{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1135-4FB01-2AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1135-4FB01-2AB0","canonicalUrl":"https://aoctrl.com/siemens/6AG1135-4FB01-2AB0","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1135-4FB01-2AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens S7-1200 Series, 6AG1135-4FB01-2AB0 Analog Output Module, 2 analog outputs, voltage ranges 0–10 V, –10 to +10 V, 1–5 V, ambient temperature –25 to 60 °C.","salesMarkdown":"The 6AG1135-4FB01-2AB0 is a 2-channel analog output module for the S7-1200 system, delivering voltage outputs across three spans: 0–10 V, ±10 V, and 1–5 V. It runs on the backplane bus at 24 V DC drawn from the power module, with a separate load voltage L+ supply for the output drivers. Two-channel voltage output only — no 4–20 mA on this module. If your analog input expects a current loop, you need a different slice. The voltage outputs are available in two-wire (no line compensation) and four-wire connection, so the wiring topology is flexible but the signal type is fixed. The max altitude is 5 000 m above sea level, so high-altitude installations are fine without derating. Physical footprint: 15 mm wide, 81 mm tall, 52 mm deep. ## Commissioning notes Configure output behavior on CPU STOP via the module parameter set: choose between de-energized (outputs go to 0 V), substitute a fixed value, or keep the last value. For safety-critical loops, de-energized is the default. Short-circuit protection is built into the voltage outputs — the max short-circuit current is 25 mA. Diagnostics for short-circuit and group error can be enabled or disabled per channel. Cycle time over all channels peaks at 1.5 ms. The address space allocates 4 bytes per module; if you need more than 2 analog outputs, add another module.","metaTitle":"Siemens 6AG1135-4FB01-2AB0 Analog Output, 2 AO, -25..60°C","metaDescription":"Current-production S7-1200 analog output module. 2 voltage outputs (0-10 V, ±10 V, 1-5 V). Ambient -25 to 60 °C. Sourced to order against BOM line.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"Max.":"60 °C; = Tmax","Min.":"-25 °C; = Tmin","Depth":"52 mm","Width":"15 mm","title":"6AG1135-4FB01-2AB0","Height":"81 mm","Remark":"7 byte","1 V to 5 V":"Yes","Group error":"Yes","description":"SIPLUS ET 200S EM 2AQ U based on 6ES7135-4FB01-0AB0 with conformal coating, -25…+60 °C,","Current, max.":"50 mA; DC","Short-circuit":"Yes","-10 V to +10 V":"Yes","Shielded, Max.":"200 m","Weight, approx.":"40 g","lifecycle_stage":"current","Power loss, max.":"2 W","Rated value (DC)":"24 V; From power module","Group diagnostics":"Disable / enable","For Inductive Load":"0.5 ms","For Resistive Load":"0.1 ms","For Capacitive Load":"0.5 ms","Between The Channels":"No","Group error SF (red)":"Yes","Number of analog outputs":"2","Diagnostics short-circuit":"Disable / enable","With Voltage Outputs, Min.":"1 kΩ","Response to CPU/master STOP":"Output current and de-energized/substitute a value/keep last value","Reverse polarity protection":"Yes","Address space per module, max.":"4 byte","Cycle time (all channels) max.":"1.5 ms","from backplane bus 3.3 V DC, max.":"10 mA","Voltages at the outputs towards MANA":"15 V; max. 15 V continuous; 75 V for max. 1 s (mark to space ratio 1:20)","Between The Channels And Backplane Bus":"Yes","For Voltage Output Two-Wire Connection":"Yes; Without compensation of the line resistances","For Voltage Output Four-Wire Connection":"Yes","Between the channels and load voltage L+":"Yes","Voltage output, short-circuit protection":"Yes","Voltage, relative to output range, (+/-)":"0.2 %","from load voltage L+ (without load), max.":"130 mA","Installation altitude above sea level, max.":"5 000 m","Voltage output, short-circuit current, max.":"25 mA","With Voltage Outputs, Capacitive Load, Max.":"1 µF","Ambient air temperature-barometric pressure-altitude":"Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)","Resolution with overrange (bit including sign), max.":"14 bit; 1 to 5 V: 12 bit, ±10 V: 13 bit + sign","Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04":"Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,456.11","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e51396e92b3a763c69906944371f4bb2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=347104&mlfb=6AG1135-4FB01-2AB0"},"ai":{"faq":[{"question":"What is the maximum ambient temperature rating?","answer":"The module is rated for ambient operation up to 60 °C."},{"question":"What is the minimum ambient temperature rating?","answer":"The module is rated for ambient operation down to –25 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1135-4FB01-2AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1135-4FB01-2AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}