{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1135-4LB02-7AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1135-4LB02-7AB0","canonicalUrl":"https://aoctrl.com/siemens/6AG1135-4LB02-7AB0","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1135-4LB02-7AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIMATIC ET 200SP analog output module, 6AG1135-4LB02-7AB0, 2 channels, voltage outputs ±10 V / ±5 V / 1 V to 5 V, 24 V DC supply, -25 to 60 °C.","salesMarkdown":"## Cold-rated analog output for freezer-floor panels The 6AG1135-4LB02-7AB0: Each output delivers voltage signals across three selectable ranges: ±10 V, ±5 V, and 1 V to 5 V, with a 0.05 % accuracy relative to the output range. The ±10 V range covers most VFD speed-setpoint and valve-positioner signals; the 1-5 V range is common for legacy pneumatic I/P transducers still found in older cold-chain plants. ## Panel fit and wiring constraints The module body is 15 mm wide, 81 mm high, and 52 mm deep — it snaps onto the ET 200SP DIN-rail bus adapter alongside other I/O slices. Power draw is 1.2 W max from the backplane bus, plus 10 mA from the 3.3 V DC bus. The 24 V DC rated supply powers the output drivers; reverse-polarity protection is built in. The module sinks 0.2 ms for resistive loads, 0.5 ms for inductive or capacitive loads (up to 0.5 µF).","metaTitle":"Siemens 6AG1135-4LB02-7AB0 Analog Output Module, -25 to 60°C","metaDescription":"Siemens 6AG1135-4LB02-7AB0 analog output module with 2 outputs, voltage ranges ±10V/±5V/1-5V, 24V DC supply. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"Max.":"60 °C; = Tmax","Min.":"-25 °C; = Tmin","Depth":"52 mm","Width":"15 mm","Height":"81 mm","Remark":"7 byte","1 V to 5 V":"Yes","Group error":"Yes","-5 V to +5 V":"Yes","Short-circuit":"Yes","-10 V to +10 V":"Yes","Shielded, Max.":"200 m; 100 m if Twa < 2 ms","Weight, approx.":"40 g","lifecycle_stage":"current","Isochronous mode":"Yes","Power loss, max.":"1.2 W","Rated value (DC)":"24 V","Group diagnostics":"Disable / enable","For Inductive Load":"0.5 ms","For Resistive Load":"0.2 ms","For Capacitive Load":"0.5 ms; At max. 0.5 µF","Between The Channels":"No","Group error SF (red)":"Yes","Isolation tested with":"500 V DC","Number of analog outputs":"2","Diagnostics short-circuit":"Disable / enable","With Voltage Outputs, Min.":"1 kΩ","Response to CPU/master STOP":"Output current and de-energized/substitute a value/keep last value","Reverse polarity protection":"Yes","Address space per module, max.":"4 byte","Cycle time (all channels) max.":"0.5 ms; At max. 0.5 µF","Diagnostic information readable":"Yes","from backplane bus 3.3 V DC, max.":"10 mA","Voltages at the outputs towards MANA":"15 V; max. 15 V continuous; 75 V for max. 1 s (mark to space ratio 1:20)","Between The Channels And Backplane Bus":"Yes","For Voltage Output Two-Wire Connection":"Yes","For Voltage Output Four-Wire Connection":"Yes","Between the channels and load voltage L+":"Yes","Voltage output, short-circuit protection":"Yes","Voltage, relative to output range, (+/-)":"0.05 %","from load voltage L+ (without load), max.":"80 mA","Installation altitude above sea level, max.":"5 000 m","Voltage output, short-circuit current, max.":"25 mA","With Voltage Outputs, Capacitive Load, Max.":"0.5 µF","Ambient air temperature-barometric pressure-altitude":"Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)","Resolution with overrange (bit including sign), max.":"16 bit; 15 bit + sign","Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04":"Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e51396e92b3a763c69906944371f4bb2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=411627&mlfb=6AG1135-4LB02-7AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6AG1135-4LB02-7AB0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1135-4LB02-7AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1135-4LB02-7AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}