250 mV to +250 mV":"Yes; 16 bit incl. sign","Overflow/underflow":"Yes; channel by channel","Between The Channels":"No","Diagnostics function":"Yes","Isolation tested with":"707 V DC (type test)","Measurement principle":"integrating (Sigma-Delta)","Channel status display":"Yes; green LED","For Module Diagnostics":"Yes; green/red DIAG LED","Input resistance (PTC)":"1 MΩ","For Channel Diagnostics":"Yes; red LED","For Voltage Measurement":"Yes","For voltage measurement":"4","Number of analog inputs":"4","Type TXK/TXK(L) to GOST":"Yes; 16 bit incl. sign","between the inputs (UCM)":"10 V DC","Common mode voltage, max.":"10 V","Current consumption, max.":"35 mA","Input resistance (Ni 100)":"1 MΩ","Input resistance (Ni 120)":"1 MΩ","Input resistance (Ni 200)":"1 MΩ","Input resistance (Ni 500)":"1 MΩ","Input resistance (Pt 100)":"1 MΩ","Input resistance (Pt 200)":"1 MΩ","Input resistance (Pt 500)":"1 MΩ","Input resistance (Type B)":"1 MΩ","Input resistance (Type C)":"1 MΩ","Input resistance (Type E)":"1 MΩ","Input resistance (Type K)":"1 MΩ","Input resistance (Type L)":"1 MΩ","Input resistance (Type N)":"1 MΩ","Input resistance (Type R)":"1 MΩ","Input resistance (Type S)":"1 MΩ","Input resistance (Type T)":"1 MΩ","Input resistance (Type U)":"1 MΩ","Input resistance (type J)":"1 MΩ","Internal Comparison Point":"Yes; with BaseUnit type A1","Input resistance (Ni 1000)":"1 MΩ","Input resistance (Pt 1000)":"1 MΩ","Number of smoothing levels":"4; None; 4/8/16 times","Calibration possible in RUN":"Yes","Fixed Reference Temperature":"Yes","Vertical Installation, Max.":"50 °C; = Tmax","Vertical Installation, Min.":"-40 °C; = Tmin (incl. condensation/frost)","For thermocouple measurement":"4","Conversion time (per channel)":"180 / 60 / 50 ms","Horizontal Installation, Max.":"60 °C; = Tmax; +70 °C with configured empty slots to the left and right of the module","Horizontal Installation, Min.":"-40 °C; = Tmin (incl. condensation/frost)","Input resistance (LG-Ni 1000)":"1 MΩ","Monitoring the supply voltage":"Yes","Address space per module, max.":"8 byte; + 1 byte for QI information","Common mode interference, min.":"90 dB","Reference channel of the group":"Yes","Cycle time (all channels), min.":"Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels); for line compensation in case of a three-wire connection, an additional cycle is necessary","Input resistance (-1 V to +1 V)":"1 MΩ","Reference channel of the module":"Yes","Input resistance (0 to 150 ohms)":"1 MΩ","Input resistance (0 to 300 ohms)":"1 MΩ","Input resistance (0 to 600 ohms)":"1 MΩ","Input resistance (0 to 3000 ohms)":"1 MΩ","Input resistance (0 to 6000 ohms)":"1 MΩ","Integration time, parameterizable":"Yes","Crosstalk between the inputs, min.":"50 dB","Number of reference channel groups":"4; Group 0 to 3","Reparameterization possible in RUN":"Yes","Input resistance (-50 mV to +50 mV)":"1 MΩ","Input resistance (-80 mV to +80 mV)":"1 MΩ","permissible range, lower limit (DC)":"19.2 V","permissible range, upper limit (DC)":"28.8 V","Input resistance (-250 mV to +250 mV)":"1 MΩ","Additional Power Line Wire-Break Check":"2 ms; for 3/4 wire transducer (resistance thermometer and resistor)","Between The Channels And Backplane Bus":"Yes","Voltage, relative to input range, (+/-)":"0.05 %","Input resistance (Type TXK/TXK(L) to GOST)":"1 MΩ","Monitoring of the supply voltage (PWR-LED)":"Yes; green PWR LED","Resistance, relative to input range, (+/-)":"0.05 %","Installation altitude above sea level, max.":"5 000 m","Protection against fouling acc. to EN 60664-3":"Yes; Type 1 protection","Additional Processing Time For Wire-Break Check":"2 ms; In the ranges resistance thermometers, resistors and thermocouples","Linearity error (relative to input range), (+/-)":"0.01 %","For resistance/resistance thermometer measurement":"4","Temperature error (relative to input range), (+/-)":"0.005 %/K","For Resistance Measurement With Two-Wire Connection":"Yes","Ambient air temperature-barometric pressure-altitude":"Tmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)","For Resistance Measurement With Four-Wire Connection":"Yes","Resolution with overrange (bit including sign), max.":"16 bit","For Resistance Measurement With Three-Wire Connection":"Yes","Technical unit for temperature measurement adjustable":"Yes; °C/°F/K","Color code for module-specific color identification plate":"CC00","Resistant to commercially available coolants and lubricants":"Yes; Incl. diesel and oil droplets in the air","Between The Channels And The Power Supply Of The Electronics":"Yes","Constant measurement current for resistance-type transmitter, typ.":"0.7 mA; 1.7 mA for Cu10 sensors","Interference voltage suppression for interference frequency f1 in Hz":"16.6 / 50 / 60 Hz","Permissible Input Voltage For Voltage Input (Destruction Limit), Max.":"30 V","Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)":"0.05 %","Series mode interference (peak value of interference < rated value of input range), min.":"70 dB","Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04":"Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)","Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A":"Yes; Conformal coating, Class A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$278.13","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e51396e92b3a763c69906944371f4bb2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=479528&mlfb=6AG1134-6JD00-2CA1"},"ai":{"faq":[{"question":"What temperature sensor types does the 6AG1134-6JD00-2CA1 support?","answer":"It supports Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, LG-Ni1000, Cu10 RTDs and thermocouple types B, C, E, J, K, L, N, R, S, T, U, each with 16-bit resolution including sign, except Pt100 and PTC at 15-bit."},{"question":"What are the physical dimensions of the module?","answer":"The module measures 73 mm high, 15 mm wide, and 58 mm deep, weighing approximately 30 g."},{"question":"What is the maximum cable length allowed?","answer":"Shielded cable can run up to 200 m for resistance sensors (RTDs, PTCs, resistance ranges) and up to 50 m when using thermocouples."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1134-6JD00-2CA1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1134-6JD00-2CA1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}