{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1136-6AB00-2CA1","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1136-6AB00-2CA1","canonicalUrl":"https://aoctrl.com/siemens/6AG1136-6AB00-2CA1","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1136-6AB00-2CA1","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIPLUS ET 200SP analog input module, 6AG1136-6AB00-2CA1, 24 V DC, 14-byte input / 5-byte output, SIL 3, current production.","salesMarkdown":"The 6AG1136-6AB00-2CA1: This is a current-production SIPLUS analog input module for the Siemens ET 200SP distributed I/O system. It takes one slice in the base unit (BU type A0 or A1) and runs on 24 V DC with a minimum tolerance of L+ minus 1.5 V. The module provides 14 bytes of input data and 5 bytes of output data, mapped to work with S7-300/400F safety CPUs. It uses a sigma-delta measurement principle and supports integration times from 1x to 64x oversampling cycles. Power draw is 2 W typical. On the status side, you get a green RUN LED, red ERROR and channel diagnostic LEDs, plus a green/yellow module diagnostics LED. The module includes wire-break detection, diagnostic alarms, and firmware update capability over the backplane. If you are sourcing this against a BOM line, the standard counterpart is the 6ES7136-6AB00-0CA1. The SIPLUS variant adds extended temperature range and conformal coating for harsh environments. Both use the same base units, so a swap in the field for a standard unit is possible if the environmental rating isn't required. ## Safety and diagnostics Rated SIL 3. No module-specific interrupt (MSI) simplifies safety integration. Diagnostic coverage includes per-channel status LEDs, a module diagnostic LED, and a diagnostic alarm that signals wire breaks and other faults. The maximum encoder/sensor supply current is 300 mA total across all channels.","metaTitle":"Siemens 6AG1136-6AB00-2CA1 SIPLUS ET 200SP Analog Input, 24","metaDescription":"Current-production SIPLUS analog input module for ET 200SP. 14-byte input, 5-byte output, diagnostic LEDs, SIL 3. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"MSI":"No","24 V":"Yes; min. L+ (-1.5 V)","Depth":"58 mm","Width":"15 mm","title":"6AG1136-6AB00-2CA1","Height":"73 mm","Inputs":"14 byte; S7-300/400F CPU, 13 byte","Outputs":"5 byte; S7-300/400F CPU, 4 byte","RUN LED":"Yes; green LED","I&M data":"Yes; I&M0 to I&M3","ERROR LED":"Yes; red LED","Step: low":"Yes; 2x / 4x conversion cycle time","0 to +10 V":"Yes","Step: High":"Yes; 32x / 64x conversion cycle time","Step: None":"Yes; 1x conversion cycle time","Wire-break":"Yes","description":"SIPLUS ET 200SP F-AI 4xU 0..10V HF based on 6ES7136-6AB00-0CA1 with conformal coating, -30…+60 °C, fail-safe analog inputs, up to PL e (ISO 13849), up to SIL 3 (IEC 61508)","Oversampling":"No","Step: Medium":"Yes; 8x / 16x conversion cycle time","Shielded, Max.":"200 m","Parameterizable":"Yes","Weight, approx.":"48 g","lifecycle_stage":"current","Diagnostic alarm":"Yes","Power loss, typ.":"2 W","Rated value (DC)":"24 V","usable BaseUnits":"BU type A0, A1","Limit value alarm":"No","Automatic encoding":"Yes","Cyclic Measurement":"Yes","FW update possible":"Yes","Average value filter":"Yes","Between The Channels":"No","Diagnostics function":"Yes","Output current, max.":"300 mA; total current of all encoders/channels","Integration time (ms)":"20 / 16,667","Isolation tested with":"707 V DC (type test)","Measurement principle":"Sigma Delta","SIL acc. to IEC 61508":"SIL 3","Channel status display":"Yes; green LED","For Module Diagnostics":"Yes; green/red DIAG LED","For Channel Diagnostics":"Yes; red LED","For Voltage Measurement":"Yes","For voltage measurement":"4","Number of analog inputs":"4","Short-circuit protection":"Yes","between the inputs (UCM)":"10 Vpp","Common mode voltage, max.":"10 V","Current consumption, max.":"0.4 A","Number of smoothing levels":"7","Calibration possible in RUN":"No","Reverse polarity protection":"Yes","Vertical Installation, Max.":"50 °C; = Tmax","Vertical Installation, Min.":"-30 °C; = Tmin","Input resistance (0 to 10 V)":"16 kΩ","Horizontal Installation, Max.":"60 °C; = Tmax; +70 °C with configured empty slots to the left and right of the module","Horizontal Installation, Min.":"-30 °C; = Tmin (incl. condensation/frost)","Monitoring the supply voltage":"Yes","Common mode interference, min.":"70 dB","Electronic coding element type H":"Yes","Category according to ISO 13849-1":"Cat. 4","Current consumption (rated value)":"0.38 A","Integration time, parameterizable":"Yes","Reparameterization possible in RUN":"No","permissible range, lower limit (DC)":"19.2 V","permissible range, upper limit (DC)":"28.8 V","Between The Channels And Backplane Bus":"Yes","Power available from the backplane bus":"70 mW","Voltage, relative to input range, (+/-)":"0.1 %","Monitoring of the supply voltage (PWR-LED)":"Yes; green PWR LED","Performance level according to ISO 13849-1":"PLe","Installation altitude above sea level, max.":"4 000 m","Protection against fouling acc. to EN 60664-3":"Yes; Type 1 protection","power supply according to NEC Class 2 required":"No","Low demand mode: PFDavg in accordance with SIL3":"< 5.00E-05","Linearity error (relative to input range), (+/-)":"0.1 %","Temperature error (relative to input range), (+/-)":"0.023 %/K","Ambient air temperature-barometric pressure-altitude":"Restrictions for installation altitudes > 2 000 m, see entry ID: 109771992","Resolution with overrange (bit including sign), max.":"16 bit","STEP 7 TIA Portal configurable/integrated from version":"see entry ID: 109746275","High demand/continuous mode: PFH in accordance with SIL3":"< 1.00E-09 1/h","Color code for module-specific color identification plate":"CC00","Resistant to commercially available coolants and lubricants":"Yes; Incl. diesel and oil droplets in the air","Between The Channels And The Power Supply Of The Electronics":"Yes","Interference voltage suppression for interference frequency f1 in Hz":"50 / 60 Hz","Permissible Input Voltage For Voltage Input (Destruction Limit), Max.":"35 V","Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)":"0.1 %","Series mode interference (peak value of interference < rated value of input range), min.":"40 dB","Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04":"Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)","Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A":"Yes; Conformal coating, Class A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e51396e92b3a763c69906944371f4bb2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1536551&mlfb=6AG1136-6AB00-2CA1"},"ai":{"faq":[{"question":"What is the closest functional second-source?","answer":"The standard ET 200SP analog input module (6ES7136-6AB00-0CA1) is the closest functional equivalent. The SIPLUS variant adds extended temperature range and conformal coating for harsh environments. Both share the same form factor and base unit compatibility."},{"question":"Does this module support module-specific interrupts (MSI)?","answer":"No, MSI is not supported. This simplifies integration in safety applications where interrupt handling is often kept minimal."},{"question":"Will this module drop into a panel specified around the standard 6ES7136-6AB00-0CA1 without rewiring?","answer":"Yes. The SIPLUS variant uses the same base units (BU type A0 or A1) and has identical dimensions (15 mm width, 73 mm height, 58 mm depth). No rewiring is needed for a direct swap."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1136-6AB00-2CA1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1136-6AB00-2CA1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}