{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1134-6JF00-2CA1","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1134-6JF00-2CA1","canonicalUrl":"https://aoctrl.com/siemens/6AG1134-6JF00-2CA1","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1134-6JF00-2CA1","rawCanonicalId":null},"summary":{"shortDescription":"Siemens ET 200SP, 6AG1134-6JF00-2CA1, analog input module, Pt100/TC, 16 bit incl. sign, 15 mm width.","salesMarkdown":"This is a current-production Siemens ET 200SP analog input module — order code 6AG1134-6JF00-2CA1 — sized for RTD and thermocouple loops. It reads Pt100, Ni100, Pt1000, and most common TC types (K, J, T, E, N, R, S, B, C, L, U) with 16 bit resolution including sign, plus PTC with 15 bit. That covers the sensor range you’ll find in process and building HVAC panels. The 15 mm width per module packs eight inputs onto a standard ET 200SP rail — useful when you’re stuffing density into a retrofitted gland plate. Wire-break detection works channel by channel, so you can flag a field cut without guessing which loop dropped. The group error output gives the CPU a single shot if any channel faults. Cable run matters on site: shielded max 200 m for resistance sensors, but only 50 m for thermocouples. That TC limit means you’ll mount the module closer to the field junction box than you might expect if you’re used to RTD runs. No oversampling onboard, so don’t count on sub-cycle acquisition — this is for stable process values, not fast dynamics.","metaTitle":"Siemens 6AG1134-6JF00-2CA1 AI Pt100/TC, 15 bit","metaDescription":"Current-production Siemens ET 200SP AI module. Handles Pt100, Ni100, TC types, 16 bit incl. sign. Wire-break detection per channel. 15 mm wide. 58 mm deep. Order to RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"MSI":"No","PTC":"Yes; 15 bit","Depth":"58 mm","Width":"15 mm","title":"6AG1134-6JF00-2CA1","Height":"73 mm","Ni 100":"Yes; 16 bit incl. sign","Ni 120":"Yes; 16 bit incl. sign","Ni 200":"Yes; 16 bit incl. sign","Ni 500":"Yes; 16 bit incl. sign","Pt 100":"Yes; 16 bit incl. sign","Pt 200":"Yes; 16 bit incl. sign","Pt 500":"Yes; 16 bit incl. sign","Type B":"Yes; 16 bit incl. sign","Type C":"Yes; 16 bit incl. sign","Type E":"Yes; 16 bit incl. sign","Type J":"Yes; 16 bit incl. sign","Type K":"Yes; 16 bit incl. sign","Type L":"Yes; 16 bit incl. sign","Type N":"Yes; 16 bit incl. sign","Type R":"Yes; 16 bit incl. sign","Type S":"Yes; 16 bit incl. sign","Type T":"Yes; 16 bit incl. sign","Type U":"Yes; 16 bit incl. sign","Ni 1000":"Yes; 16 bit incl. sign","Pt 1000":"Yes; 16 bit incl. sign","I&M data":"Yes; I&M0 to I&M3","LG-Ni 1000":"Yes; 16 bit incl. sign","Wire-break":"Yes; channel by channel","Group error":"Yes","description":"SIPLUS ET 200SP AI 8xRTD/TC 2-wire based on 6ES7134-6JF00-0CA1 with conformal coating, -40…+60 °C, analog input module, suitable for BU type A0, A1, color code CC00, channel diagnostics, 16-bit, +/-0.1%","-1 V to +1 V":"Yes; 16 bit incl. sign","Oversampling":"No","0 To 150 Ohms":"Yes; 15 bit","0 To 300 Ohms":"Yes; 15 bit","0 To 600 Ohms":"Yes; 15 bit","0 To 3000 Ohms":"Yes; 15 bit","0 To 6000 Ohms":"Yes; 15 bit","Shielded, Max.":"200 m; 50 m with thermocouples","Parameterizable":"Yes","Weight, approx.":"32 g","lifecycle_stage":"current","-50 mV to +50 mV":"Yes; 16 bit incl. sign","-80 mV to +80 mV":"Yes; 16 bit incl. sign","Diagnostic alarm":"Yes","Isochronous mode":"No","Power loss, typ.":"0.75 W","Rated value (DC)":"24 V","usable BaseUnits":"BU type A0, A1","Limit value alarm":"Yes; two upper and two lower limit values in each case","-250 mV to +250 mV":"Yes; 16 bit incl. sign","FW update possible":"Yes","Overflow/underflow":"Yes; channel by channel","Between The Channels":"No","Diagnostics function":"Yes","Isolation tested with":"707 V DC (type test)","Measurement principle":"integrating (Sigma-Delta)","Channel status display":"Yes; green LED","For Module Diagnostics":"Yes; green/red DIAG LED","Input resistance (PTC)":"1 MΩ","For Channel Diagnostics":"Yes; red LED","For Voltage Measurement":"Yes","Number of analog inputs":"8","Type TXK/TXK(L) to GOST":"Yes; 16 bit incl. sign","between the inputs (UCM)":"10 V DC","Common mode voltage, max.":"10 V","Current consumption, max.":"35 mA","Input resistance (Ni 100)":"1 MΩ","Input resistance (Ni 120)":"1 MΩ","Input resistance (Ni 200)":"1 MΩ","Input resistance (Ni 500)":"1 MΩ","Input resistance (Pt 100)":"1 MΩ","Input resistance (Pt 200)":"1 MΩ","Input resistance (Pt 500)":"1 MΩ","Input resistance (Type B)":"1 MΩ","Input resistance (Type C)":"1 MΩ","Input resistance (Type E)":"1 MΩ","Input resistance (Type K)":"1 MΩ","Input resistance (Type L)":"1 MΩ","Input resistance (Type N)":"1 MΩ","Input resistance (Type R)":"1 MΩ","Input resistance (Type S)":"1 MΩ","Input resistance (Type T)":"1 MΩ","Input resistance (Type U)":"1 MΩ","Input resistance (type J)":"1 MΩ","Internal Comparison Point":"Yes; with BaseUnit type A1","Between Different Circuits":"75 V DC/60 V AC (base isolation)","Input resistance (Ni 1000)":"1 MΩ","Input resistance (Pt 1000)":"1 MΩ","Number of smoothing levels":"4; None; 4/8/16 times","Calibration possible in RUN":"Yes","Fixed Reference Temperature":"Yes","Reverse polarity protection":"Yes","Vertical Installation, Max.":"50 °C; = Tmax","Vertical Installation, Min.":"-40 °C; = Tmin (incl. condensation/frost)","Conversion time (per channel)":"180 / 60 / 50 ms","Horizontal Installation, Max.":"60 °C; = Tmax; +70 °C with configured empty slots to the left and right of the module","Horizontal Installation, Min.":"-40 °C; = Tmin (incl. condensation/frost)","Input resistance (LG-Ni 1000)":"1 MΩ","Monitoring the supply voltage":"Yes","Address space per module, max.":"16 byte; + 1 byte for QI information","Common mode interference, min.":"90 dB","Reference channel of the group":"Yes","Cycle time (all channels), min.":"Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels)","Input resistance (-1 V to +1 V)":"1 MΩ","Reference channel of the module":"Yes","Input resistance (0 to 150 ohms)":"1 MΩ","Input resistance (0 to 300 ohms)":"1 MΩ","Input resistance (0 to 600 ohms)":"1 MΩ","Input resistance (0 to 3000 ohms)":"1 MΩ","Input resistance (0 to 6000 ohms)":"1 MΩ","Integration time, parameterizable":"Yes","Crosstalk between the inputs, min.":"-50 dB","Number of reference channel groups":"4; Group 0 to 3","Reparameterization possible in RUN":"Yes","Input resistance (-50 mV to +50 mV)":"1 MΩ","Input resistance (-80 mV to +80 mV)":"1 MΩ","permissible range, lower limit (DC)":"19.2 V","permissible range, upper limit (DC)":"28.8 V","Input resistance (-250 mV to +250 mV)":"1 MΩ","Between The Channels And Backplane Bus":"Yes","Voltage, relative to input range, (+/-)":"0.05 %","Input resistance (Type TXK/TXK(L) to GOST)":"1 MΩ","Monitoring of the supply voltage (PWR-LED)":"Yes; green PWR LED","Resistance, relative to input range, (+/-)":"0.05 %","Installation altitude above sea level, max.":"5 000 m","Protection against fouling acc. to EN 60664-3":"Yes; Type 1 protection","Additional Processing Time For Wire-Break Check":"2 ms; In the ranges resistance thermometers, resistors and thermocouples","Linearity error (relative to input range), (+/-)":"0.01 %; ±0.1 % for resistance thermometers and resistance","Temperature error (relative to input range), (+/-)":"0.0009 %/K; ±0.005 % / K at thermocouple","For Resistance Measurement With Two-Wire Connection":"Yes","Ambient air temperature-barometric pressure-altitude":"Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)","For Resistance Measurement With Four-Wire Connection":"No","Resolution with overrange (bit including sign), max.":"16 bit","For Resistance Measurement With Three-Wire Connection":"No","Technical unit for temperature measurement adjustable":"Yes; °C/°F/K","Color code for module-specific color identification plate":"CC00","Resistant to commercially available coolants and lubricants":"Yes; Incl. diesel and oil droplets in the air","Between The Channels And The Power Supply Of The Electronics":"Yes","Constant measurement current for resistance-type transmitter, typ.":"2 mA","Interference voltage suppression for interference frequency f1 in Hz":"16.6 / 50 / 60 Hz","Permissible Input Voltage For Voltage Input (Destruction Limit), Max.":"30 V","Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)":"0.05 %","Series mode interference (peak value of interference < rated value of input range), min.":"70 dB","Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04":"Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)","Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A":"Yes; Conformal coating, Class A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e51396e92b3a763c69906944371f4bb2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=629668&mlfb=6AG1134-6JF00-2CA1"},"ai":{"faq":[{"question":"What is the MSI status on this module?","answer":"The MSI (Master Slave Interface) is listed as No — this module does not support MSI communication."},{"question":"What is the PTC resolution?","answer":"PTC (positive temperature coefficient) sensors are supported with 15 bit resolution."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1134-6JF00-2CA1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1134-6JF00-2CA1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}