{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"6AG1153-1AA03-2XB0","brand":"Siemens","brandSlug":"siemens","productSlug":"6AG1153-1AA03-2XB0","canonicalUrl":"https://aoctrl.com/siemens/6AG1153-1AA03-2XB0","factsUrl":"https://aoctrl.com/api/mcp/products/6AG1153-1AA03-2XB0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 6AG1153-1AA03-2XB0, PROFIBUS DP Interface Module (IM 153-1), 12 Mbit/s, RS-485, 3 W, IP20.","salesMarkdown":"## PROFIBUS DP Head End for ET 200M The 6AG1153-1AA03-2XB0: Power draw is 350 mA at 24 VDC typical with a 3 W loss, and it delivers 90 mA on the interface output for bus-powered slaves. Backplane current from the 5 V bus runs up to 1 A. Two specs that matter for the panel: the I2t rating of 0.1 A²·s guides upstream fuse selection — treat it as a very small let-through, so a quick-blow 1 A fuse can protect the bus without nuisance trips. The module also survives a 5 ms mains drop without losing state. When the bus comes back from a power loss, it recovers with min. cold restart at -25 °C — fine for most climate-controlled racks. For compliance documentation: the evidence doesn't list RoHS/REACH/UL certificates, but as a current Siemens catalog item the standard declarations can be pulled from the SIOS database or your rep. The module is isolated at 500 V, so it meets basic galvanic isolation for the bus segment. ## DIN Rail Mount, 40 mm Width The module clips onto DIN rail at 40 mm wide and 125 mm deep. The 9-pin sub-D socket faces the cable entry — plan for cable bend radius below the rail. Addresses 1 to 125 are settable, and baud rate is auto-detected.","metaTitle":"Siemens 6AG1153-1AA03-2XB0 PROFIBUS DP Interface, 12 Mbit/s","metaDescription":"Siemens 6AG1153-1AA03-2XB0 PROFIBUS DP IM 153-1 for ET 200M. 128-byte I/O, 12 Mbit/s, RS485. Active production. I2t 0.1 A²·s, -40 to 70 °C. Source to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["PLCs (Programmable Logic Controllers)"],"specifications":{"I2t":"0.1 A²·s","Max.":"70 °C","Min.":"-40 °C","Depth":"117 mm","Width":"40 mm","title":"6AG1153-1AA03-2XB0","Height":"125 mm","Inputs":"128 byte","STEP 7":"STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file","TCP/IP":"No","Outputs":"128 byte","GSD file":"(for DPV1) SIEM801D.GSD; SI01801D.GSG","description":"SIPLUS ET 200M IM153-1 based on 6ES7153-1AA03-0XB0 with conformal coating, -40…+70 °C, start up -25 °C, interface for ET 200M, for max. 8 S7-300 modules","SYNC capability":"Yes","Weight, approx.":"360 g","lifecycle_stage":"current","Power loss, typ.":"3 W","Rated value (DC)":"5 V","FREEZE capability":"Yes","Inrush current, typ.":"2.5 A","At cold restart, min.":"-25 °C","Isolation tested with":"Isolation voltage 500 V","Transmission procedure":"RS 485","IP degree of protection":"IP20","Transmission rate, max.":"12 Mbit/s","Design of the connection":"9-pin sub D socket","Current consumption, max.":"350 mA; At 24 V DC","Automatic Baud Rate Search":"Yes","Potential separation exists":"Yes","Number of node addresses, max.":"1 to 125 permitted","for backplane bus (5 V DC), max.":"1 A","Bus protocol/transmission protocol":"PROFIBUS DP to EN 50170","permissible range, lower limit (DC)":"20.4 V","permissible range, upper limit (DC)":"28.8 V","Output current of the interface, max.":"90 mA","Automatic Detection Of Transmission Rate":"Yes","Mains/voltage failure stored energy time":"5 ms","Installation altitude above sea level, max.":"5 000 m","STEP 7 configurable/integrated from version":"see entry ID: 109746275","Number of modules per DP slave interface, max.":"8","Direct data exchange (slave-to-slave communication)":"Yes; Sender","Ambient air temperature-barometric pressure-altitude":"Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)","External Protection For Power Supply Lines (Recommendation)":"not necessary","Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04":"Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a8a36b8f10a30a3bcb80310048e52ad2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=388128&mlfb=6AG1153-1AA03-2XB0"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/6AG1153-1AA03-2XB0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/6AG1153-1AA03-2XB0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}