{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1138-4FB04-2AB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1138-4FB04-2AB0","canonicalUrl":"https://aoctrl.com/siemens/6AG1138-4FB04-2AB0","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1138-4FB04-2AB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIPLUS ET 200S, F-DQ safety output module, 4 digital transistor outputs, 24 V DC, SIL 3 / Cat. 4, rated -25 to 60 °C, 4 A per channel.","salesMarkdown":"## Safety output module for harsh environments The Siemens 6AG1138-4FB04-2AB0 is a SIPLUS variant of the ET 200S F-DQ safety output module, built to survive the same crusher vibration and abrasive dust that kills standard electronics. It carries SIL 3 per IEC 61508 and Category 4 per EN 954-1, so it is rated for safety functions that demand fault-tolerant shutdown — think emergency-stop circuits, guard-door monitoring, or press-brake control in a mill. Four transistor outputs, each rated 4 A up to 40 °C and 5 A up to 55 °C, with a module total of 6 A max. That means you can drive contactors or solenoid valves directly without an interposing relay, as long as the load current per channel stays inside the thermal limit. ## Wiring and fault detection in the panel Snaps onto the ET 200S DIN-rail profile — the 30 mm width leaves room for adjacent I/O slices in a crowded enclosure. Wiring is screw terminal; the 24 V DC load supply feeds the module separately from the backplane bus, which draws 28 mA max at 3.3 V DC. Built-in wire-break detection (lower limit 12 Ω, upper limit 1 kΩ) and short-circuit detection let the module flag a failed field connection before the safety function is compromised. The group error SF (red LED) pulls the diagnostics bus — the PLC sees the fault without scanning each channel. ## Thermal limits and cable runs The output current derates at the high end: 4 A at 60 °C, same as at 40 °C, but the 55 °C point allows 5 A — so if the cabinet runs hot but stays under 55 °C, you get the extra amp per channel. Cable runs up to 500 m shielded or unshielded — long enough to reach field actuators across a conveyor line or a processing floor. Typical power loss is 3.5 W, manageable without forced cooling in a standard IP20 cabinet.","metaTitle":"Siemens 6AG1138-4FB04-2AB0 SIPLUS ET 200S F-DQ, SIL 3, 4 DO","metaDescription":"Siemens SIPLUS ET 200S F-DQ safety output module, 4 digital outputs, SIL 3 / Cat. 4, 24 V DC, 4 A per channel, rated -25 to 60 °C.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"52 mm","Width":"30 mm","Height":"81 mm","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$562.61","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e51396e92b3a763c69906944371f4bb2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=250860&mlfb=6AG1138-4FB04-2AB0","alternativesUrl":"https://aoctrl.com/api/mcp/products/6AG1138-4FB04-2AB0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1138-4FB04-2AB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1138-4FB04-2AB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}