{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1134-6TD00-2CA1","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1134-6TD00-2CA1","canonicalUrl":"https://aoctrl.com/siemens/6AG1134-6TD00-2CA1","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1134-6TD00-2CA1","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIMATIC S7-1200 F analog input module, 4 channels differential, 4-20 mA, 15 bit + sign, diagnostics.","salesMarkdown":"## Module overview The Siemens 6AG1134-6TD00-2CA1 is a 4-channel analog input module for the S7-1200 F failsafe system, accepting 4-20 mA signals with 15-bit plus sign resolution across differential inputs. ## Diagnostics per channel Each channel can report wire-break (4 mA > wire-break threshold) and short-circuit (input or encoder supply to ground) individually. Diagnostic and limit-value alarms are generated, with a dedicated group error output. Module width is 15 mm, depth 58 mm, height 73 mm, and it mounts on a DIN rail via BU type A0 or A1 base units. Maximum cable length for shielded twisted pair is 800 m.","metaTitle":"Siemens 6AG1134-6TD00-2CA1 4AI 15bit","metaDescription":"Siemens 6AG1134-6TD00-2CA1 analog input module for S7-1200 F. 4 differential inputs, 4-20 mA, 15 bit + sign, wire-break/short-circuit diagnostics. Active lifecycle.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"MSI":"No","24 V":"Yes","Depth":"58 mm","Width":"15 mm","Height":"73 mm","I&M data":"Yes; I&M0 to I&M3","0 to 20 mA":"No","Wire-break":"Yes; channel by channel","Group error":"Yes","Oversampling":"No","4 mA to 20 mA":"Yes; 15 bit + sign","Short-circuit":"Yes; Channel-by-channel, short-circuit of the encoder supply to ground or of an input to the encoder supply","Shielded, Max.":"800 m","Parameterizable":"Yes","Weight, approx.":"31 g","lifecycle_stage":"current","-20 mA to +20 mA":"No","Diagnostic alarm":"Yes","Isochronous mode":"No","Power loss, typ.":"0.65 W; without sensor supply","Rated value (DC)":"24 V","usable BaseUnits":"BU type A0, A1","Limit value alarm":"Yes","FW update possible":"Yes","Overflow/underflow":"Yes; channel by channel","Between The Channels":"No","Diagnostics function":"Yes","Output current, max.":"20 mA; max. 50 mA per channel for a duration < 10 s","Isolation tested with":"707 V DC (type test)","Measurement principle":"integrating (Sigma-Delta)","Channel status display":"Yes; green LED","For Module Diagnostics":"Yes; green/red DIAG LED","For Channel Diagnostics":"Yes; red LED","For Voltage Measurement":"No","Number of analog inputs":"4; Differential inputs","Measuring range scalable":"No","Short-circuit protection":"Yes","Current consumption, max.":"25 mA; without sensor supply","Number of smoothing levels":"4; None; 4/8/16 times","Calibration possible in RUN":"No","Reverse polarity protection":"Yes","Vertical Installation, Max.":"50 °C; = Tmax","Vertical Installation, Min.":"-40 °C; = Tmin (incl. condensation/frost); start-up @ -30 °C","Horizontal Installation, Max.":"60 °C; = Tmax; +70 °C with configured empty slots to the left and right of the module","Horizontal Installation, Min.":"-40 °C; = Tmin (incl. condensation/frost); start-up @ -30 °C","Monitoring the supply voltage":"Yes","Address space per module, max.":"8 byte; + 1 byte for QI information","Input resistance (4 mA to 20 mA)":"280 Ω; + approx. 0.35 V diode forward voltage","Integration time, parameterizable":"Yes; channel by channel","Crosstalk between the inputs, min.":"60 dB","Reparameterization possible in RUN":"Yes","permissible range, lower limit (DC)":"19.2 V","permissible range, upper limit (DC)":"28.8 V","Between The Channels And Backplane Bus":"Yes","Current, relative to input range, (+/-)":"0.3 %","Address space per module with HART, max.":"28 byte; + 1 byte for QI information","Monitoring of the supply voltage (PWR-LED)":"Yes; green PWR LED","Installation altitude above sea level, max.":"5 000 m","For Current Measurement As 2-Wire Transducer":"Yes","Protection against fouling acc. to EN 60664-3":"Yes; Type 1 protection","Linearity error (relative to input range), (+/-)":"0.01 %","Temperature error (relative to input range), (+/-)":"0.005 %/K","Ambient air temperature-barometric pressure-altitude":"Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)","Resolution with overrange (bit including sign), max.":"16 bit","Color code for module-specific color identification plate":"CC03","Resistant to commercially available coolants and lubricants":"Yes; Incl. diesel and oil droplets in the air","Between The Channels And The Power Supply Of The Electronics":"No","Interference voltage suppression for interference frequency f1 in Hz":"10 / 50 / 60 Hz","Permissible Input Current For Current Input (Destruction Limit), Max.":"50 mA","Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)":"0.05 %","Series mode interference (peak value of interference < rated value of input range), min.":"60 dB","Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04":"Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)","Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A":"Yes; Conformal coating, Class A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$617.22","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e51396e92b3a763c69906944371f4bb2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=630255&mlfb=6AG1134-6TD00-2CA1","alternativesUrl":"https://aoctrl.com/api/mcp/products/6AG1134-6TD00-2CA1/alternatives.json"},"ai":{"faq":[{"question":"What diagnostics does this module offer?","answer":"It provides per-channel wire-break detection, short-circuit detection (input or encoder supply), diagnostic alarms, limit-value alarms, and a group error signal. Each channel has a red LED for channel diagnostics."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1134-6TD00-2CA1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1134-6TD00-2CA1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}